Scheduler parity: Modbus Bridge vs Direct Connect

The two bridges' schedulers, compared behaviour by behaviour, so they can be aligned.

Behaviours Tested Untested Unclear
Modbus Bridge (scheduler pages, test plan at its main f2e9134, PR #217) 238 130 93 15
Direct Connect (Scheduler, test plan, 0.5.5) 266 106 119 41

Of the Modbus Bridge's 238 behaviours, this bridge has 74 the same, 121 that differ and is missing 55. It has 83 of its own (Direct Connect only). 13 more rows compare

Corrections from the Modbus Bridge's code check (2026-10-17)

This page read the Modbus Bridge side from its doc markers. That bridge's session has since checked them against its code (franklinwh-modbus-bridge PR #233):

  • 28 of the 83 "Direct Connect only" rows exist there too: 17 undocumented, 11 documented under other ids. Treat them as same or differs, not missing there.
  • Rows TRG-06, TRG-13, TRG-23, HAA-01 and PRI-01 described the Modbus Bridge wrongly; each row carries a note.
  • TRG-19 (next fire for long intervals) is the same bug in both (our #208).

The counts on this page have not been rebased on those corrections yet.

whole sections of the dependencies and examples pages, which carry no markers.

How it was built. Each row is one behaviour id. Ids are shared: where this bridge's page documents the counterpart of a Modbus Bridge behaviour, it uses the same id, even when the behaviour differs. Has / tested for the Modbus Bridge comes from its test plan; for this bridge from the markers in the Scheduler pages. The gap is a short note written while reading both bridges' code. The Modbus Bridge's claims are taken from its docs and were not re-verified against its code here; this bridge's side was read from its code, and the less obvious defects were reproduced with a mock (no hardware).

Column Meaning
# Behaviour id. "—" for a section-level comparison (no marker).
Page · heading This bridge's page and the heading both bridges share.
Modbus Bridge / Direct Connect yes / tested, yes / untested, yes / unclear or no.
Gap same, differs, missing here (Modbus Bridge only) or Direct Connect only, then the difference.
Why missing Missing here rows only: Not ported, Depends on, Transport limit, Design choice or Unknown, then the source. See Gap reasons and classes.
Class Differs rows only: behavioural (with what it writes) or variance, then why.
Issue The issue in this repository. Issues opened from this review are listed under Issues filed from this review.

Gap reasons and classes

Added to the table below: Why missing for the 55 missing here rows and Class for the 121 differs rows. Each was assigned from the code and docs cited in the row, the BACKLOG and the issues; nothing was run against a gateway or an emulator.

Why missing (55 rows)

Reason Rows What it means
Not ported 24 Not built here yet, and recorded as wanted (BACKLOG or an issue).
Depends on 23 Needs another missing piece first (named in the row): mostly catch-up, release policy, ownership, supervision.
Unknown 8 No record of why. Questions below.
Transport limit 0 None. Every missing behaviour can be built on the transports this bridge already uses: the force path is the same WSet model 704 on the Modbus TCP Server (aGate :502) through the Modbus client (this bridge) (battery_control.py:1-7), and the reserve and mode reads it needs are local (PROTOCOL.md). The two transport limits found sit in differs rows (dependency matrix): Direct Connect (:9000) has no battery force, and reserve (1405) is cloud-only.
Design choice 0 None recorded for a missing row. Run now ignoring conditions is recorded as by design in #162, but that row is a differs row (OUT-20).

Differs (121 rows)

Class Rows
Behavioural: battery write 68
Behavioural: other device or HA write 7
Behavioural: recorded outcome or notification 18
Behavioural: display only (timeline, Next, Test, buttons) 11
Implementation variance 16
Needs owner 1

Rule used. Variance means the same intent gives the same trigger, conditions, action, target, exit and recorded result by different code. Anything that could change a battery write, another device write or a recorded outcome is behavioural. Display-only rows that misstate when or where something runs are behavioural, ranked last.

Behavioural differences, ranked by risk

Battery writes first, then other device and HA writes, then the record, then display. Within a group, the order is a judgement of likelihood times effect, not a measurement.

Rank Row Writes Difference Issue
1 EXT-01 battery window close releases a force it never sent or does not own #189
2 EXT-05 battery never hands over; releases another's force #189
3 § 5. Peak-demand window battery overlapping force schedules release each other (#189) #189
4 RST-01 battery restart releases only the in-memory force, to the first gateway's host #192
5 OUT-24 battery Stop releases via the first gateway's host; no exit HA actions #192
6 EXT-20 battery shutdown releases to the first gateway's host #192
7 TGT-09 battery Run now forces the top-bar gateway, not the schedule's #193
8 RST-02 battery start-up default is notify: a force left by a crash keeps running (there: released) #199
9 RST-04 battery release_stale() never called #199
10 ACT-13 battery a refused force is logged fired and never retried #191
11 § An action is refused or does nothing battery refused writes logged fired (#191) #191
12 PRI-03 battery a later-ready force overrides a running one whatever the priority #196
13 EXT-04 battery delete does not release the running force #195
14 TRG-34 battery hidden 90 min duration cuts a window force short #160
15 ACT-17 battery time limit = duration_min x 60, hidden 90 min in windows #160
16 § 1. Evening top-up battery hidden duration ends the force (#160) #160
17 § 2. Evening peak discharge until the minimum SoC battery workaround for #160 changes the window #160
18 TRG-16 battery weekly with no days fires every day (Modbus Bridge: never) #198
19 TRG-23 battery monthly with no day fires every day #198
20 TRG-09 battery start = end is open all day: a force runs 24 h #198
21 ACT-04 battery empty power is a 0 W force #209
22 TRG-28 battery Always fires once ever, but releases on every falling edge #190
23 § An entry never fires battery Always fires once ever (#190) #190
24 TRG-27 battery Always fires on the rising edge, not continuously #190
25 TRG-29 battery stored occurrence never pruned keeps Always from firing again #190
26 TGT-10 battery unbound = first registered gateway, which moves #182
27 EXT-17 battery Release refused when the Modbus client (this bridge) is off; no read-back #174
28 § Dependency matrix battery force needs the Modbus client (this bridge): :9000 has no battery force (transport limit, HYBRID-CAPABILITIES); reserve write never runs (#129): 1405 is cloud-only (PROTOCOL.md) #129
29 CON-02 battery name order, priority only within a tick: decides which force runs #196
30 PRI-02 battery contest only within a tick, per resource #196
31 PRI-01 battery default If busy = override (there: defer); unknown values act as override
32 SEN-10 battery stale NEM price kept: price-gated forces run on old prices #207
33 SEN-04 battery grid.connected reads 0 at exactly 0 W: a grid gate can fire a force #206
34 § A condition is always true when it should not be battery conditions can pass when they should not (#206) #206
35 ACT-14 battery no WSetEna read-back check: a force can be recorded as sent when it did not take #139
36 ACT-03 battery % sized on 702 or a 5000 W fallback, no trusted rating: different watts written
37 ACT-10 battery W/kW not capped by the bridge at 702
38 PRI-07 battery busy = only dispatch rows of schedules or the widget; mode entries unchecked
39 PRI-08 battery defer gives up for the day; wait retries each tick #204
40 PRI-10 battery after a manual command ends, a deferred entry does not run
41 OUT-04 battery retry 30 s doubling to 600 s (there: 15, 30, 60 s); no notification #172
42 ACT-02 battery invalid actions saved; fail only at run #202
43 OUT-20 battery Run now ignores conditions (by design per #162) #162
44 ACT-05 battery percent accepted; any unknown unit is read as percent
45 TRG-30 battery falling edge sends Release (the Modbus Bridge does not re-check)
46 CND-27 battery a retry waits the whole hold again, delaying the force #203
47 SEN-08 battery undefined window is None (fails closed) not False: == 0 gates differ
48 TRG-22 battery no range check; day 0 = every day, so an invalid entry fires #202
49 TRG-08 battery the after-midnight part follows the opening day's calendar: a force may run on a day the Modbus Bridge skips
50 CND-22 battery multi-gateway: tariff/billing sensors from each gateway's own meter, so conditions can differ
51 CND-06 battery case-insensitive text: a condition can pass that fails there
52 CND-08 battery bracketed lists and text members parse differently: condition result can differ
53 CLK-01 battery each gateway's aGate clock: fire times differ when the container clock is not site time
54 CND-20 battery an empty ALL exit group stops the schedule ever starting
55 TRG-13 battery an overnight one-off keeps forcing past midnight
56 IDX-03 battery an edited power or action is not re-sent to a running force until the next window
57 TRG-11 battery stored days still restrict a one-off, so it may not fire
58 TGT-01 battery a stale or disabled gateway's schedules are not evaluated
59 TGT-11 battery unbound and bound contend as one group (two groups there)
60 ACT-19 battery form save keeps API-only keys (the Modbus Bridge drops target_soc): different force end
61 TRG-10 battery an unparsable window falls back to Fire at + duration instead of 00:00
62 ACT-15 battery WSetRvrtTms not written (the library writes WSetEna/WSetMod/WSetPct only); PICS Issue 4 calls it cosmetic
63 CLK-04 battery DST change applies up to 10 min late
64 EXT-07 battery exit already true: no start here; a brief force there
65 PRI-06 battery a loser does not fire again that occurrence
66 RST-03 battery stored occurrence: no re-fire after restart (there: re-dispatches)
67 PRI-13 battery claims per gateway, not per target
68 OUT-25 battery Stop with nothing running does not block the window; the entry can still fire
69 HAA-06 device/HA exit HA actions run at every window close, even if never fired #189
70 HAA-07 device/HA on-entry HA actions repeat on every retry #203
71 ACT-28 device/HA Run now runs HA actions of HA-only schedules
72 EXT-09 device/HA exit evaluated for every action kind (mode, HA-only)
73 EXT-12 device/HA restore_on_exit writes the mode back (the Modbus Bridge only audits) #162
74 ACT-23 device/HA missing mode accepted, fails and retries at run #202
75 HAA-01 device/HA invalid HA actions saved; skipped at run #202
76 OUT-18 record no failure notifications #172
77 OUT-13 record dispatch record holds successful forces only #139
78 TRG-40 record missed rows come from stale claims, not outages
79 TRG-41 record a window no tick saw leaves no missed row
80 CND-29 record gated logged once a day, two leaves
81 HAA-08 record guard skip leaves no log row
82 HAA-12 record HA failures folded into the run row; rarely fail the run
83 TGT-06 record History rows do not name the gateway #205
84 EXT-10 record exit row names no condition
85 PRI-14 record requester only in the dispatches table
86 OUT-01 record config changes logged as one word; import not logged
87 OUT-05 record recovery logged as plain fired; no notification #172
88 TRG-24 record invalid cron saved instead of rejected; never fires in either #202
89 CND-02 record import accepts unknown sensors silently #202
90 CND-26 record hold over 86400 s accepted
91 CND-35 record no warning for an unexposed HA entity #202
92 HAA-02 record incomplete rows kept and skipped at run with a reason
93 HAA-10 record %ha:…% placeholders not substituted #169
94 IDX-06 display timeline omits interval schedules and ignores the gateway #161
95 TRG-19 display Next shows a time the engine does not fire at #208
96 TRG-32 display Next uses the container clock #161
97 IDX-07 display one-off drawn only on its date (the Modbus Bridge draws it every week)
98 TRG-33 display active_now also needs a fire; changes Stop/Run now
99 CND-30 display editor Test evaluates the top-bar gateway, not the schedule's
100 CND-31 display Test against live: default gateway, container clock, top-level rows only #161
101 TGT-02 display site fan-out only through the API #162
102 TGT-15 display timeline is one list, not per gateway #161
103 OUT-19 display Stop shown on a different rule, container clock #161
104 CLK-02 display previews on the container clock #161

