Connection design — sessions, staleness and failure, for both channels

Status: DRAFT for review. No code until this is agreed. Written 2026-10-12. Measurements are from the running bridge against the reference aGate at 192.168.0.110, read-only.

Partly superseded, 2026-10-13. The owner has directed that this bridge retire its DIRECT Modbus TCP and reach the same capabilities through the Modbus Bridge's REST API — see MODBUS_VIA_REST_DESIGN.md. That removes the Modbus half of §4.1, including the dependency on a pysunspec2 change we do not own. The LOCAL-channel half (TCP 9000, §1.4) still stands and is unaffected.

Companion: the Modbus Bridge's docs/dispatch-reliability-design.md (david2069/franklinwh-modbus-bridge PR #57). Its §5.2 reaches the same conclusion on connection ownership from a different starting point. Where this document agrees, it says so rather than re-deriving; where our situation differs, it says why.


1. The problem, measured

This bridge opens a new TCP connection for almost every interaction with the gateway, on both channels, and closes it again immediately.

1.1 What the sockets say

Sampled from the container's own network namespace, to 192.168.0.110:502:

State Count
TIME_WAIT 38
CLOSE_WAIT 4
ESTABLISHED 0

TIME_WAIT lasts 60 s, so that is roughly 38 connections opened and closed in the preceding minute — by us alone — while holding no live connection at all. The peer's independent sample over 60 s saw "at least 9" from this container; the difference is sampling (theirs was every 2 s and misses short-lived sockets), and the socket table is the more complete count.

CLOSE_WAIT is a separate defect. It means the gateway closed and we have not. Four sockets are sitting in a state only our process can clear. That is a leak, not churn, and it is invisible in any log.

1.2 What the logs say

8 × franklinwh_modbus.controller: Connection failed: Response timeout in 30 minutes, 1–4 minutes apart. The Modbus Bridge logs the same error 1,249–2,289 times a day against the same device.

1.3 Why the count is so much higher than the call count

Our own call sites are few:

Caller Cadence
~~VPP monitor → battery_control.status()~~ ~~60 s~~ — removed 2026-10-12: VPP is read locally (1707 programme id), so this path opens no socket
~~Poller summary() → port_open(host, 502)~~ ~~every poll (30 s)~~ — removed in 0.5.9 (#221): modbus_502 is the last real connection's result, and no socket is opened to show it
cached_ratings() 1 h TTL
~~GET /api/battery/command → battery_control.status()~~ ~~every 30 s per open browser tab~~ — 0.5.9 (#223): cached; refreshed at most hourly, when the Battery control is shown (at most once per 30 s), or by Control → Modbus client → Test
/api/battery/control/status on demand

The VPP monitor has since been moved to the local channel and no longer opens a socket at all, which removes roughly one connection per minute per gateway from the figures below.

Three or four calls a minute cannot produce 38 connections — so the multiplier is inside the library. The fwh-modbus session established why, and then corrected its own first answer: this is verified in the deployed pysunspec2 1.3.6 (ModbusClientTCP.read: local_connect → disconnect), and it applies to writes as well as reads — one send_command is about 7 TCP opens:

  • connect() builds the device and runs a full scan(), which opens one connection for the scan and closes it at the end. The session is left with no socket.
  • Thereafter every model.read() opens a TCP connection, reads, and closes it in a finally. read_control_status() is M704 + M715, so ~2 connections. A full status pass is 6–8.
  • is_connected() is itself a register read — so checking the connection opens one.
  • reconnect() discards the device, sleeps 1 s, and performs a full rescan (17 models on this aGate) before retrying.

So one status() call is not one connection; it is a scan plus several reads, each its own socket. And a failure costs more than a success, because the retry path rescans.

The consequence for this design, stated plainly: connections-per-minute is mostly a measure of REQUEST COUNT, not of reconnects. We are not leaking connections through bad lifecycle management on the Modbus side — we are making a normal number of requests through a library that spends a socket on each one. That changes what a fix looks like (§4.1a).

One more library behaviour worth recording: it treats any exception whose message contains "modbus" as a dead link, so a device exception reply — a legitimate protocol answer — triggers a reconnect and a full rescan. Whether that materially inflates reconnect rates is an open hypothesis, not a finding.

