Test plan — does the gateway curtail PV during an island, and how?

Status: planned, not run. Written 2026-10-15 after the first observed island. Not before ~2026-11-15 — the owner is away from site for a month or more. See BACKLOG.md → TEST-OFFGRID-BREAKER, which has the same constraint and should be run in the same visit if the weather allows: the two tests need opposite conditions (this one needs a clear sky at solar noon, that one needs nothing but the owner at the switchboard), so they are separate runs, not one.

The question

This site has 6.6 kWp of AC-coupled PV behind a 5 kW aGate. On grid that is unremarkable — surplus exports. Islanded, there is nowhere for surplus to go. PV output must equal house load plus battery charge, and the battery cannot absorb more than the inverter's rating. So above roughly load + 5 kW the gateway must do something to PV, or overload itself.

The owner's expectation is that the gateway shuts PV down. The hypothesis below is narrower and testable: it curtails rather than disconnects, and does so by frequency shift.

Why frequency shift is the hypothesis

AC-coupled PV has its own inverter, which the aGate does not command directly.

Frequency shift is a guess, and it is written here only because it is cheap to falsify. We have not read a FranklinWH document describing how this gateway curtails AC-coupled PV, and nothing in our captures shows it doing so. Raising island frequency to throttle PV is a mechanism used in this class of equipment generally, which is not evidence about this device. If the guess is wrong the test still answers the real question — what the gateway actually does — because gridFreq, p_sun and the relay states are recorded either way.

What is measured and not a guess: the island ran at gridFreq 49.96–50.02 Hz throughout 2026-10-15. That is the baseline any frequency movement would be measured against.

Supporting observation, not proof: the Modbus channel logged DERMeasureAC.DERMode = "PV Clipped" for ~51 s at 06:50:49 on 2026-10-15 — the moment of cutover into the island. So a PV-clipping state exists and the gateway enters it. What is unknown is the threshold and the mechanism.

Predictions, stated before the run

# If the hypothesis holds If it does not
1 gridFreq rises above 50.0 Hz as PV approaches the limit frequency stays at 50.0 and something else gives
2 p_sun plateaus below its clear-sky potential; the plateau ≈ p_load + battery charge limit p_sun tracks irradiance and the battery charge rate is what clips
3 solarRelayStatus stays 1 (closed) throughout it goes to 0 — the owner's "PV shuts down" reading, which would make the curtailment hypothesis wrong
4 Modbus DERMode reports PV Clipped while curtailing it reports something else, or nothing
5 Recovery is smooth when load rises or SoC falls PV trips off and needs a reconnect delay (typically 60 s) to return

Prediction 3 is the one that decides between "curtails" and "shuts down". It is written down first so the result cannot be read either way afterwards.

Cross-channel corroboration already in hand (2026-10-15)

Three independent channels captured the same island, and they agree on the two things this test depends on:

  • PV runs while islanded. Direct Connect p_sun 811 W with solarRelayStatus 1; Modbus 300–500 W with the battery charging; Cloud p_sun 1.649 kW at 07:34 with p_fhp −1.434 kW. So the starting point for this test — that PV produces during an island and must therefore be curtailed somehow — is established on three channels, not assumed.
  • run_status is not the signal, on EITHER channel. Cloud runtimeData.run_status showed 1 ×53, 2 ×14, 0 ×4 and never 5/6/7 — matching local 1301. The "5/6/7 = off-grid" mapping is therefore unconfirmed for a real island on both channels, not a local quirk.

Also settled, and it matters for reading the results: ibgRunStatus is a programme id, not a run status. Local 1707 ibgRunStatus read 7 throughout, and Cloud runtimeData.mode read 7 in 71/71 polls — the same value on both channels, where the normal value is the mode id 85232 "Self-Consumption" and a Modbus dispatch showed 9. So during this test, ibgRunStatus/mode identifies the programme, and dspRunstatus is the run state to watch.

The premise does not rest on the solar sensor

The franklinwh-modbus-bridge session, at the owner's direction, withdrew its corroboration on the grounds that these are values the aGate reports, not ground truth — if the PV relays are open, the reported solar figures are measuring something else. That is a fair objection to a power reading, and it is why this plan does not rest on one.