Questions for the owner

Unknown (missing here, no record of why):

  1. Legacy format (CON-07, ACT-07, ACT-08, ACT-09; also EXT-16). These describe the Modbus Bridge's legacy / v2 split and legacy power_pct entries. This bridge never had either. Mark them not applicable and drop them from the parity count?
  2. API oneoff trigger (TRG-35). The Modbus Bridge has an API-only oneoff type with an ISO fire_at; here a one-off is a date window. Wanted, or not applicable?
  3. Rating trust model (ACT-11, and ACT-12, OUT-17 that build on it). No record says whether a calibrated / peak-confirmed rating gate is wanted here. #162 lists the overshoot guard but not the trust model. Port it?
  4. Power staging (ACT-16). The Modbus Bridge stages power and re-sends the active command; here a force is one BatteryCommand. Not applicable?
  5. Mock warning in the form (TGT-13). Wanted?

Needs owner (differs):

  1. Storm example (§ 4. Storm forecast). Is weather.condition matching *thunder* right, or should the example use weather.code in 95, 96, 99 (and should weather.code be in the picker)?

Behaviours

# Page · heading Modbus Bridge Direct Connect Gap Why missing Class Issue
IDX-01 index · The entry list yes / untested yes / untested differs: DC shows all by default variance: list filter default only
IDX-02 index · The entry list yes / untested yes / untested differs: DC opens an unsaved 'Copy of' form, disabled variance: both end with a disabled copy; only the save step differs
IDX-03 index · The entry list yes / tested yes / untested differs: DC confirms but does not re-send a running force; change applies next window behavioural (battery): an edited power or action is not re-sent to a running force until the next window
IDX-04 index · Templates, export and import yes / untested yes / untested differs: DC loads disabled, no enable prompt variance: templates load disabled in both
IDX-05 index · Templates, export and import yes / tested yes / tested same: DC also exports/imports its own franklinwh-local-schedules
IDX-06 index · Visual timeline yes / tested yes / tested differs: DC: one list, interval/cron/always not drawn, not per gateway behavioural (display): timeline omits interval schedules and ignores the gateway #161
IDX-07 index · Visual timeline yes / tested yes / untested differs: DC draws a one-off only on its date behavioural (display): one-off drawn only on its date (the Modbus Bridge draws it every week)
IDX-08 index · The entry list no yes / tested Direct Connect only: Turn on/off partial PUT merged (fixed 0.5.2) #157
IDX-09 index · The entry list no yes / unclear Direct Connect only: PUT without enabled re-enables #168
IDX-10 index · Templates, export and import no yes / tested Direct Connect only: eleven presets incl. four force presets (MB has four different templates)
IDX-11 index · Visual timeline no yes / untested Direct Connect only: timeline ignores gateway and uses container clock #161
IDX-12 index · Using schedules from Home Assistant (Direct Connect only) no yes / unclear Direct Connect only: Pause/Resume API ineffective (does not hold a run, tick ignores paused) #200
CON-01 concepts · The tick yes / untested yes / tested same: DC cadence configurable 5-60 s
CON-02 concepts · The tick yes / tested yes / untested differs: DC reads all by name; priority only in a same-tick contest behavioural (battery): name order, priority only within a tick: decides which force runs
CON-03 concepts · The tick yes / tested yes / tested same: none
CON-04 concepts · The tick yes / tested yes / tested same: DC: per-resource claims (battery, grid, circuit)
CON-05 concepts · The tick yes / untested yes / untested differs: DC waits for the next tick (<=15 s) variance: same write, up to one tick (<=15 s) later
CON-06 concepts · The tick yes / unclear yes / untested differs: DC has no module switch variance: the Modbus Bridge switch hides routes but the engine still runs: same writes
CON-07 concepts · Legacy and v2 entries yes / untested no missing here: DC has one format Unknown: none found; the page states one format, not why
CON-08 concepts · The tick no yes / tested Direct Connect only: stale/disabled/never-polled gateway skipped (max(90 s, 3 polls))
CON-09 concepts · Window, activation and run no yes / tested Direct Connect only: stored occurrences: fire once per occurrence, retry while failed
CON-10 concepts · What the engine remembers no yes / untested Direct Connect only: last fired occurrence, runs and dispatches survive restart
TRG-01 triggers · Fire-based triggers: the active window yes / tested yes / tested same: none
TRG-02 triggers · Fire-based triggers: the active window yes / untested yes / untested differs: DC: the one Fire at minute; force has no own timer, released at next tick after variance: both release about a minute after a zero-duration fire
TRG-03 triggers · Fire-based triggers: the active window yes / tested yes / untested same: none
TRG-04 triggers · Recurring windows yes / tested yes / untested same: untested in DC
TRG-05 triggers · Recurring windows yes / tested yes / tested same: none
TRG-06 triggers · Recurring windows yes / untested yes / tested differs: DC: each window is its own occurrence (fires once per window) Modbus Bridge check (their PR #233): separate windows each fire there too; only back-to-back windows merge. variance: both fire once per window
TRG-07 triggers · Recurring windows yes / tested yes / untested same: DC: end <= start wraps
TRG-08 triggers · Recurring windows yes / untested yes / untested differs: DC attributes the after-midnight part to the day it opened behavioural (battery): the after-midnight part follows the opening day's calendar: a force may run on a day the Modbus Bridge skips
TRG-09 triggers · Recurring windows yes / tested yes / unclear differs: DC: start == end is a 24-hour window behavioural (battery): start = end is open all day: a force runs 24 h #198
TRG-10 triggers · Recurring windows yes / untested yes / untested differs: DC: 24:00 = end of day; unparsable window dropped, empty list falls back to fire_at behavioural (battery): an unparsable window falls back to Fire at + duration instead of 00:00
TRG-11 triggers · One-off date window yes / tested yes / tested differs: DC: stored days still restrict; form shows windows that are ignored behavioural (battery): stored days still restrict a one-off, so it may not fire
TRG-12 triggers · One-off date window yes / tested yes / tested same: DC card has no 'passed' label
TRG-13 triggers · One-off date window yes / untested yes / untested differs: DC runs past midnight into the next date Modbus Bridge check (their PR #233): an overnight one-off there also runs from 00:00 on its own date. behavioural (battery): an overnight one-off keeps forcing past midnight
TRG-14 triggers · Daily at time yes / tested yes / tested same: none
TRG-15 triggers · Daily at time yes / untested yes / untested same: form max 1440
TRG-16 triggers · Weekly at time yes / tested yes / tested differs: DC: no days = every day behavioural (battery): weekly with no days fires every day (Modbus Bridge: never)
TRG-17 triggers · Every N minutes yes / tested yes / tested same: none
TRG-18 triggers · Every N minutes yes / untested yes / untested same: untested in DC
TRG-19 triggers · Every N minutes yes / untested yes / unclear differs: DC next_fire disagrees with the window behavioural (display): Next shows a time the engine does not fire at #208
TRG-20 triggers · Every N minutes yes / tested yes / untested same: none
TRG-21 triggers · Monthly / calendar yes / tested yes / tested same: none
TRG-22 triggers · Monthly / calendar yes / tested yes / untested differs: DC does not validate; day 0/None = no restriction behavioural (battery): no range check; day 0 = every day, so an invalid entry fires
TRG-23 triggers · Monthly / calendar yes / untested yes / untested differs: DC: no day of month = fires every day Modbus Bridge check (their PR #233): monthly with no day fires on the 1st there. behavioural (battery): monthly with no day fires every day #198
TRG-24 triggers · Custom cron yes / tested yes / untested differs: DC accepts it; never fires behavioural (record): invalid cron saved instead of rejected; never fires in either
TRG-25 triggers · Custom cron yes / untested yes / untested same: untested in DC
TRG-26 triggers · Custom cron yes / tested yes / tested same: none
TRG-27 triggers · Always evaluate yes / tested yes / tested differs: DC: window = conditions; fires on rising edge behavioural (battery): Always fires on the rising edge, not continuously
TRG-28 triggers · Always evaluate yes / untested yes / unclear differs: DC: once EVER (stored occurrence, survives restart); falling edges still release behavioural (battery): Always fires once ever, but releases on every falling edge #190
TRG-29 triggers · Always evaluate yes / unclear yes / unclear differs: DC: stored occurrence row, never pruned behavioural (battery): stored occurrence never pruned keeps Always from firing again #190