We also make it worse ourselves, twice:

  1. The liveness probe is any(port_open(host, 502, timeout=3.0) for _ in range(3)). port_open is a real socket.create_connection. A healthy gateway costs 1; an unreachable one costs 3 connects × 3 s, every 30 s. The bridge probes hardest exactly when the device is least able to answer.
  2. That probe runs for mock gateways too — summary() does it unconditionally, so each in-process mock tries 127.0.0.1:502 every poll. Pointless, and it makes modbus_502 meaningless for mocks rather than absent.

1.4 The local channel has the same shape, less visibly

client.py has 32 _client(s, host) call sites. Each is with _client(...) as c: c.login() — a new TCP connection to :9000 and a fresh login per call. The poller's summary() at least batches its reads into one session, which is why it was written that way; every other REST endpoint does not.

This channel has not shown symptoms, so it is not the urgent half. It is in scope because the same design should cover it, and because adding the grid-voltage read (phase 3) put one more read inside that session rather than another session — the right instinct, worth making a rule.


1.5 · The local session belongs in the LIBRARY, not here

Owner's direction, 2026-10-13. A held session for TCP 9000 is to be designed and implemented in the franklinwh-direct-connect-api library. The bridge changes afterwards, consuming it. A bridge-side wrapper around the library's client was started and deliberately abandoned — it is the wrong layer, and it would have left the library still shipping connect-per-call to every other consumer.

What was established before stopping, which the library work can start from:

  • DirectConnectTransport.connect() is already idempotent — it returns immediately if _sock is not None. Holding a session needs no transport change to begin with.
  • The transport already carries _logged_in, whose own comment reads "re-login after a transient reconnect". The re-login path was anticipated and never exercised, because nothing ever kept a connection long enough to need it.
  • The bridge has 31 with _client(...) as c: c.login() sites. 30 of them call login() immediately. So the pattern is uniform, and migrating is mechanical once the library offers a session.
  • Cost today: the poller alone opens a fresh TCP connection and a fresh login per gateway every poll_interval (30 s). On this site that is ~2 sessions/minute for the real gateway plus the mocks, each with a full login round-trip.

Why the library is the right layer: the session, its lock, reconnect, idle close and the re-login-after-reconnect path are all properties of the connection, which the library owns. Put them in the bridge and every other consumer — the CLI, the emulator, any third party — keeps paying connect-per-call, and the bridge grows a second connection model alongside the one it already needs for Modbus.

2. What we do not know, and must not guess

Taken from the Modbus Bridge's unknowns, because they apply identically to us and neither of us should answer them twice.

# Unknown Why it decides something
U1 The aGate's concurrent-connection limit on :502, and its behaviour when exceeded (refuse? drop the oldest? slow everything?) Decides whether one connection is a preference or a hard requirement
U2 Response-time distribution with a single quiet client Separates "slow device" from "contention", and sets timeouts
U3 Cost of a full model scan, and whether reconnect-with-rescan is itself a cause of timeouts Decides whether reconnect may skip the rescan
U4 Whether churn (many short connections) behaves differently from a few long-lived ones Decides whether this design is a fix or merely tidier
L1 Whether our CLOSE_WAIT sockets are a library leak or ours Ours to answer; see §6
L2 Whether the library's "any exception containing modbus means dead link" rule inflates our reconnect and rescan rate Decides whether request reduction alone helps

(Numbered L* so they do not collide with the Modbus Bridge's U* list, which is shared between both repos and has its own U9.)

Explicitly: nobody should discover U1 by exhausting it on the live site. Both bridges have agreed that.

There is one thing we can state now: with three independent clients (this bridge, the Modbus Bridge, Energipay) each churning connections, the device's socket table is driven by turnover, not by concurrency — and TIME_WAIT entries occupy it after the conversation has ended. A limit expressed in concurrent sockets can still be reached by three processes that are each "only using one at a time".


