Smart Circuits — local API & UI design evaluation

Status: design, not implemented · Filed: 2026-09-13 Evidence: live reads of 1409 / 1411 / 1401 from a reference aGate, 2026-09-13; franklinwh-cloud/docs/; FWHAI Smart Circuits screenshot.


1. What the local channel actually exposes

Three cmdTypes. All three were read live; the results decide the design.

cmd name verdict
1409 smart_circuits The source of truth. Names, mode, SoC cutoff, protected-load flag and the schedule.
1411 smart_circuit_meter Live V / I / P + cumulative energy per channel.
1401 smart_circuit_schedule Do not use — see §1.2.

1.1 1409 carries the schedule, in the modern format

Real response from Circuit 1:

"Sw1Name": "Circuit 1", "Sw1Mode": 0, "Sw1ProLoad": 0,
"Sw1SocLowSet": 53, "Sw1AtuoEn": 0, "Sw1Freq": 0,
"Sw1TimeEn":  [1, 1, 0, 0],
"Sw1TimeSet": [1, 0, 1, 0],
"Sw1Time":    ["2026-06-19 16:02", "2026-06-19 17:03",
               "2026-06-19 20:11", "2026-06-19 20:12"]

Four schedule slots per circuit: TimeEn = slot enabled, Time = the datetime as a V2 string, TimeSet = per-slot flag (open/close pairing — slots read as on/off/on/off, matching [1,0,1,0]).

⚠️ RETRACTED 2026-09-14 — see §11

The claim below ("local schedule writing is reachable here and is not reachable from the cloud library") was the headline of this document and it is wrong. Live testing proved the aGate accepts 1409 schedule writes and silently discards them. Schedules are readable locally, not writable. The paragraph is kept for the record.

franklinwh-cloud/docs/API_COOKBOOK.md:1607 states the cloud library cannot write these:

"Until the exact V2 payload constructor is fully mapped natively, schedules should only be modified manually or toggled dynamically using boolean switches…"

The local channel hands us the whole block as plain JSON, and we already have a proven full-block read-modify-write against 1409 (set_smart_circuit, cmd 1409 opt:1). So local schedule writing is reachable here and is not reachable from the cloud library — the strongest argument for building this in the bridge rather than deferring to Automations.

1.2 1401 is a decoy — do not build on it

The catalog describes 1401 as the per-switch schedule. The live read says otherwise: every sw1–sw3 field is zero or empty while 1409 shows a real, populated schedule, and the response carries a fourth block that is plainly uninitialised memory:

"sw4Mode": 5, "sw4AtuoEn": 2, "sw4Freq": 809119792,
"sw4TimeEn": [859451440, 809120816, 16, 822083584],
"sw4Time": [":0", ":0", "0", "3"]

Those integers are ASCII bytes reinterpreted as int32. 1401 parses a 4-switch struct the firmware never fills. Reading it is harmless; writing to it is not something to attempt.

Action: the catalog.py entry for 1401 oversells it and should be corrected to name 1409 as the schedule source and mark 1401 unimplemented.

1.3 1411 metering, and what "energy metrics" really means

"Sw1Volt": 1020, "SW1Curr": 0, "SW1ExpPower": 0, "SW1ExpEnergy": 0,
"Sw2Volt": 0,    "SW2Curr": 0, "SW2ExpPower": 0, "SW2ExpEnergy": 0,
"CarSWCurr": 1,  "CarSWPower": -3,
"CarSWExpEnergy": 10077, "CarSWImpEnergy": 15458,
"freq": 499
  • Per-circuit power (ExpPower) and cumulative energy (ExpEnergy) exist — so "Current draw / Energy today" in the FWHAI card is reproducible, except that these are lifetime counters, not daily. A daily figure needs the bridge to difference the counter across midnight — which is exactly what the bridge's metrics DB is for. Do not claim "today" from a raw read.
  • freq: 499 → 49.9 Hz confirms the ÷10 scaling. But Sw1Volt: 1020 → 102.0 V does not match AU 230 V mains. Both circuits are currently OFF, so this is unverified: confirm the voltage scale with a circuit switched on before showing volts in the UI.