TRG-30 triggers · Always evaluate yes / untested yes / tested differs: DC does release on the falling edge behavioural (battery): falling edge sends Release (the Modbus Bridge does not re-check)
TRG-31 triggers · Quick presets yes / untested yes / untested same: DC preset list differs
TRG-32 triggers · Next fire yes / tested yes / tested differs: DC searches 366 days; container clock behavioural (display): Next uses the container clock #161
TRG-33 triggers · Next fire yes / untested yes / tested differs: DC: inside window AND fired this occurrence behavioural (display): active_now also needs a fire; changes Stop/Run now
TRG-34 triggers · Editing a trigger in the form yes / untested yes / unclear differs: DC: hidden duration_min (default 90) also limits a scheduled force behavioural (battery): hidden 90 min duration cuts a window force short #160
TRG-35 triggers · Editing a trigger in the form yes / untested no missing here: DC has no API oneoff type Unknown: none found; no API oneoff type here
TRG-36 triggers · After an outage or a restart (catch-up) yes / tested no missing here: DC: stale gateway skipped; no outage record Not ported: ORCH 2b (catch-up on outage); #162 #162
TRG-37 triggers · After an outage or a restart (catch-up) yes / tested no missing here: no catch-up Not ported: ORCH 2b (catch-up); #162 #162
TRG-38 triggers · After an outage or a restart (catch-up) yes / tested no missing here: no catch-up Not ported: ORCH 2b (catch-up after restart); #162 #162
TRG-39 triggers · After an outage or a restart (catch-up) yes / tested no missing here: no catch-up Depends on: catch-up (TRG-37) #162
TRG-40 triggers · After an outage or a restart (catch-up) yes / tested yes / tested differs: DC: claimed runs whose window ended >120 s ago marked missed behavioural (record): missed rows come from stale claims, not outages
TRG-41 triggers · After an outage or a restart (catch-up) yes / untested yes / untested differs: DC: an unclaimed window leaves no missed row behavioural (record): a window no tick saw leaves no missed row
TRG-42 triggers · After an outage or a restart (catch-up) yes / untested no missing here: no missed policy Depends on: catch-up missed policy (TRG-37) #162
TRG-43 triggers · After an outage or a restart (catch-up) yes / tested no missing here: no late fire Depends on: catch-up (TRG-37) #162
TRG-44 triggers · After an outage or a restart (catch-up) yes / untested no missing here: no late fire Depends on: catch-up (TRG-37) #162
TRG-45 triggers · After an outage or a restart (catch-up) yes / untested no missing here: no late fire Depends on: catch-up (TRG-37) #162
TRG-46 triggers · After an outage or a restart (catch-up) yes / untested no missing here: no late fire Depends on: catch-up (TRG-37) #162
TRG-47 triggers · After an outage or a restart (catch-up) yes / untested no missing here: no catch-up Depends on: catch-up (TRG-37) #162
TRG-48 triggers · After an outage or a restart (catch-up) yes / untested no missing here: no missed policy Depends on: catch-up (TRG-37) #162
TRG-49 triggers · Summary no yes / untested Direct Connect only: calendar restrictions apply to every trigger type
TRG-50 triggers · Recurring windows no yes / tested Direct Connect only: start/end date range restriction with a reason
TRG-51 triggers · One-off date window no yes / unclear Direct Connect only: One-off ignores its Time windows; no date = every day #198
TRG-52 triggers · Next fire no yes / unclear Direct Connect only: next_fire/active_now on container clock #161
TRG-53 triggers · Editing a trigger in the form no yes / untested Direct Connect only: trigger type change seeds defaults
TRG-54 triggers · After an outage or a restart (catch-up) no yes / untested Direct Connect only: no late fire ever #162
TRG-55 triggers · After an outage or a restart (catch-up) no yes / tested Direct Connect only: stale snapshot skips evaluation
TRG-56 triggers · After an outage or a restart (catch-up) no yes / tested Direct Connect only: older open runs coalesced
CND-01 conditions · Rules for every condition yes / tested yes / tested same: none
CND-02 conditions · Rules for every condition yes / tested yes / untested differs: import does not warn about unknown sensors behavioural (record): import accepts unknown sensors silently #202
CND-03 conditions · Rules for every condition yes / tested yes / untested differs: same idea, but every gateway tick also fetches each HA instance's whole /api/states variance: one snapshot per gateway per tick in both; HA read differs
CND-04 conditions · Rules for every condition yes / untested yes / untested same: none; on/off sensors are stored as int 1/0
CND-05 conditions · Operators yes / tested yes / tested same: none
CND-06 conditions · Operators yes / tested yes / untested differs: DC compares text case-insensitively; untested behavioural (battery): case-insensitive text: a condition can pass that fails there
CND-07 conditions · Operators yes / tested yes / untested same: untested here
CND-08 conditions · Operators yes / tested yes / untested differs: brackets not stripped; untested here behavioural (battery): bracketed lists and text members parse differently: condition result can differ
CND-09 conditions · Operators yes / tested yes / untested same: untested here
CND-10 conditions · Operators yes / tested yes / untested same: untested here
CND-11 conditions · Operators yes / tested yes / untested same: untested here
CND-12 conditions · Operators yes / tested yes / untested same: untested here
CND-13 conditions · Value and Lookup yes / untested yes / untested same: none
CND-14 conditions · Value and Lookup yes / tested yes / untested same: untested here
CND-15 conditions · Value and Lookup yes / untested yes / untested differs: Explain prints the Lookup label; Test against live prints an empty RHS variance: display text of a Lookup only; evaluation is the same
CND-16 conditions · Groups and items: ALL / ANY yes / tested yes / tested same: empty top-level block is true even with match any
CND-17 conditions · Groups and items: ALL / ANY yes / tested yes / tested same: none
CND-18 conditions · Groups and items: ALL / ANY yes / tested yes / untested same: untested here
CND-19 conditions · Groups and items: ALL / ANY yes / untested yes / untested differs: empty block saved as [] (same effect) variance: [] and null have the same effect
CND-20 conditions · Groups and items: ALL / ANY yes / untested yes / untested differs: an empty ALL exit group blocks the schedule from starting (exit condition already holds) behavioural (battery): an empty ALL exit group stops the schedule ever starting
CND-21 conditions · Scope: which gateway's values yes / untested yes / untested same: applies to gateway_scope all; untested
CND-22 conditions · Scope: which gateway's values yes / untested yes / tested differs: DC measures each gateway against its own meter (better) behavioural (battery): multi-gateway: tariff/billing sensors from each gateway's own meter, so conditions can differ
CND-23 conditions · Hold for (dwell) yes / tested yes / untested same: untested here
CND-24 conditions · Hold for (dwell) yes / tested yes / untested same: untested here
CND-25 conditions · Hold for (dwell) yes / untested yes / untested same: none
CND-26 conditions · Hold for (dwell) yes / tested yes / untested differs: no maximum; untested here behavioural (record): hold over 86400 s accepted
CND-27 conditions · Hold for (dwell) yes / untested yes / untested differs: a retry waits the whole hold again behavioural (battery): a retry waits the whole hold again, delaying the force #203
CND-28 conditions · When conditions are evaluated yes / tested yes / untested same: none
CND-29 conditions · When conditions are evaluated yes / tested yes / untested differs: once per calendar day per gateway, up to two leaves; untested behavioural (record): gated logged once a day, two leaves
CND-30 conditions · Test Verification yes / tested yes / tested differs: editor Test uses the top-bar gateway, not the schedule's behavioural (display): editor Test evaluates the top-bar gateway, not the schedule's
CND-31 conditions · Test Verification yes / untested yes / unclear differs: Test against live reads the default gateway and container clock, top-level rows only, no exit/hold/conflict check behavioural (display): Test against live: default gateway, container clock, top-level rows only #161
CND-32 conditions · Test Verification yes / untested yes / untested differs: no login on this bridge's HTTP API variance: no login anywhere on this bridge (LAN trust, BACKLOG); evaluate writes nothing
CND-33 conditions · Home Assistant entities yes / tested yes / tested same: since 0.5.4 unavailable/unknown are no reading, as in the Modbus Bridge; before 0.5.4 they read 0 #167 (fixed in 0.5.4)
CND-34 conditions · Home Assistant entities yes / tested yes / tested differs: REST /api/states (whole list) every tick of every gateway; no WebSocket variance: REST each tick vs WebSocket: same values per tick