3. Goals

  1. Stop the churn. One owned connection per gateway per channel, reused.
  2. Never probe with a throwaway socket. Liveness is a property of the owned connection's recent history, not a separate connect.
  3. Make a stale value say so. A cached reading served after a failed read must be labelled stale with its age, never presented as current.
  4. Fail honestly — reuse the phase 3 Outcome{ok|failed|unknown|skipped} rather than inventing a second vocabulary for the same distinctions.
  5. Mocks cost nothing. A mock gateway must not open, probe, or account for any Modbus socket.
  6. Measurable before and after. Per-gateway counters, so the claim "this reduced churn" is checkable rather than asserted.

Non-goal: a connection pool. The question asked for pooling; the answer is that pooling is the wrong shape here. A pool exists to serve concurrent callers from several sockets. Against a device whose connection limit is unknown and probably small, more sockets is the failure mode, not the remedy. What we want is the opposite: exactly one connection per gateway, with callers queued behind it. That is also what the Modbus Bridge concluded (§5.2) and what Home Assistant's ModbusHub does — one client per hub, every call serialised through one lock, a failed call logged and returning None without tearing the connection down.


4. Design

4.1 One session object per gateway, per channel

A GatewaySession owns the connection for one gateway on one channel (local :9000, modbus :502). It is created on demand, holds the socket, and serialises every caller through a single lock. Nothing else opens a socket to that gateway.

Keyed by (gateway_id, channel) in the existing gateway registry — not global, because two gateways are genuinely independent and must not queue behind each other.

Why a lock and not a pool: the device is the scarce resource, not our CPU. Queuing two callers behind one socket is correct behaviour against a device that may only tolerate one. Latency under contention is the price, and it is visible (§4.6) rather than hidden.

4.1a The Modbus half of §4.1 is blocked on a library change

This must not be glossed. A GatewaySession that owns a socket achieves nothing on the Modbus channel while pysunspec2 opens and closes its own connection per read and per write. Holding our socket open underneath that simply adds an idle socket to the device's table.

So the Modbus side of this design splits in two:

Part Owner Available now?
Stop making unnecessary requests (delete the probe, skip mocks, de-duplicate status calls) us yes — and it is the only Modbus-side lever we hold
Hold one connection across requests franklinwh-modbus / pysunspec2 no — needs their change

That is an argument for sequencing, not for waiting: request reduction is worth doing on its own, is independently measurable, and does not depend on anyone else's schedule. The session object should be built for the local channel first, where we own the whole path, and extended to Modbus when the library can keep a socket.

4.2 Connection lifetime and liveness

  • Opened lazily, on first use, not at boot. A gateway nobody reads costs nothing.
  • Kept open across calls. No close-per-read.
  • Liveness is inferred, never probed. The session already knows when it last succeeded; that answers "is this up" without a socket. This deletes the port_open × 3 probe outright, and with it the "hammer a dead device harder" behaviour.
  • Idle close after a configurable idle period, so an untouched gateway does not hold a socket on the device indefinitely. Default proposed: 10 minutes. The right value depends on U1; stated here so it is a decision, not an accident.
  • Reconnect is bounded by backoff, and a failed reconnect does not immediately try again — a reconnect storm is how a brief outage becomes a sustained one.

4.3 Where staleness lives

Phase 2b already records per-leg link history: first/last success, consecutive failures, outage rows, and a 3-strike debounce before a link is called down. The session reports into that, rather than growing its own parallel notion of health.

Served values carry {value, as_of, stale}. stale is set when the last read failed and a cached value is being used. The Modbus Bridge found the same defect from the other side (its C8: "Derived 4 battery key(s) from M713 model cache" published as current). A cached number presented as live is worse than a gap, because nothing downstream can tell.

4.4 Timeouts, retries and outcomes

No new retry machinery. Phase 3's resilience.call already provides deadline, retry classification, and the ok / failed / unknown / skipped verdict — including the rule that an ambiguous write is never retried. The session wraps its I/O in that.

What the session adds is the connection-level distinction resilience cannot see:

Situation Verdict Connection action
Read succeeded ok keep
Read failed, socket healthy (device said no) failed keep — do not tear down over a refusal
Transport error / timeout failed mark suspect; reconnect on next use, with backoff
Write timed out after sending unknown keep, never auto-retry, report loudly

"Do not tear the connection down over a failed call" is taken from ModbusHub and is the opposite of what we do today, where any exception discards the client and the next call pays for a full rescan.

