Dependencies and troubleshooting

Direct Connect Bridge. Mirrors the Modbus Bridge page Dependencies and troubleshooting section for section. It replaces the old Scheduler: troubleshooting and examples page; the examples are now on Examples.

Dependency matrix

✔ = required for a meaningful value or for the action to work. ◐ = optional, changes the result. Blank = not needed.

Conditions

A condition whose sensor has no value is false, for every operator. So a sensor that depends on something you have not set up makes its condition fail. The sensors are listed on Conditions.

Sensors Gateway poll Modbus client (this bridge) Constants Meter + utility + tariff NEM region / HA price entity PV location HA instance + exposed entity
battery.soc_pct, battery.power_w, grid.*, solar.power_w, load.power_w, generator.power_w, mode.name, status.*, bridge.latency_ms ✔
battery.status ✔
battery.capacity_kwh, stored_kwh, remaining_kwh ✔ ✔ (battery capacity; 0 = unset)
battery.time_to_*_now_min ✔ ✔ (capacity, SoC targets)
battery.time_to_charge_min, time_to_discharge_min (at max rate) ✔ ◐ (Model 702 rating, else the max power constant) ✔
solar_forecast.day_pct, vs_expected_pct ✔ (today's solar) ✔
weather.*, solar_forecast.* ✔ (+ kWp, tilt, azimuth)
solar.today_kwh ✔
tariff.buy_rate, sell_rate, season, time_period, tier, import_billable ✔ ◐ (dynamic tariff)
tariff.*_window_active ✔ (the window defined on the tariff)
tariff.spot_price, feed_in_price ◐ (dynamic tariff) ✔ ◐ (HA price entity)
demand.*, bonus.*, energy.*, tariff.export_charge_* ✔ (grid power, each tick) ✔ (those charges and windows) ◐ (dynamic tariff)
fixed.* ✔ (fixed charges)
service.* ✔ (utility; unset permissions read 1)
system.* ◐ (derived from the aGate)
const.* ✔ (defaults exist)
ha:<instance>:<entity> ✔

Where to set each one:

Dependency Where
Gateway poll Settings → Gateways (host, enabled). A gateway whose last poll is older than three poll intervals (at least 90 s) is not evaluated at all.
Modbus client (this bridge) Control → Modbus client: on, with the aGate's Modbus TCP Server (aGate :502) reachable and answering SunSpec.
Constants Settings → Automation → Automation Constants
Meter, utility, tariff Energy & costs (meters, utilities, tariffs); see Energy and costs
NEM region, HA price entities, PV location Settings → Integrations
HA instance and exposed entities Settings → Integrations (instance) and the Home Assistant tab (expose)
Site timezone Settings → Setup → Where is this site?

Actions

Battery action Gateway reachable (local) Modbus client (this bridge) ready Cloud credentials HA instance Notification device
Set operating mode ✔
Smart circuit on/off ✔
Go off-grid / reconnect ✔
Set reserve SoC — never runs (#129) (listed as needed, not used)
Notify (Home Assistant) ✔ ✔ (enabled)
Force charge / discharge / standby ✔ (on, library installed, a host, a SunSpec read that succeeds)
No battery action (HA only)
Home Assistant action Needs
+ notify a notification device. The button is disabled until you add one.
+ entity a Home Assistant instance. The guided picker lists only exposed, controllable entities; Advanced (raw service)… takes any domain, service and entity.

The scheduler does not use MQTT. Neither the engine nor its worker publishes or reads MQTT; schedules run without a broker. MQTT entities for schedules are planned (#128).

The Force item in the Battery action list is disabled, with the reason, while the Modbus client (this bridge) is not available. A schedule saved earlier with a force action still runs; see the next section for what that does.

Troubleshooting

Start with two tools on the Scheduler tab:

  • ⋮ → Test against live on the card. It says Would fire or Would not fire, with the reason ("outside its window", "not one of its days of the week", "already fired this occurrence", "entry conditions not met", …) and each top-level condition row with its live value. It reads the default gateway and the container's clock; see Conditions → Test Verification.
  • The History view. Filter by gated, error, missed or deferred to see what the scheduler decided, and why.

A condition is always false

Cause How to tell Fix
The sensor has no value the editor's Test marks the row amber, no value; Test against live shows "—" Set up what the sensor needs (matrix above).
A Lookup sensor has no value the row fails Set that sensor up, or use a Value.
Wrong unit tariff.buy_rate is $/kWh; tariff.spot_price is c/kWh Check the sensor's label in the picker and the live value.
in used on text text never matches a number list Use matchlist for names.
!= on a missing value != is false with no value Use a positive test, such as status.vpp == 0.
The text does not match == ignores case, but the words must match Use like with * for a partial match.
The tariff window is not defined a window flag reads None when the tariff has no such window Define the window on the tariff.
Second gateway its tariff sensors come from its own meter, else the default meter Connect the gateway to the right meter.
Tested on the wrong gateway Test uses the top-bar gateway; Test against live always the default gateway Pick the schedule's gateway in the top bar before Test.

A condition is always true when it should not be

Cause Fix
Before 0.5.4, a Home Assistant entity that was unavailable or unknown read 0, so price < 10 passed (#167, fixed in 0.5.4) Update. Since 0.5.4 such an entity has no value and the condition is false.
grid.connected is derived from grid power being non-zero: grid.connected == 0 is true whenever the grid power is exactly 0 W Use status.off_grid == 1 for an outage.
service.* permissions read 1 (allowed) when not set on the utility Set them on the utility.
An empty not_in list is true Fill the list.
An exit block sent through the API as an empty ALL group is true at once Send an empty list for "no exit conditions".