CND-35 conditions · Home Assistant entities yes / tested yes / untested differs: no such warning behavioural (record): no warning for an unexposed HA entity #202
CND-36 conditions · Conditions (intro) no yes / untested Direct Connect only: DC evaluates exit conditions for every action kind while the window is open
CND-37 conditions · Home Assistant entities no yes / tested Direct Connect only: DC auto-scales $/kWh to c/kWh (tested)
SEN-01 conditions · Notes on some sensors yes / tested no missing here: no time.* sensors; use calendar restrictions Not ported: SENSOR-PARITY §A time.* #162
SEN-02 conditions · Notes on some sensors yes / tested no missing here: no time.* sensors Not ported: SENSOR-PARITY §A time.* #162
SEN-03 conditions · Notes on some sensors yes / tested yes / tested same: none
SEN-04 conditions · Grid yes / tested yes / tested differs: DC derives it from grid power != 0, so it reads 0 at exactly 0 W while on grid behavioural (battery): grid.connected reads 0 at exactly 0 W: a grid gate can fire a force #206
SEN-05 conditions · Battery yes / tested no missing here: no reserve sensors Not ported: SENSOR-PARITY §A battery.reserve_*; reserve is readable locally as 1726 reserved_soc (PROTOCOL.md), so not a transport limit
SEN-06 conditions · Notes on some sensors yes / tested yes / tested same: capacity is a user constant (no local capacity register); rate falls back to a constant
SEN-07 conditions · Constants yes / tested yes / tested same: DC adds default operating mode; capacity/max power not in the picker
SEN-08 conditions · Tariff yes / tested yes / tested differs: from the gateway's meter; None when undefined (fails closed) behavioural (battery): undefined window is None (fails closed) not False: == 0 gates differ
SEN-09 conditions · Tariff yes / tested yes / untested same: untested here
SEN-10 conditions · Tariff yes / tested yes / tested differs: last good NEM price kept however old behavioural (battery): stale NEM price kept: price-gated forces run on old prices #207
SEN-11 conditions · Utility Plan yes / tested yes / tested same: none
SEN-12 conditions · Utility Plan yes / tested no missing here: no such sensor Not ported: SENSOR-PARITY §A service.tz_matches_clock
SEN-13 conditions · Weather yes / tested yes / untested same: untested here; weather.code not in the picker
SEN-14 conditions · Gateway identity yes / untested no missing here: no gateway.* sensors; system.* describe the install Not ported: SENSOR-PARITY §A gateway.*
SEN-15 conditions · Other yes / tested no missing here: no dispatch.* sensors Not ported: SENSOR-PARITY §A dispatch.*
SEN-16 conditions · Other yes / unclear no missing here: no dispatch.* sensors Depends on: dispatch.* sensors (SEN-15)
SEN-17 conditions · Energy yes / tested no missing here: only billing-period import/export cost sensors Depends on: FEAT-BILLING-SERVICE, per SENSOR-PARITY §B
SEN-18 conditions · Every sensor in the picker no yes / tested Direct Connect only: different groups (Gateway, Derived Battery, …, one per HA instance)
SEN-19 conditions · Tariff no yes / untested Direct Connect only: DC keeps the last good NEM price with no age limit #207
ACT-01 actions · Summary yes / untested yes / tested same: none
ACT-02 actions · Summary yes / untested yes / untested differs: DC validates no action at save; failures appear only at run behavioural (battery): invalid actions saved; fail only at run #202
ACT-03 actions · Power and sizing yes / tested yes / untested differs: DC sizes pct against the 702 rating or a 5000 W fallback; no trusted rating behavioural (battery): % sized on 702 or a 5000 W fallback, no trusted rating: different watts written
ACT-04 actions · Power and sizing yes / tested yes / unclear differs: DC empty power = 0 W; form seeds 100 % behavioural (battery): empty power is a 0 W force #209
ACT-05 actions · Power and sizing yes / untested yes / untested differs: DC offers % and kW in the form, W via API behavioural (battery): percent accepted; any unknown unit is read as percent
ACT-06 actions · Power and sizing yes / untested no missing here: DC has no params validation at all (see ACT-02) Depends on: save-time validation #202
ACT-07 actions · Power and sizing yes / tested no missing here: no legacy format here Unknown: none found; legacy power_pct format never existed here
ACT-08 actions · Power and sizing yes / untested no missing here: n/a Unknown: none found; legacy format
ACT-09 actions · Power and sizing yes / untested no missing here: n/a Unknown: none found; legacy format
ACT-10 actions · Power and sizing yes / unclear yes / unclear differs: DC does not cap W/kW (library behaviour unverified) behavioural (battery): W/kW not capped by the bridge at 702
ACT-11 actions · Power and sizing yes / tested no missing here: no trust model Unknown: none found; #162 does not list a rating trust model #162
ACT-12 actions · Power and sizing yes / tested no missing here: DC refuses only when the Modbus client is not ready (ACT-30) Depends on: trusted rating (ACT-11) #162
ACT-13 actions · Power and sizing yes / tested yes / unclear differs: DC classifies a capability refusal as OK: logged fired, not retried behavioural (battery): a refused force is logged fired and never retried #191
ACT-14 actions · What is written yes / tested yes / untested differs: DC sends one BatteryCommand via the library and trusts its return; no read-back behavioural (battery): no WSetEna read-back check: a force can be recorded as sent when it did not take
ACT-15 actions · What is written yes / untested yes / untested differs: DC: bridge watchdog releases; hardware timer called cosmetic in a code comment (unverified) behavioural (battery): WSetRvrtTms not written (the library writes WSetEna/WSetMod/WSetPct only); PICS Issue 4 calls it cosmetic
ACT-16 actions · What is written yes / unclear no missing here: no staging in the scheduler path Unknown: none found; the force here is one BatteryCommand (battery_control.py:534), no staging
ACT-17 actions · Parameters you can set only through the API yes / tested yes / untested differs: DC time limit is always duration_min x 60; hidden 90 min in Recurring windows behavioural (battery): time limit = duration_min x 60, hidden 90 min in windows #160
ACT-18 actions · Parameters you can set only through the API yes / untested yes / untested differs: DC target SoC is in the form; checked every 5 s from the poller variance: same release rule at the same 5 s cadence; target in the form here
ACT-19 actions · Parameters you can set only through the API yes / untested yes / untested differs: DC form keeps the whole action object behavioural (battery): form save keeps API-only keys (the Modbus Bridge drops target_soc): different force end
ACT-20 actions · Battery actions: Force Standby yes / tested yes / untested same: DC still needs a ready Modbus client (this bridge)
ACT-21 actions · Battery actions: Release yes / untested no missing here: no Release action Not ported: #162 ("a Release action"); SCHEDULE-AND-AUTOMATIONS #162
ACT-22 actions · Non-battery actions: Reserve and Operating Mode yes / tested yes / tested same: DC picker tou/self/backup from gateway work modes
ACT-23 actions · Non-battery actions: Reserve and Operating Mode yes / untested yes / untested differs: DC checks nothing; missing mode fails at run behavioural (device/HA): missing mode accepted, fails and retries at run
ACT-24 actions · Non-battery actions: Reserve and Operating Mode yes / untested yes / unclear same: DC also logs a rejected mode or off-grid write as fired #191
ACT-25 actions · Non-battery actions: Reserve and Operating Mode yes / tested no missing here: no write-lock tracking Depends on: read-back of command results #139: a 1727 write can be accepted (result:0) and not applied (PROTOCOL.md)
ACT-26 actions · Non-battery actions: Reserve and Operating Mode yes / untested yes / untested same: DC: If busy is force-only; same-tick priority still applies
ACT-27 actions · No battery action (HA only) yes / tested yes / tested same: none
ACT-28 actions · No battery action (HA only) yes / untested yes / untested differs: DC Run now runs the fire-phase HA actions behavioural (device/HA): Run now runs HA actions of HA-only schedules
ACT-29 actions · Summary no yes / tested Direct Connect only: Unknown action kind at run is skipped and logged fired
ACT-30 actions · Battery actions: Force Charge and Force Discharge no yes / untested Direct Connect only: Force refused unless a SunSpec read through the Modbus client (this bridge) succeeds
ACT-31 actions · Battery actions: Force Charge and Force Discharge no yes / tested Direct Connect only: No host: force skipped
ACT-32 actions · Non-battery actions: Reserve and Operating Mode no yes / tested Direct Connect only: reserve_soc always skipped, logged fired #129
ACT-33 actions · Smart circuits, off-grid and notify (Direct Connect only) no yes / tested Direct Connect only: Smart circuit write with read-back; NOT confirmed retried
