What the local API can do that FWHAI and Modbus cannot

Filed: 2026-09-14 · Counts from franklinwh_local.catalog (70 commands), the franklinwh-cloud source, and modbus_capability.json (44 points).

Important distinction (corrected 2026-09-29): FWHAI (the Home-Assistant integration) is not the same as the franklinwh-cloud API. The cloud library implements much more than FWHAI surfaces — a sendMqtt relay (211/311/315…), a ForceMixin, generator/power-control writes, and rich location reads. So "FWHAI can't do X" does not imply "the cloud API can't." Claims below are scored against the cloud API (the franklinwh-cloud package), and call out where the only gap is FWHAI's exposure. Modbus is a separate, narrow control plane.


1. Installer-grade DER / grid-compliance control — the biggest gap

1205 der_comms — the SunSpec Modbus and IEEE 2030.5 / CSIP on-off toggles. No cloud equivalent exists: grepping franklinwh-cloud for sunsMdEn, sunspec or 2030 returns nothing. Modbus obviously cannot serve the switch that enables Modbus. Only the local API can turn Modbus TCP on or off, which also makes it the thing the Modbus bridge depends on but cannot provide for itself.

~27 individually addressable compliance commands — 1203, 1211–1229, 1251–1277: OV/OF trip points, fixed power factor, Q(V), P(V), P(f) droop, reconnect ramp, DC injection, ride-through flags, battery grid-access mode, ES voltage window, ES reconnect timing, constant-PF, constant-Q, PV/QP/QV curves, ramp rate, fast reconnect.

The catalog marks these as having a cloud equivalent, but that overstates it: the cloud collapses the whole lot into one read (get_grid_profile_info(requestType=2)). Local exposes each as its own command with its own fields. Read granularity is far higher, and per-setting writes are reachable here and nowhere else.

2. Firmware OTA — 1501 / 1503

firmware_deliver and firmware_upgrade. No cloud equivalent (no OTA methods in franklinwh-cloud), none in Modbus. Writing pushes a firmware file / triggers an upgrade — the most dangerous pair in the catalog, and untested here on purpose.

3. Generator configuration beyond mode — 1901

Cloud offers set_generator_mode() (manuSw auto/manual) and set_generator_charge_schedule() (the three chargeN operating windows via POST updateIotGenerator — mixins/devices.py:1081), which matches the local block's chargeNEn/StartTime/EndTime. What is genuinely local-only is the rest of the 1901 block (hardware-verified 2026-09-14): the maintenance-exercise schedule (oilmanoEn/manoFre/ manoDate/manoStartTime/manoTime) and the auto start/stop SoC-threshold writes (genStartElec/ genCloseElec — the cloud only reads these). Modbus has no generator surface at all.

4. Commissioning and device identity

Narrower than previously claimed — the cloud covers most of this: - Device enumeration IS on the cloud: get_accessories(option=3/4) (mixins/devices.py:84), get_apower_info() (aPowers by serial), get_site_and_device_info() (mixins/account.py:101). Genuinely local-only is only the per-device commissioning checkResult flag (devMap[].checkResult) — grep of the cloud package for checkResult/devMap returns nothing. - 1123 agate_serial is NOT local-only — the serial IS the cloud gatewayId used by every call and is returned by get_home_gateway_list() (mixins/account.py:13) and get_apower_info(). - 1201 time_location is largely covered by the cloud — time + tz: get_device_info() deviceTime + zoneInfo (mixins/devices.py:465); DST + GPS: get_equipment_location() dst + coords (mixins/account.py:147); postcode: get_device_detail() postCode (mixins/devices.py:1976). The local edge is only that it returns them in one gateway-direct read.

5. Maintenance controls — 1721

The local 1721 block carries reboot, reset and update. reboot and reset are NOT local-only — the cloud's own sendMqtt cmdType 315 payload structurally exposes both (alongside cleanUnlockAlarm/cleanLockAlarm/cleanAlarmFlag); both surfaces refuse to populate reset by policy, so it is symmetric, not local-only. Only update is genuinely local-only (no cloud OTA/update method — see §2). reset is almost certainly a factory reset, so it stays unexposed on both.

6. Deep telemetry FWHAI does not surface

  • 1705 per-cell BMS — 16 cell voltages, per-cell temperatures. The cloud can reach this (211 type 2/3) but FWHAI publishes no per-cell entities; Modbus has none.
  • 1703 power electronics — inverter/DC-bus detail, per device.
  • 1827 ibg_state,1835` device_states — DSP/PE/BMS state machines.
  • 1829 event_block — the gateway's own event log.
  • 1701 install_profile — the electrical install-profile fields (electricSys/airSwitchCur/…) are genuinely uncovered. But the grid power-plane limits are NOT: gridSoftLimit/gridHardLimit (≈ globalGridChargeMax/DischargeMax) and isPcsDischgEn have cloud read+write via get/set_power_control_settings (mixins/power.py:44,53) and update_system_settings (:2321).
  • 1801 battery_inhibit — charge-inhibit thresholds and the blackstart flag. (Unreadable on this firmware: returns field positions, not values.)

7. Five undecoded commands

1207, 1209, 1821, 1823, 1825 — present locally, absent from every other surface, purpose unknown. Recorded so they are not mistaken for something known.


The other direction — what local CANNOT do

Worth stating so this reads as a comparison rather than a boast:

capability local who has it
Reserve SoC write (Self / TOU) ❌ no path at any opt Cloud updateSocV2 (REST); Modbus 15508 for Self if installer-unlocked
Smart-circuit schedule write ❌ accepted and discarded Cloud/app only
Dispatch, storm hedging, tariff automation ❌ not device data FWHAI's own engine
WiFi/mobile signal, network state ❌ out-of-band locally Cloud 317/341
SunSpec standardised DER control ❌ Modbus models 701/702/704/710/713/714/715
Register-speed control loop ❌ Modbus TCP

The short answer

The local API's genuinely unique territory (after the 2026-09-29 cloud-inventory re-check) is the installer / commissioning write surface: the DER-comms (SunSpec / 2030.5) on-off toggle, per-setting grid-compliance writes (the cloud only reads the profile), firmware OTA, the 1721 update (factory-reset-class) control, the per-device commissioning checkResult, the generator maintenance-exercise schedule + SoC-threshold writes, and the electrical install-profile fields — plus deep per-device telemetry that FWHAI doesn't publish. NOTE: device enumeration, the gateway serial, gateway time/timezone/DST/GPS/postcode, generator charge-windows, reboot/reset, reserve SoC, schedules, and the grid power-plane limits are all reachable via the cloud API (just not all via FWHAI). Modbus owns standardised, fast DER control.

The single most consequential item is 1205: the local API is the only way to turn SunSpec Modbus and IEEE 2030.5 on or off — so it gates the existence of the Modbus control plane itself.