An action is refused or does nothing

Symptom Cause Fix
Force is greyed unavailable in the list The Modbus client (this bridge) is off, not installed, or cannot read SunSpec from the Modbus TCP Server (aGate :502) Fix it under Control → Modbus client. The reason is shown under the list.
History shows fired for a force, but the battery did not move A force refused by the Modbus client (this bridge) path is recorded as fired: its reason text is not recognised as a failure (#191) Read the fired row's text: "force charge: This bridge's Modbus client is off…" or "could not connect…". Check the Logs tab.
History shows fired for Set operating mode or Go off-grid, but nothing changed A write the aGate answered with a non-zero result is also recorded as fired (#191) Read the row: "mode -> tou: {'ok': False, …}".
Set reserve SoC shows fired but nothing changed The action is always skipped, even with cloud credentials (#129) Set the reserve in the FranklinWH app, or from Control.
A smart circuit turned on when the schedule said Off, or the gateway went off-grid when it said reconnect Before 0.5.5 the form saved Off as text that ran as on (#188, fixed in 0.5.5) Update, then check what such schedules did in History. Since 0.5.5 an On/Off value the bridge cannot read is refused, with no write.
The mode did not change back A mode change is not undone at the end of the window, unless restore on exit is set (API only) Add a second schedule, or set restore_on_exit. See Exit and release.
A force stopped early Its Target SoC, or its Duration (min): a Recurring windows schedule still has the hidden duration (90 for a new one), and the force stops after it (#160) Use Daily at time or Weekly at time for a force.
A force stopped when another schedule's window ended A force schedule's window end sends Release whether or not it fired, and whoever started the force (#189) Do not overlap force schedules on one gateway.
History shows error The action failed; the bridge retries while the window is open, waiting 30 s, then doubling up to 10 minutes If the window closes first, the run is logged as missed.
History shows deferred Another schedule won the gateway on the same tick, or If busy = defer and another force is running Change priorities, or If busy.
History shows waiting — "battery busy with another dispatch" If busy = wait It retries every tick while the window is open.
Run now acted on the wrong gateway With several gateways, Run now uses the gateway selected in the top bar Select the schedule's gateway, or Site, before Run now.
Stop released the wrong gateway Stop sends the release through the Modbus client (this bridge) to the default gateway's host, not the schedule's gateway (#192) Release from Control on the right gateway.

An entry never fires

Cause How to tell Fix
Disabled the card shows Off, Next: disabled Turn it on. Imported and duplicated schedules start disabled. A PUT without enabled turns it on (#168).
Outside its window or calendar Test against live: "outside its window", "not one of its days of the week", "before start date …" Check the trigger and its restrictions.
Already fired this occurrence Test against live: "already fired this occurrence" It fires at most once per window.
Gate never passes gated rows in History (once a day) with the failing values Fix the conditions; use Test.
Hold too long waiting row but no fire Shorten the hold, or check the gate is not flickering.
Another schedule wins deferred — "'' (priority N) holds battery this occurrence" Priority.
Exit condition already true Test against live may still say Would fire; the engine logs nothing and does not start Check End early when… with its Test.
An Always schedule ran once nothing after its first run, ever An Always schedule fires once and never again (#190). Use a repeating trigger.
Wrong gateway a schedule on Default gateway runs only on the first-registered gateway; if that gateway is disabled, it runs nowhere (#182) Bind the schedule to a gateway. See Targets.
Stale gateway data the gateway has not polled for three poll intervals (at least 90 s); its schedules are skipped silently Check the Network and Health tabs.
The window was short the scheduler ticks every 15 s by default; a one-minute window is always seen —
Paused pause does not hold a run: the next tick tries it again (#200) Disable the schedule instead.

A Home Assistant action did not run

Direct Connect only (from the old troubleshooting page, checked against the code):

  • Check its when: On entry, On exit or Entry & exit.
  • Check its guard. An action whose guard is false at that moment is skipped without a History row of its own.
  • A value in the message that cannot be read shows as ?; the message is still sent. %ha:…% placeholders are not replaced (#169).
  • A notify device that is switched off, or whose instance is gone, is skipped: the fired row's text says "notify skipped: …".
  • The Push notifications switch does not stop schedule notifications (#171).

Where the old sections went

The old Scheduler: troubleshooting and examples page now redirects here. Its sections:

Old section Now
What each condition needs Dependency matrix → Conditions
What each action needs Dependency matrix → Actions
Troubleshooting Troubleshooting
A schedule never fires An entry never fires
A condition is always false A condition is always false
An action is refused or does nothing An action is refused or does nothing
A Home Assistant action did not run A Home Assistant action did not run
Examples Examples
(whole page) this page and Examples
1. Low-battery alert Examples → Low-battery alert
2. Notify at the start and end of the peak window Examples → Notify at the start and end of the peak window
3. Overnight off-peak charge Examples → Overnight off-peak charge
4. Time-of-Use at peak, then back to Self-Consumption Examples → Time-of-Use at peak, then back to Self-Consumption
5. Only when Home Assistant says so Examples → 6. Weekend export, unless Home Assistant says you are away