ACT-34 actions · Smart circuits, off-grid and notify (Direct Connect only) no yes / tested Direct Connect only: On/Off read strictly since 0.5.5; before it, Off ran as on #188 (fixed in 0.5.5)
ACT-35 actions · Smart circuits, off-grid and notify (Direct Connect only) no yes / untested Direct Connect only: Off-grid action with SoC, no confirm
ACT-37 actions · Summary no yes / tested Direct Connect only: smart_circuit_schedule listed unavailable with reason
ACT-38 actions · Battery actions: Force Charge and Force Discharge no yes / untested Direct Connect only: Force disabled in the form with the reason when the Modbus client (this bridge) is unavailable
ACT-39 actions · What is written no yes / unclear Direct Connect only: One in-memory force for the whole bridge; a second gateway's force drops the first's watchdog #194
ACT-40 actions · What is written no yes / untested Direct Connect only: Up to 5 attempts with sleeps inside one tick; blocks all gateways #197
ACT-41 actions · What is written no yes / unclear Direct Connect only: UNKNOWN verdict unreachable for scheduler actions #201
ACT-42 actions · What is written no yes / unclear Direct Connect only: Retry deadline falls to 1 s for Always and zero-duration windows #209
HAA-01 actions · Home Assistant actions yes / untested yes / tested differs: DC saves anything; skips with a reason at run Modbus Bridge check (their PR #233): its import skips validation too (their #232), so invalid actions can be saved there as well. behavioural (device/HA): invalid HA actions saved; skipped at run #202
HAA-02 actions · Home Assistant actions yes / untested yes / untested differs: DC form saves incomplete rows behavioural (record): incomplete rows kept and skipped at run with a reason
HAA-03 actions · When they run yes / tested yes / untested same: DC: after the battery action whatever its result (HAA-07)
HAA-04 actions · When they run yes / tested yes / untested same: none
HAA-05 actions · When they run yes / tested yes / untested same: none
HAA-06 actions · When they run yes / tested yes / unclear differs: DC: at every closing edge of the window, even if never fired; not on Stop or an in-window end behavioural (device/HA): exit HA actions run at every window close, even if never fired #189
HAA-07 actions · When they run yes / untested yes / unclear differs: DC runs them on every attempt behavioural (device/HA): on-entry HA actions repeat on every retry #203
HAA-08 actions · Guards yes / tested yes / untested differs: DC skips silently, no log; API also accepts a tree behavioural (record): guard skip leaves no log row
HAA-09 actions · Placeholders in notifications yes / tested yes / tested same: DC prints numbers as stored (no .0 trimming)
HAA-10 actions · Placeholders in notifications yes / untested yes / untested differs: DC: dotted ids work, ha: ids do not behavioural (record): %ha:…% placeholders not substituted #169
HAA-11 actions · Failure alerts yes / tested no missing here: no failure notifications Not ported: #172 (notifier not passed to the outcome path) #172
HAA-12 actions · What is logged yes / tested yes / untested differs: DC folds results into the fired/exit/manual row; failures rarely fail the run behavioural (record): HA failures folded into the run row; rarely fail the run
HAA-13 actions · Failure alerts no yes / untested Direct Connect only: run_action_outcome called without notifier #172
HAA-14 actions · Placeholders in notifications no yes / tested Direct Connect only: Placeholders also in service entity_id and data
HAA-15 actions · Home Assistant actions no yes / tested Direct Connect only: Raw service with bad JSON is skipped with the reason
HAA-16 actions · Home Assistant actions no yes / tested Direct Connect only: Guided entity action calls domain.service with entity and data
HAA-17 actions · Placeholders in notifications no yes / tested Direct Connect only: %run.%, %schedule.%, %gateway.id% variables
HAA-18 actions · Home Assistant actions no yes / untested Direct Connect only: Notify as a battery action kind
TGT-01 targets · Pick a target yes / untested yes / tested differs: DC: bound schedule only on its gateway's tick; not evaluated while stale/disabled behavioural (battery): a stale or disabled gateway's schedules are not evaluated
TGT-02 targets · Pick a target yes / untested yes / untested differs: DC: API-only gateway_scope all; no Site target in the form behavioural (display): site fan-out only through the API #162
TGT-03 targets · Pick a target yes / untested no missing here: no utility-service target Not ported: ORCH 2b (Target = Service); #162 #162
TGT-04 targets · How a fan-out works yes / tested yes / tested same: DC: occurrence and resource claim per gateway
TGT-05 targets · How a fan-out works yes / tested yes / untested same: DC: per gateway:entry; but see TGT-20 and ACT-39
TGT-06 targets · How a fan-out works yes / tested yes / untested differs: History rows do not name the gateway behavioural (record): History rows do not name the gateway #205
TGT-07 targets · How a fan-out works yes / untested yes / unclear same: DC: a stale/disabled gateway gets no window-end release either
TGT-08 targets · How a fan-out works yes / untested yes / tested same: DC: stale/disabled gateway skipped with a debug log only
TGT-09 targets · How a fan-out works yes / untested yes / unclear differs: DC Run now: one gateway, and the top-bar gateway overrides the bound one behavioural (battery): Run now forces the top-bar gateway, not the schedule's #193
TGT-10 targets · Entries with no target id yes / untested yes / untested differs: DC unbound = first-registered gateway, unstored behavioural (battery): unbound = first registered gateway, which moves #182
TGT-11 targets · Entries with no target id yes / unclear yes / untested differs: DC: unbound claims the tick gateway, same group as bound behavioural (battery): unbound and bound contend as one group (two groups there)
TGT-12 targets · In the form yes / unclear no missing here: no service select Depends on: service target (TGT-03)
TGT-13 targets · In the form yes / untested no missing here: no mock warning in the form Unknown: none found
TGT-14 targets · In the form yes / tested yes / tested same: none
TGT-15 targets · On the timeline yes / untested yes / untested differs: DC timeline ignores gateway; one list behavioural (display): timeline is one list, not per gateway #161
TGT-16 targets · How a fan-out works yes / unclear no missing here: n/a; see TGT-07 Depends on: run ownership (EXT-06, #189) and site/service targets
TGT-17 targets · Entries with no target id no yes / unclear Direct Connect only: Disabled first gateway: unbound schedules run nowhere #182
TGT-18 targets · In the form no yes / tested Direct Connect only: Mock gateways skip the 702 ratings read
TGT-19 targets · In the form no yes / untested Direct Connect only: Test against live always uses the default gateway
TGT-20 targets · How a fan-out works no yes / unclear Direct Connect only: Stop, Pause, shutdown and boot reconcile use the default gateway's host #192
TGT-21 targets · Pick a target no yes / untested Direct Connect only: Gateway select only with >1 gateway; Default gateway = empty id
TGT-22 targets · Pick a target no yes / untested Direct Connect only: Schedule bound to an unknown gateway id never runs, silently
TGT-23 targets · Pick a target no yes / tested Direct Connect only: gateway_scope survives a form save (#157 fix) #157
EXT-01 exit-and-conflicts · How a run ends yes / tested yes / tested differs: DC releases at every force entry's window close, owned or not; logged exit 'window closed' behavioural (battery): window close releases a force it never sent or does not own #189
EXT-02 exit-and-conflicts · How a run ends yes / tested yes / tested same: none; DC marks the occurrence fired
EXT-03 exit-and-conflicts · How a run ends yes / tested yes / tested differs: DC uses per-occurrence keys instead of clearing a mark variance: per-occurrence keys vs clearing a mark: both fire again next window
EXT-04 exit-and-conflicts · How a run ends yes / tested yes / untested differs: DC: disable releases on next tick; delete does not release behavioural (battery): delete does not release the running force #195
EXT-05 exit-and-conflicts · How a run ends yes / unclear yes / unclear differs: DC never hands over; it always releases, even another's force behavioural (battery): never hands over; releases another's force #189
EXT-06 exit-and-conflicts · How a run ends yes / unclear no missing here: no ownership hand-over in DC Not ported: #189 (no ownership: window end releases a force it does not own)
EXT-07 exit-and-conflicts · Exit conditions yes / tested yes / tested differs: DC does not start when exit already holds behavioural (battery): exit already true: no start here; a brief force there
EXT-08 exit-and-conflicts · Exit conditions yes / tested yes / tested same: none (DC plain release)