2. The region question: 3 circuits (US) vs 2 (AU)

Cloud CAPABILITY_RESOLUTION_SPEC.md Rule 2 is explicit: country_id == 3 (AU) ⇒ circuit_count = 2, "Channel 3 controls are ignored or hidden". Rule 1 forces has_v2l = False for AU.

The local channel gives no clean discriminator. Two problems:

  1. 1409 always returns three blocks. This AU gateway reports Sw3Name: "Circuits 3", Sw3SocLowSet: 20, Sw3Freq: 15, with Sw3Time all "2000-01-01 …" — factory defaults for a channel that was never configured. Presence of Sw3* proves nothing.
  2. The cloud's discriminator is missing locally. Cloud reads modeChoose from 311 (modeChoose: 3 ⇒ 3-circuit). Our 1409 response has no modeChoose — only SwMerge: 0 (the US multi-aGate merge flag).

And the obvious local fallback — "count the metering channels in 1411" — is a trap: GENERATOR_V2L_API.md:215 states the CarSW port is Sw3 in the 311 payload. So 1411's three channels are SW1, SW2, CarSW(=Sw3) — the third circuit is metered under the CarSW name, not SW3. Counting SW<n> keys yields 2 on any unit, US or AU.

Worse, this AU unit reports CarSWExpEnergy: 10077 / CarSWImpEnergy: 15458 — non-zero lifetime counters on a channel AU is supposed not to have. Stale registers or a wired channel; one device cannot tell us.

Recommendation

Do not auto-detect from the payload shape. Instead:

  1. Config-first: a SMART_CIRCUIT_COUNT setting (auto | 2 | 3), default auto.
  2. auto = a stated heuristic, not a guess dressed as a fact: treat circuit 3 as absent when its schedule is entirely factory-default (Sw3Time all 2000-01-01) and it has never been renamed from the default. Surface it in the UI as "Circuit 3 — not detected (override in Settings)" rather than hiding it silently.
  3. Never hide the raw data. /api/cloud/smart_circuits_info keeps returning all three blocks verbatim; region logic belongs in the presentation layer only.

Defect filed against franklinwh-cloud — issue #7: API_COOKBOOK.md:1610 claims "AU grids standardise on 3 physical outputs per aGate with V2L". That contradicts CAPABILITY_RESOLUTION_SPEC.md Rules 1 and 2 (AU = 2 circuits, no V2L) and DISCOVER_IMPLEMENTATION_PLAN.md:102 (AU SC 302 has no V2L port). The spec and the hardware agree; the cookbook prose is wrong and should be corrected.


3. Where the bridge stands today

Already built:

  • client.read(…, "smart_circuits") → 1409, and set_smart_circuit(circuit, on) (full-block RMW + read-back verify).
  • cloud_compat.smart_circuit_detail() — already maps the V2 schedule arrays (time_enabled / time_schedules / time_set). The data is reaching the API today.
  • /api/cloud/smart_circuits and /api/cloud/smart_circuits_info.

Gaps:

gap note
smart_circuits_map() hardcodes range(1, 4) Emits a phantom circuit 3 on AU. First thing to fix.
No 1411 metering anywhere No power or energy per circuit.
Writes limited to on/off No schedule, no SoC cutoff, no load limit.
No UI at all Smart Circuits has no tab.

4. Proposed API

Noun-scoped, matching the cloud CLI convention we settled on for EPIC-CLI-ALIGN.

GET    /api/circuits                  → [{id, name, on, mode, pro_load, soc_cutoff{…},
                                          power_w, energy_kwh, volts, amps, present}]
GET    /api/circuits/{id}             → one circuit, incl. schedule slots
POST   /api/circuits/{id}/power       {on: bool}            # exists as set_smart_circuit
PUT    /api/circuits/{id}/schedule    {slots: [{enabled, start, end}]}
PUT    /api/circuits/{id}/soc_cutoff  {enabled: bool, soc: int}

Design rules, all of them consequences of §1:

  • One 1409 read + one 1411 read per refresh, in a single aGate session — the same pattern as battery(). Never one session per circuit.
  • Every write is a full-block RMW on 1409 with read-back verification, reusing the proven set_smart_circuit path. There is no partial write to 1409.
  • Slot model: expose 4 slots as 2 on/off pairs (TimeSet [1,0,1,0]), not 4 opaque datetimes. Validate before writing — the firmware will happily accept an end before a start.
  • Energy is a lifetime counter. energy_kwh is reported as such; a "today" figure is derived by the bridge from stored samples, and is null until there is a midnight baseline.
  • Schedule writes are the risky half. They must land behind the same confirm-and-verify treatment as other writes, and the first hardware test should use circuit 2 ("Test Switch"), not the live Circuit 1.

5. Proposed UI

A Smart Circuits tab in the sidebar, between Control and Battery (mirroring FWHAI's ordering), with per-circuit cards:

● Circuit 1                                   [ ON ]
  CURRENT DRAW            ENERGY (TODAY)
  0 W                     0.00 kWh
  ────────────────────────────────────────────────
  Circuit Power                          (toggle)
  Mode: Schedule · SoC cutoff 53%          [Edit]

Beyond FWHAI — and the reason to build it rather than defer to Automations:

  • Schedule editor on the card's Edit: two on/off windows per circuit, enable toggles, a read-back confirmation. This is the capability the cloud library documents itself as lacking, and FWHAI deliberately omits.
  • SoC-cutoff control (SocLowSet + AtuoEn) — cloud parity with set_smart_circuit_soc_cutoff.
  • Absent circuit shown, not hidden — per §2, a greyed "not detected" card with a Settings override, so an AU user sees why there are two.

Relationship to the Schedule engine

SCHEDULE-AND-AUTOMATIONS is the bridge's own scheduler and does not exist yet. The 1409 schedule is different in kind: it runs on the gateway, so it keeps working when the bridge is down. These are complementary, and the UI must not blur them —

"Schedules set here run on the aGate itself and continue if the bridge stops. Bridge Automations are more flexible but require the bridge to be running."

When the engine lands, a circuit driven by a bridge automation should show that on the card so two schedulers fighting over one relay is visible rather than mysterious.


6. Open questions

  1. Voltage scale (§1.3) — resolve with a circuit switched ON.
  2. Sw1Freq / Sw3Freq (0 and 15) — unexplained. Not "frequency" in the 49.9 Hz sense.
  3. US 3-circuit shape — unverifiable without US hardware. The region heuristic must stay overridable for that reason alone.
  4. SwMerge — US merged circuits across chained aGates. Out of scope; read-only for now.
  5. Sw1MsgType — written as the RMW target flag; its read meaning is unconfirmed.

7. Phasing

phase scope risk
1 Fix range(1, 4); add 1411 to the read; GET /api/circuits; read-only UI cards with power + on/off (toggle reuses the proven write). low
2 SoC cutoff write; energy-today from the metrics DB. medium
3 Schedule editor + PUT …/schedule. Hardware-test on circuit 2 first. high — first unproven write
4 Automations integration (FEAT-BMS-SESSIONS-SCHEDULED pattern): circuit actions in the schedule engine, with gateway-vs-bridge ownership shown on the card. after engine

8. CarSW — working hypothesis (2026-09-14)

User hypothesis: CarSW refers to US Smart Circuits where switch 1 and switch 2 (120 V) are merged, giving a V2L input mode — and only when the Generator module is also installed.

Partly corroborated by this repo's own docs. CLI_SUPPORT_INFO.md:359 derives V2L from "Country + SC version + Generator presence" and states:

AU=no port; V2 SC=built-in; V1+Gen=CarSW

So CarSW is the V2L path on V1 Smart Circuits with the Generator module — the generator dependency in the hypothesis is documented. GENERATOR_V2L_API.md:215 adds that on such a system modeChoose=3 reports a 3-circuit layout (Sw1 + Sw2 + Sw3/CarSW).

The merge half is plausible but not documented: SwMerge exists in 1409 (0 on this AU gateway) and the cloud describes merged circuits as a US feature, but nothing ties merging to the CarSW port. Recorded as a hypothesis, not a fact.

