The four Modbus states, and why the dashboard showed two of them side by side

Four different things are called "Modbus" in this project. Three are the gateway's, one is ours, and a dashboard that shows two of them without saying whose is which reads as a contradiction. It did: MODBUS :502 — Not probed sat next to SUNSPEC MODBUS — Enabled, and both were correct.

The two enable flags in 1205/1206 der_comms

One read returns both, and they are not the same subject.

field subject observed meaning
sunsMdEn the aGate 1 SunSpec Modbus TCP server on/off, served on ip:port (502). 1 = the gateway accepts Modbus connections.
enable the aGate 0 IEEE 2030.5 / SEP2 on/off — a different protocol entirely. The rest of the payload belongs to it: uri, dcap2030_5, lfdi, sfdi, pin, status2030_5.

The bridge surfaces them as summary.der_comms = {"sunsMdEn": …, "sep2": …}, where sep2 is enable (client.py). The UI labels them "SunSpec Modbus" and "IEEE 2030.5/CSIP", which is right — the trap is that enable, the more general-sounding name, is the 2030.5 flag and not the Modbus one.

sunsMdEn enables the Modbus interface (reads). It is not the write plane: the franklinwh-modbus write-lock is a separate gate, and 1251 SUNSPEC_MODBUS_*_EVAL are certification flags, different again.

Verification

Measured 2026-10-15, aGate X-01-AU, firmware V12R02B30D06:

1206 der_comms → sunsMdEn: 1   enable: 0   port: 502   status2030_5: 0
                 dcap2030_5: "/sep2/dcap"   lfdi: ""   sfdi: ""

sunsMdEn: 1 is corroborated independently: the Modbus Bridge held 2–3 established connections to the gateway's :502 that morning and polled it successfully, which is only possible if that listener is on.

The other two

state subject where it comes from
Bridge Modbus client enabled/disabled ours battery_control.is_enabled() — the Control-tab switch. Governs whether this bridge opens Modbus connections at all.
:502 reachability ours, about the aGate _probe_modbus() — a TCP probe. Tri-state: reachable / refused / not probed, the last when our client is switched off (#30, #32).

The rule

State whose setting it is. "Enabled" on its own is ambiguous across four subjects. A card showing a gateway setting must say so; a card showing our own switch must say that.

Do not infer one from another. Our client being disabled says nothing about sunsMdEn. sunsMdEn: 1 says nothing about whether we are connected. The gateway serving Modbus says nothing about whether writes are permitted.