EXT-09 exit-and-conflicts · Exit conditions yes / untested yes / untested differs: DC evaluates exit for every action kind while the window is open behavioural (device/HA): exit evaluated for every action kind (mode, HA-only)
EXT-10 exit-and-conflicts · Exit conditions yes / untested yes / tested differs: DC detail names no rows behavioural (record): exit row names no condition
EXT-11 exit-and-conflicts · Release policy yes / tested no missing here: no release policies; always plain release Not ported: ORCH 2b (on-exit release policy); #162 #162
EXT-12 exit-and-conflicts · Release policy yes / tested yes / untested differs: DC restore_on_exit (API only) writes the captured mode back, set_mode schedules only; end-to-end untested behavioural (device/HA): restore_on_exit writes the mode back (the Modbus Bridge only audits) #162
EXT-13 exit-and-conflicts · Release policy yes / tested no missing here: not in DC Not ported: ORCH 2b (release policy); #162 #162
EXT-14 exit-and-conflicts · Release policy yes / tested no missing here: no policies; DC Stop never restores Not ported: ORCH 2b (release policy); #162 #162
EXT-15 exit-and-conflicts · Release policy yes / untested no missing here: no field Depends on: release policy (EXT-11)
EXT-16 exit-and-conflicts · Release policy yes / untested no missing here: no such migration Depends on: release policy (EXT-11); the migration is the Modbus Bridge's own
EXT-17 exit-and-conflicts · What a release does on the gateway yes / tested yes / untested differs: DC release has no read-back; refused when Modbus client off behavioural (battery): Release refused when the Modbus client (this bridge) is off; no read-back #174
EXT-18 exit-and-conflicts · Hold instead of release (API only) yes / tested no missing here: no hold Not ported: #162 ("hold instead of release") #162
EXT-19 exit-and-conflicts · Hold instead of release (API only) yes / unclear no missing here: no hold Depends on: hold (EXT-18)
EXT-20 exit-and-conflicts · Bridge shutdown yes / untested yes / unclear differs: DC releases the in-memory force to the first gateway's host, not the force's host behavioural (battery): shutdown releases to the first gateway's host #192
EXT-21 exit-and-conflicts · How a run ends no yes / unclear Direct Connect only: DC: deleting a running schedule does not release its force #195
EXT-22 exit-and-conflicts · Exit conditions no yes / tested Direct Connect only: nested exit groups (MB also supports; tested here)
EXT-24 exit-and-conflicts · How a run ends no yes / unclear Direct Connect only: flapping exit conditions repeat Release and exit HA actions #189
EXT-25 exit-and-conflicts · How a run ends no yes / unclear Direct Connect only: force watchdog uses hidden duration_min in Recurring windows #160
EXT-26 exit-and-conflicts · How a run ends no yes / untested Direct Connect only: bridge watchdog enforces duration and target SoC every 5 s
EXT-27 exit-and-conflicts · Release policy no yes / tested Direct Connect only: restore_on_exit captures mode before first attempt
EXT-28 exit-and-conflicts · Release policy no yes / tested Direct Connect only: PUT merge keeps restore_on_exit #157
PRI-01 priorities · Priorities and conflicts yes / untested yes / untested differs: DC: any integer, free-text conflict (unknown = override), default override Modbus Bridge check (their PR #233): its import skips validation (their #232); the default and unknown-value handling are as their code, not their old markers. behavioural (battery): default If busy = override (there: defer); unknown values act as override
PRI-02 priorities · Entries on the same target yes / tested yes / tested differs: DC: contest only among entries ready on the same tick, per resource behavioural (battery): contest only within a tick, per resource
PRI-03 priorities · Entries on the same target yes / untested yes / untested differs: DC: later-ready entries judged only by If busy; override (default) pre-empts regardless of priority; mode entries never checked behavioural (battery): a later-ready force overrides a running one whatever the priority #196
PRI-04 priorities · Entries on the same target yes / untested yes / untested same: none (untested in both)
PRI-05 priorities · Entries on the same target yes / untested yes / tested same: DC: mode only claims on its fire tick
PRI-06 priorities · Entries on the same target yes / tested yes / tested differs: DC logs deferred, settles the occurrence skipped, no re-fire that occurrence behavioural (battery): a loser does not fire again that occurrence
PRI-07 priorities · Manual control yes / tested yes / tested differs: DC: active dispatches rows of another schedule or _widget; force winners only behavioural (battery): busy = only dispatch rows of schedules or the widget; mode entries unchecked
PRI-08 priorities · Manual control yes / tested yes / tested differs: DC defer marks the day done; wait logs every tick and retries behavioural (battery): defer gives up for the day; wait retries each tick
PRI-09 priorities · Manual control yes / tested yes / tested same: none
PRI-10 priorities · Manual control yes / untested yes / untested differs: DC: only wait does; defer gave up for the day behavioural (battery): after a manual command ends, a deferred entry does not run
PRI-11 priorities · What the bridge cannot see yes / untested yes / untested same: none (both dispatch over it)
PRI-12 priorities · What the bridge cannot see yes / unclear no missing here: no ownership in DC Depends on: run ownership (EXT-06, #189)
PRI-13 priorities · Entries on different targets yes / unclear yes / tested differs: DC has gateway binding and scope all; claims per gateway on its tick behavioural (battery): claims per gateway, not per target
PRI-14 priorities · Who sent what (requester) yes / tested yes / tested differs: DC records schedule id or _widget in the dispatches table only; no control-log requester behavioural (record): requester only in the dispatches table
PRI-15 priorities · What the bridge cannot see yes / unclear no missing here: no supervision in DC Depends on: supervision (OUT-07 to OUT-11) #162
PRI-16 priorities · Manual control no yes / tested Direct Connect only: wait retries every tick (MB: wait = defer)
PRI-17 priorities · Entries on the same target no yes / tested Direct Connect only: per-resource claims: grid, per-circuit, wildcard merge, unknown kind
PRI-18 priorities · Entries on the same target no yes / tested Direct Connect only: notify/none claims nothing (MB: own lane, equivalent)
PRI-19 priorities · Manual control no yes / unclear Direct Connect only: defer marks the date, so interval/cron/window#n entries defer and log every tick #204
OUT-01 outcomes · Activity Log results yes / tested yes / untested differs: DC logs a word only; import writes no row behavioural (record): config changes logged as one word; import not logged
OUT-02 outcomes · Activity Log results yes / tested yes / tested same: DC also filters severity
OUT-03 outcomes · Activity Log results yes / untested yes / untested differs: DC History loads 200 rows, chips per status present; fired is used variance: History view length and chips only
OUT-04 outcomes · Retries yes / tested yes / tested differs: DC 30 s doubling to 600 s, plus in-tick resilience retries; no notification behavioural (battery): retry 30 s doubling to 600 s (there: 15, 30, 60 s); no notification #172
OUT-05 outcomes · Retries yes / tested yes / tested differs: DC logs plain fired; no notification behavioural (record): recovery logged as plain fired; no notification #172
OUT-06 outcomes · Retries yes / untested yes / untested same: DC settles it skipped
OUT-07 outcomes · Supervision of a running command yes / tested no missing here: no supervision Not ported: #162 ("dispatch verification and re-send") #162
OUT-08 outcomes · Supervision of a running command yes / tested no missing here: no supervision Not ported: #162; the force uses the same WSet model 704 on the Modbus TCP Server (aGate :502) (battery_control.py:1-7), so not a transport limit #162
OUT-09 outcomes · Supervision of a running command yes / tested no missing here: no supervision Not ported: #162 #162
OUT-10 outcomes · Supervision of a running command yes / tested no missing here: no supervision Not ported: #162 #162
OUT-11 outcomes · Supervision of a running command yes / tested no missing here: no supervision Not ported: #162 #162
OUT-12 outcomes · Supervision of a running command yes / untested no missing here: no supervision Depends on: supervision (OUT-07) #162
OUT-13 outcomes · The dispatch record yes / tested yes / tested differs: DC dispatches table: successful forces only (schedule, Run now, widget) behavioural (record): dispatch record holds successful forces only #139
OUT-14 outcomes · The dispatch record yes / untested no missing here: no verification states Depends on: supervision (OUT-07) and an outcome record #139 #162