Either way it reinforces the phase-1 decision to surface CarSW as its own channel rather than folding it into circuit 3: on this AU gateway SwMerge=0, no generator is installed (genEn=0, genModel="", cmd 1901) and V2L is region-disabled — yet the CarSW counters are non-zero and still climbing (100.77 → 100.81 kWh out across a day). Whatever is feeding them, it is not a V2L port that the documented rules say cannot exist here. Unresolved; needs a US V1+Generator system to settle.


9. Vendor documentation check (2026-09-14)

Read against FranklinWH's own support pages (Smart Circuits, Generator).

Confirms:

  • Scheduling exists as a first-class mode — "Customize the time period or electricity consumption to automatically turn the circuit on or off" — matching the on/off slot pairs in 1409.
  • Merging is real and load-based: three circuits "can be controlled independently or merged if they share electrical infrastructure". That is direct support for the CarSW/merge hypothesis in §8, and gives SwMerge a concrete meaning.
  • SoC auto cut-off is an OFF-GRID feature, not a general one: it "automatically disconnect[s] circuits in sequence based on battery SOC during a grid outage". This explains SwXSocLowSet (53% on circuit 1 here) and ties the smart-circuit surface to docs/OFFGRID_DESIGN.md — the cutoff only bites when islanded, so the UI should say so rather than implying it applies on grid.
  • Overload protection disconnects circuits when load exceeds panel capacity. No local field for this has been identified; a circuit may therefore switch off for reasons the bridge cannot see.

Does not settle the region question. The AU page says "three configurable circuits", contradicting CAPABILITY_RESOLUTION_SPEC.md (AU = 2) and this AU gateway, which physically has two. The page appears region-agnostic marketing served under /au/. Hardware and the capability spec agree with each other, so the evidence-based detection in §2 stands — this is exactly why SMART_CIRCUIT_COUNT must remain overridable, and why present is reported with its reasoning rather than as a bare count.

Corrects our generator reading. The generator page states the generator supports "up to 3 non-overlapping operating periods (00:00-23:59) with minimum 1-minute intervals between them" — which is exactly the charge1..3 trio in 1901. Those are the generator's operating windows, not the grid-charge windows the catalog guessed at, and not the uninterpretable block this repo previously called them. The maintenance mapping is confirmed too: "exercise duration and interval period, specific day of week and start time" ↔ manoTime / manoFre / manoDate / manoStartTime.


10. SyHdVersion — the discriminator §2 said did not exist (2026-09-14)

§2 concluded the local channel has no clean way to tell a 2-circuit gateway from a 3-circuit one. That was wrong. The 1101 login manifest carries:

"SyHdVersion": 102

This is FWHAI's sysHdVersionInt, and 102 is aGate X-01-AU (SKU AGT-R1V1-AU, 100 A). It arrives with every login, so every session already had the answer.

Detection now takes the model's channel count as a prior with one-way force: the model can rule a circuit out, and can settle an unknown, but it can never rule one in — a gateway that supports three circuits may have no enclosure fitted at all. So installed: false remains reachable on a 3-circuit model, and SMART_CIRCUIT_COUNT still overrides everything. source reports which decided it: detected, model+detected, or setting.

This also reconciles the old service-amps argument: FWHAI's 100 A is the model's rated capacity (a device-class fact), while the site's install profile reads 63. Two different quantities, not a contradiction.

Vendor "Backwards Compatibility Statement" (rev US V1.0, 21 July 2026)

Authoritative for SKU ↔ model naming and accessory fit — with one large caveat: it is the US/Canada revision and contains no AU models whatsoever, so it cannot settle the AU circuit count. What it does give:

SKU vendor name accessory generation
AGT-R1V1-US aGate X 1.1 ACCY-GENV1-US, ACCY-SCV1-US fit 1.0/1.1
AGT-R1V2-US aGate X 1.3 ACCY-GENV2-US, ACCY-SCV2-US fit 1.3/1.3.1
AGT-R1V3-US / -CAN aGate X 1.3/1.3.1 —
  • Naming mismatch: FWHAI labels these "aGate X-10 / X-20"; FranklinWH calls them "aGate X 1.1 / 1.3". Both are kept (model = FWHAI's, vendor_model = the vendor's) so the two projects can be cross-read without either being silently "corrected".
  • Discrepancy recorded, not resolved: FWHAI lists ACCY-SCV2-US as compatible with gateway 102 (AU), while the vendor document scopes SCV2 to "aGate X 1.3/1.3.1". Since the document covers no AU hardware, neither source settles it — so the row carries a note rather than a silent edit.
  • ACCY-SCV1-US remark: "pre-assembled smart circuit, not support aPower S".
  • Fleet limits captured: 15 aPowers per aGate (8 when mixing aPower X with aPower 2; up to 8 aPower S on 1.3/1.3.1), 4 on MAC 1.

11. Live test of the schedule write — it is discarded (2026-09-14)

Tested on circuit 2 ("Test Switch") with the user's authorisation. The write does not work, and §1.1's headline claim is retracted.

# payload reply read-back
1 two windows, enabled: false result: 0 unchanged
2 same, with SwXMsgType target selector set (all 0, target 1) result: 0 unchanged
3 window 1 enabled: true result: 0 unchanged

The control rules out the transport. Immediately after attempt 3, an on/off write on the same command, same circuit, same session shape flipped Sw2Mode 0→1→0 with the read-back confirming both directions. So 1409 writes are being applied — the schedule fields specifically are ignored.

This is the signature already documented for 1405 mode_soc: "writes are accepted (result:0) then silently discarded — reserve is cloud-owned." Schedules appear to be cloud-owned in the same way, which also explains why the cloud library declines to write them (API_COOKBOOK.md:1607) — that is a vendor-side constraint, not a gap we could route around locally.

No collateral damage. The full block is echoed on every attempt, and a field-by-field diff of all 39 fields against the pre-test capture showed no change whatsoever after six writes. The read-back safety net did exactly its job: every attempt reported ok: false rather than trusting result: 0.

Consequences - The API keeps PUT /api/circuits/{id}/schedule — harmless, self-verifying, and it may be honoured on other firmware — but the response now carries discarded: true for the accepted-and-ignored case so result: 0 can never read as success. - The UI's schedule editor is removed; schedules render read-only with the finding and a pointer to the FranklinWH app. - Phase 3 of §7 is not achievable on this firmware. Re-test after any gateway firmware update — the whole finding is firmware-specific. - The lesson generalises: on this device an opt:1 ack means "frame parsed", not "setting applied". Every write needs a read-back, and any future write surface should assume discard until a re-read proves otherwise.


12. CarSW resolved — the Generator Module is the V2L port, and doubles as a circuit

Source: FranklinWH "Generator Module as Smart Circuit Operations Guide" (12 pp).

"The FranklinWH System provides integration for third-party standby generators / Vehicle-to-Load (V2L) through its optional Generator Module. The module also functions as a Smart Circuit for a large load…" "The maximum capacity of the Smart Circuit is up to 160 A." "Once the generator module is configured for Smart Circuit use, it cannot be used for [generator]."

This closes §8's open question. The Generator Module is a single physical port with three mutually exclusive roles — generator input, V2L input, or a (large, up to 160 A) smart circuit. That explains every loose end at once:

  • why CarSw* (V2L) fields sit inside 1409, the smart-circuit command, next to generator fields;
  • why the cloud documents "the CarSW port is Sw3";
  • why CLI_SUPPORT_INFO.md:359 reads V1+Gen=CarSW — V2L exists only when the Generator Module is fitted, because the module is the port;
  • why the user's original instinct ("V2L input only if the Generator Module is installed as well") was right about the dependency.

The mutual exclusion is vendor-stated, not inferred. OFFGRID_DESIGN.md §6 proposed that the bridge enforce a generator/V2L interlock in software "and not claim the device does". That proposal stands, and now has an explicit justification: the vendor says the configuration is one-or-the-other, so a UI offering both simultaneously is offering something the hardware cannot do.

Not resolved: why this AU gateway's CarSw* export/import counters keep climbing with SwMerge = 0, no generator (genEn 0, genModel "") and V2L region-disabled. The port's identity is now explained; the counters are not.