4.5 Mocks

A mock gateway (is_mock) gets no Modbus session at all — not a failed one, not a probe. modbus_502 becomes None ("not applicable") rather than False ("tried and failed"), consistent with the rule established in phase 2b that a leg which was never measured is reported as not measured rather than omitted or failed.

Mocks keep a local-channel session, because that is what they emulate and the emulator is the only way to test the session logic without touching the live aGate.

4.6 Observability

Per gateway, per channel: connections opened, reads, read failures, timeouts, reconnects, failed reconnects, time spent waiting on the lock, and current socket age. Surfaced on the Network tab beside the existing Link history card.

The lock-wait counter is the one that matters for this design: it is how we find out whether serialising callers behind one socket costs anything in practice.


5. What this does not fix

  • Other clients. We cannot stop the Modbus Bridge or Energipay opening connections, and should not try. We can count ours honestly and show other visible connections for correlation — the Modbus Bridge's §5.3 takes the same position.
  • The library's per-read connect/close. Our session can hold a socket, but if pysunspec2 opens its own per model.read(), holding ours achieves nothing on that path. This is the part that needs fwh-modbus, and it is the single biggest lever. Until it changes, our Modbus-side gain is limited to deleting the probe and the duplicate status calls.
  • Whether any of this is the cause of the timeouts. It is a plausible contributor. U1–U4 decide it. Shipping the design and then finding the timeouts unchanged would still leave us better off, but we should not claim a cure we have not measured.

6. Proof, before and after

Measure first, and for long enough. The Modbus Bridge added a §5.4 "Measurement (Phase 0b)" that ships before any fix and requires at least 7 days of baseline before anything changes. Adopted here, and the reason is worth stating: without it, "this reduced churn" is a claim about a number nobody wrote down. Seven days also covers a weekday/weekend cycle and at least one of the daily timeout peaks.

What to record per gateway per hour, for both channels — the same shape they are using, so the two bridges' numbers can be compared rather than merely coexisting:

  • requests ok / timeout / error, with the exception class;
  • latency p50 / p95 / max;
  • connections opened, per path;
  • reconnects, failed reconnects, rescans;
  • data freshness (age of the newest good value).

Phase 2b's link history already records a subset of this per leg. This extends it rather than starting a second table.

  1. Baseline, now: socket-state census and timeout counts per hour, with the three clients running as they are. Partly captured above; needs 7 days, not 24 h.
  2. Answer L1 ourselves: find what leaves sockets in CLOSE_WAIT. This is our bug regardless of the rest of the design, and it is the cheapest thing here.
  3. Emulator first. Exercise session reuse, idle close, reconnect backoff and staleness against the in-process mock. No live aGate.
  4. Coordinated live window for U1–U4, run jointly with the Modbus Bridge session — their experiments E0–E4 answer our unknowns too, and running them twice against one device would itself be contention.
  5. After: repeat the census. The acceptance test is a drop in connections opened per minute, with no increase in failed reads.

7. Decisions needed from the owner

  1. Should this bridge use Modbus on the reference aGate at all? It is a secondary channel for us — it provides the battery ratings, the VPP/force truth, and the dispatch path. The local API cannot replace the VPP truth. But if contention is hurting the Modbus Bridge, which is the primary controller, the cheapest fix available today is for us to poll it less or not at all. That is a priority call between two of your own systems, not a technical one.
  2. Idle-close timeout (proposed 10 minutes) and whether a gateway should hold a socket when nothing is reading it.
  3. Sequencing. §4.5 (mocks) and deleting the port_open × 3 probe are small, independent and reduce churn immediately. The session object is larger. They need not land together.
  4. Coordinating the library change with fwh-modbus (§5), which is where the largest reduction is, and which is not ours to make.

8. Separately: a latent breakage found while reading this code

Not part of this design; recorded because it will bite.

src/ imports franklinwh_local in 23 places and the new name in none. The library renamed itself in 0.4.0, and the shim says: "will be removed in 0.5.0". The bridge runs on a deprecation shim that is scheduled for deletion by a package we ourselves publish. It emits a DeprecationWarning on every import today and will be a hard ImportError at 0.5.0.