OUT-15 outcomes · The dispatch record yes / untested yes / untested same: none
OUT-16 outcomes · The dispatch record yes / tested no missing here: no REST read of dispatches Not ported: #139 #139
OUT-17 outcomes · Overshoot guard yes / tested no missing here: no overshoot guard Not ported: #162 ("an overshoot guard") #162
OUT-18 outcomes · Notifications yes / tested yes / unclear differs: no scheduler failure notifications; only boot reconcile notify behavioural (record): no failure notifications #172
OUT-19 outcomes · Run now and Stop yes / untested yes / untested differs: DC active_now also needs fired this occurrence; container clock behavioural (display): Stop shown on a different rule, container clock #161
OUT-20 outcomes · Run now yes / tested yes / untested differs: DC Run now ignores conditions entirely behavioural (battery): Run now ignores conditions (by design per #162) #162
OUT-21 outcomes · Run now yes / untested yes / untested same: DC uses duration_min (hidden 90 for windows) #160
OUT-22 outcomes · Run now yes / untested yes / untested same: none
OUT-23 outcomes · Run now yes / untested yes / untested same: DC also runs disabled entries
OUT-24 outcomes · Stop yes / tested yes / unclear differs: DC Stop: plain Release via default gateway host, no exit HA actions, no block needed behavioural (battery): Stop releases via the first gateway's host; no exit HA actions #192
OUT-25 outcomes · Stop yes / untested yes / untested differs: DC Stop with nothing changes nothing; entry may still fire behavioural (battery): Stop with nothing running does not block the window; the entry can still fire
OUT-26 outcomes · The dispatch record no yes / untested Direct Connect only: scheduled/Run now force writes a dispatches row
OUT-27 outcomes · Run now no yes / untested Direct Connect only: Run now force recorded, so Stop and If busy see it (MB: Stop does not see Run now)
OUT-28 outcomes · Run now no yes / unclear Direct Connect only: UI Run now uses the top-bar gateway over the bound one #193
OUT-29 outcomes · Retries no yes / tested Direct Connect only: missed sweep after 120 s grace (MB: catch-up instead)
OUT-30 outcomes · Activity Log results no yes / tested Direct Connect only: coalesced backlog runs
OUT-31 outcomes · Retries no yes / tested Direct Connect only: unknown outcome settles, not retried
OUT-32 outcomes · Retries no yes / unclear Direct Connect only: unknown is unreachable from the action path #201
OUT-33 outcomes · Retries no yes / unclear Direct Connect only: in-tick resilience retries block the scheduler thread #183
OUT-34 outcomes · Retries no yes / unclear Direct Connect only: refused force / rejected mode logged fired (text classification) #191
OUT-35 outcomes · Retries no yes / unclear Direct Connect only: per-attempt audit sink signature mismatch #201
OUT-36 outcomes · Run now and Stop no yes / unclear Direct Connect only: Pause ineffective #200
OUT-37 outcomes · Run now and Stop no yes / tested Direct Connect only: Resume only inside the window
OUT-38 outcomes · Run now and Stop no yes / tested Direct Connect only: paused runs become stopped at restart
OUT-39 outcomes · Where to look no yes / tested Direct Connect only: run queue /runs and /stats
OUT-40 outcomes · Activity Log results no yes / tested Direct Connect only: log severity classes with per-class caps
OUT-41 outcomes · Activity Log results no yes / tested Direct Connect only: 'nothing to do' still logged
OUT-42 outcomes · Retries no yes / tested Direct Connect only: error row names attempt and retry delay
OUT-43 outcomes · Run now no yes / untested Direct Connect only: Run now placeholders limited to gateway + HA values
CLK-01 restarts-and-clock · The clock yes / untested yes / tested differs: DC: each gateway's aGate clock (site time) behavioural (battery): each gateway's aGate clock: fire times differ when the container clock is not site time
CLK-02 restarts-and-clock · The clock yes / untested yes / unclear differs: DC: previews on container clock, tick on site clock behavioural (display): previews on the container clock #161
CLK-03 restarts-and-clock · The clock yes / tested yes / tested differs: DC: site timezone setting for mocks; no install check variance: the tick here uses the aGate clock, so the install timezone check has nothing to guard
CLK-04 restarts-and-clock · Daylight saving yes / unclear yes / unclear differs: DC: fixed offset re-read every 10 min; late by up to 10 min behavioural (battery): DST change applies up to 10 min late
CLK-05 restarts-and-clock · The clock no yes / tested Direct Connect only: unreadable gateway falls back to container clock, not UTC
CLK-06 restarts-and-clock · The clock no yes / tested Direct Connect only: implausible aGate clock refused
RST-01 restarts-and-clock · Bridge restart yes / tested yes / untested differs: DC releases only the in-memory force, to the first gateway's host behavioural (battery): restart releases only the in-memory force, to the first gateway's host #192
RST-02 restarts-and-clock · Bridge restart yes / untested yes / tested differs: DC: reconcile policy, default notify (battery untouched) behavioural (battery): start-up default is notify: a force left by a crash keeps running (there: released)
RST-03 restarts-and-clock · Bridge restart yes / tested yes / tested differs: DC: a fired occurrence is stored, no re-fire behavioural (battery): stored occurrence: no re-fire after restart (there: re-dispatches)
RST-04 restarts-and-clock · Bridge restart yes / untested yes / unclear differs: DC: release_stale never called; no catch-up behavioural (battery): release_stale() never called #199
RST-05 restarts-and-clock · Bridge restart no yes / tested Direct Connect only: paused runs resolved to stopped at start-up
RST-06 restarts-and-clock · Bridge restart no yes / tested Direct Connect only: release/resume policies re-arm or re-force
RST-07 restarts-and-clock · Bridge restart no yes / untested Direct Connect only: with notify a force outlives a restart; timer lost
RST-08 restarts-and-clock · Bridge restart no yes / unclear Direct Connect only: reconcile and shutdown handle only the first gateway #192
DEP-01 dependencies · Dependency matrix → Actions no yes / untested same: none (untested here) #128
— dependencies · A Home Assistant action did not run no section Direct Connect only: kept from the old troubleshooting page #169 #171
— dependencies · A condition is always true when it should not be section section differs: DC: tariff windows read None when unconfigured; grid.connected reads 0 at 0 W; before 0.5.4 an unavailable HA entity read 0 (#167) behavioural (battery): conditions can pass when they should not (#206) #206
— dependencies · An action is refused or does nothing section section differs: a force refused by the Modbus client path, and a mode/off-grid write with a non-zero result, are logged fired behavioural (battery): refused writes logged fired (#191) #191
— dependencies · An entry never fires section section differs: DC Always runs once ever (occurrence stays done across restarts) behavioural (battery): Always fires once ever (#190) #190
— dependencies · Dependency matrix section section differs: DC: force needs the Modbus client (this bridge); reserve never runs (#129); no trusted-rating gate behavioural (battery): force needs the Modbus client (this bridge): :9000 has no battery force (transport limit, HYBRID-CAPABILITIES); reserve write never runs (#129): 1405 is cloud-only (PROTOCOL.md) #129
— examples · 1. Evening top-up section section differs: weekly fire-at+duration (#160); power in % or kW (W API only); target SoC field behavioural (battery): hidden duration ends the force (#160) #160
— examples · 2. Evening peak discharge until the minimum SoC section section differs: daily 17:00 + 240 min because of #160 behavioural (battery): workaround for #160 changes the window #160
— examples · 3. Charge from the grid when the NEM spot price is low section section same: stale NEM price kept forever #207
— examples · 4. Storm forecast: fill the battery section section differs: weather.code not in the picker; condition text unverified needs owner: needs owner: is weather.condition text "thunder" right, or should the example use weather.code?
— examples · 5. Peak-demand window section section differs: window flag None when undefined; overlapping force schedules release each other behavioural (battery): overlapping force schedules release each other (#189) #189
— examples · 6. Weekend export, unless Home Assistant says you are away section section same: since 0.5.4 an unavailable entity has no value, as in the Modbus Bridge #167 (fixed in 0.5.4)
— examples · 7. Full by 07:00, starting as late as possible section no missing here: no time.* sensors; one cron schedule per rung instead Depends on: time.* sensors (SEN-01), SENSOR-PARITY §A #162
— examples · More examples (Direct Connect only) no section Direct Connect only: template-based recipes moved from the old troubleshooting page