State of charge, with the grid relay open and p_uti 0 throughout:

time SoC p_sun p_fhp p_load
07:53 14.11% 250 W −36 W —
08:23 15.16% 823 W −628 W ~220 W
08:54 17.79% 1385 W −1187 W ~230 W
08:59 18.74% 1372 W −1141 W 231 W

The battery gained ~4.6% of its capacity in an hour while the house drew 200–500 W, with the grid relay open. SoC is a different measurement from solar power, and energy has to come from somewhere. Either PV was generating, or SoC and grid power are wrong as well.

This is recorded as a conflict, not as a verdict. The owner states PV relays shut down during an off-grid event; fwhai has since found that its dialog's "Solar PV will be disconnected immediately" is static text keyed on has_solar, with nothing reading a relay — so the statement and the readings may not be independent sources. pvRelay2 reading 0 while solarRelayStatus reads 1 is the best candidate for a PV relay that genuinely does open.

This test is how it gets settled — by a run with a prediction written down first, rather than by either side conceding.

Conditions required

  • Forecast. Open-Meteo GHI for the site predicting clear-sky PV above load + 5 kW across the window. With 6.6 kWp that needs a genuinely clear day near solar noon; a hazy day will not reach the threshold and the test proves nothing.
  • Battery headroom. SoC low enough to absorb at the full charge rate for the whole hour — below ~70%. A full battery curtails PV for a completely different reason and would confound the result.
  • Load. Normal. Do not add load to "help" — the point is to reach the limit.

FEAT-WEATHER-SOLAR-OPENMETEO is queued and unimplemented, so for a first run the window is chosen by hand from Open-Meteo's public forecast. Automating the trigger is a later step and must not gate the measurement.

Procedure

  1. T−24 h — check the Open-Meteo forecast; pick the hour bracketing peak GHI. Confirm SoC will be below ~70% at that time.
  2. T−30 min — notify fwh-modbus, fwh-modbus-bridge, fwh-cloud, fwhai, fwh-modbus-async with the fixed start and end time, as for the 2026-10-15 island.
  3. T−10 min — start recording on every channel. Direct Connect at 5 s: p_sun, p_load, p_fhp, soc, gridFreq, gridLineVol, solarRelayStatus, pvRelay2, mainRelay1/2Status, offgridState, run_status, dspRunstatus. Start before the transition — the 2026-10-15 capture began ~53 s after cutover and therefore has no on-grid baseline. That is the single most important lesson from it.
  4. T+0 — go off-grid: POST /api/offgrid {"on": true, "soc": <floor>, "confirm": true}.
  5. T+0 to T+60 min — observe. Do not intervene unless an abort condition fires.
  6. T+60 min — return to grid: POST /api/offgrid {"on": false, "confirm": true}. One hour is a cap, not a target. End earlier the moment the question is answered.
  7. T+70 min — confirm on-grid on all channels, and post the write-ack times so the others can align their captures.

Abort conditions — any one ends the test immediately

  • SoC falls below the off-grid floor and keeps falling.
  • p_load exceeds what PV plus battery can carry, i.e. the battery discharges hard with no solar — cloud cover during the window.
  • Any relay state the plan did not predict, especially mainRelay1/2Status changing while offgridState stays 1.
  • The bridge loses the gateway for more than two consecutive polls.
  • Anything the owner does not like. The owner's call ends it, no justification needed.

Safety notes

  • This is a write to hardware that changes dispatch — critical under CLAUDE.md. It needs the owner's confirmation in the session that performs it, every time.
  • The grid stays physically live. Islanding is not isolation and is not a reason to treat any circuit as dead.
  • The aGate is not a UPS. Anything that must not reboot needs its own UPS, including the machine running this bridge.

What the run should produce

A written result that states which predictions held, with the measurements, and what it did not establish. One site, one firmware, one day — a single clear run makes a hypothesis credible, not a mapping. In particular it will not establish the exact curtailment threshold unless PV genuinely exceeds it, which is why the forecast condition is a requirement and not a preference.