Existing issues this page touches

Issue Where
#157 Turning a schedule on/off wiped its settings Fixed in 0.5.2: a PUT merges what it sends into the stored schedule (index).
#160 A force in a Recurring window stops at the hidden duration triggers, actions, exit
#161 Timeline, next fire and Test use the container clock restarts-and-clock
#162 Scheduler parity with the Modbus Bridge most missing here rows
#167 An unavailable HA entity read 0 Fixed in 0.5.4: it now has no value (conditions).
#168 PUT without enabled re-enables index
#169 %ha:…% placeholders are not substituted actions
#129 reserve_soc is always skipped actions
#172 No failure notification outcomes
#182 The default gateway is the first registered and moves targets
#165, #171, #173, #174, #175, #183 release button, notification switch, dispatch notifications, Release read-back, worker restart guard, scheduler heartbeat

Issues filed from this review

Each was found while writing the Scheduler pages, from a code read; the ones marked reproduced were confirmed by driving scheduler.tick with a temporary store and a monkeypatched battery_control.execute (no hardware, no emulator, so not evidence of what an aGate does). The Test against live point (it reads the default gateway's values) was added to #161.

Issue Title Evidence Rows
#188 Scheduler on/off picker stores "false" as text, which runs as on: smart circuit turns ON, Go off-grid / reconnect goes OFF-GRID (fixed in 0.5.5) reproduced in the engine; the form path is a code read ACT-34
#189 A force schedule's window end sends Release even if it never fired, or after another schedule or the Battery Control widget took the battery; exit HA actions run too; flapping exit conditions repeat both reproduced HAA-06, EXT-01, EXT-05, EXT-24
#190 An Always schedule fires only once, ever (its single stored run stays finished), yet keeps sending Release on every falling edge reproduced TRG-28, TRG-29
#191 A force refused by the Modbus client (this bridge), and a mode or off-grid write the aGate rejects, are logged "fired" and never retried reproduced ACT-13, ACT-24, OUT-34
#192 Stop, Pause, the shutdown release and the boot reconcile use the first gateway's host, not the host the force was recorded on code read TGT-20, EXT-20, OUT-24, RST-01, RST-08
#193 Run now from the UI acts on the top-bar gateway, not the schedule's own gateway code read TGT-09, OUT-28
#194 battery_control supervises one force per process: a second gateway's force drops the first one's time limit and target SoC code read ACT-39
#195 Deleting a running schedule does not release its force reproduced EXT-04, EXT-21
#196 Priority only counts on the same tick: a force that becomes ready later overrides a running one whatever their priorities (default If busy = override) reproduced PRI-03
#200 Pause does not hold a run: the tick re-attempts paused runs, and a run that already succeeded is not found reproduced IDX-12, OUT-36
#197 Force retries sleep inside the scheduler tick and stall every gateway (cf. #183) code read ACT-40
#201 The scheduler can never record an UNKNOWN outcome, and its resilience audit hook never writes (signature mismatch) reproduced ACT-41, OUT-32, OUT-35
#198 Weekly with no days, Monthly with no day of month, and One-off with no date fire every day; a Recurring window with start = end is open all day reproduced TRG-09, TRG-23, TRG-51
#202 Validate actions, HA actions, cron, day of month and months when a schedule is saved; import should flag unknown sensors and operators code read CND-02, CND-35, ACT-02, HAA-01
#203 On-entry HA actions repeat on every retry, and a retry waits the whole hold again code read CND-27, HAA-07
#204 If busy = defer re-defers and logs every tick for interval, cron and second-window schedules code read PRI-19
#205 History rows should name the gateway (gateway scope "all" rows cannot be told apart) code read TGT-06
#206 grid.connected reads 0 whenever grid power is exactly 0 W code read SEN-04
#207 A stale AEMO NEM price is kept forever when the fetch fails code read SEN-10, SEN-19
#208 Every N minutes of 24 h or more: Next shows anchor + N, the engine fires at the anchor reproduced TRG-19
#199 battery_control.release_stale() is never called; start-up relies on the reconcile policy alone code read RST-04
#209 An empty power sent through the API is a 0 W force; Always and zero-duration schedules get a 1-second retry deadline code read ACT-04, ACT-42