Battery dispatch: best practices

Back to the guide index · Control and write safety · Scheduler

A force command (Force Charge, Force Discharge or Force Standby) tells the battery exactly what to do, overriding the aGate's own operating mode until it is released. This page is about using it well: which mode to leave the aGate in, how to time a force, how to tell one is running, and how to end it.

The behaviour described here was read from the bridge's code on main (release 0.5.2) on 2026-10-17, unless it says otherwise. It was not exercised on a gateway for this page.

A force moves real power

A force charges from the grid or discharges into it at up to the battery's rated rate. Keep your system within the settings your installer configured and within your grid and VPP obligations.


The two rules

1. Leave the aGate in Self-Consumption or Emergency Backup

Leave the aGate in its default operating mode, Self-Consumption or Emergency Backup. Do not use the aGate's Time-of-Use (TOU) mode to time charging and discharging. Use the bridge's Scheduler instead: a force action in a window, with conditions that decide whether it starts and exit conditions and a target SoC that end it.

This is the owner's recommendation for this bridge. The reasons, from the code:

  • The Scheduler can gate a force on live data, such as SoC, a price or a Home Assistant entity, and can end it early. See Scheduler.
  • The aGate's TOU schedule cannot be written locally. GET /api/capabilities lists it as cloud-only ("1407 accepts the write and discards it"; see the guide index).
  • When a force ends, the battery goes back to whatever the aGate's mode does. In Self-Consumption that is predictable. Releasing a force does not change or restore the operating mode: battery_control writes only the SunSpec power setpoint, and nothing in it writes the mode.

2. "VPP Mode" in the FranklinWH app is expected

Observed by the owner, not documented by FranklinWH

On the owner's aGate in Australia (firmware V12R02B30D06), while a force from this bridge is active, the FranklinWH app shows "VPP Mode", and the app cannot override it. To end it, release it from the bridge (below).

This is one observation on one site and one firmware. It is not documented FranklinWH behaviour. The bridge's own code records a related measurement: during a force, the aGate's local run status (1707 ibgRunStatus) read 9 (comment in vpp_monitor.py, measured 2026-10-12).

So if you open the FranklinWH app during a scheduled charge and see VPP Mode, nothing is wrong. Do not try to fix it from the app. Release it from the bridge if you want it to end.


What a force needs

The Modbus client (this bridge) must be on. Force commands go from the Modbus client (this bridge) to the Modbus TCP Server (aGate :502). The client is off on a new install (from 0.5.9); turn it on under Control → Modbus client (this bridge). While it is off, the Battery Control card is disabled and shows why: "This bridge's Modbus client is off (Control → Modbus client); the aGate's Modbus TCP Server is not affected" (battery_control.available()).

Before each force the bridge checks that it can actually read the aGate over SunSpec (battery_control.capability()). It reports one of not configured, unreachable, no SunSpec or ready, and sends nothing unless the answer is ready.

The Modbus TCP Server (aGate :502) itself is an aGate setting. This bridge does not change it, and you should not need to.


Starting a force

From How
Control → Battery Control Pick Force Charge, Force Discharge or Force Standby from Command, with power (watts or percent of the rated rate), a duration and an optional target SoC. It asks for confirmation.
A schedule A force action. It starts when the window opens and the conditions hold. See Scheduler → The force action in detail.
The API POST /api/battery/command. Not confirm-gated; see Control.

Time the window with Daily or Weekly, not Recurring windows

For a scheduled force, use the Daily or Weekly trigger with a Fire at time and a Duration (min) that is the window. Avoid Recurring windows for a force for now.

The reason is an open defect, #160. The force's watchdog takes its time limit from the schedule's duration (_force_dispatch() in scheduler.py). The Recurring-windows form hides the Duration field, and a new schedule gets 90 minutes from the form's defaults. So a force in a three-hour recurring window releases after 90 minutes. With Daily or Weekly, the duration you type is the window, and the two agree.


How to tell a force is running

Where What you see Source
Top bar A FORCE chip, when the aGate reports a dispatch holding the battery. Its tooltip: "A force dispatch is holding the battery. The local/Modbus API can't confirm whether it's a VPP — that needs the Cloud API." A VPP chip instead when the cloud confirms a VPP. topbar.html; isForced in app.js (local run status 9, or a VPP flag)
Top bar A red, pulsing Release button, while this bridge holds a force. Hover it to see the command and the seconds left. topbar.html; polled from GET /api/battery/command every 15 s
Dashboard The Run status row, coloured, with a source chip. dashboard.html
Control → Battery Control The Active row shows the command. control.html
FranklinWH app "VPP Mode" (the owner's observation above). —

The FORCE chip and the Release button come from different places, so they do not always agree:

  • The FORCE chip comes from what the aGate reports on each poll. It shows for any force, whoever started it: this bridge, a Modbus Bridge, a utility VPP programme.
  • The Release button shows only while this bridge holds a force in its own memory (battery_control.current()). A force started by something else shows FORCE but no Release button.

The Control tab's Active row is read when the tab loads and after each command. It may not change by itself when the watchdog ends a force; reload to be sure. This is read from the code and was not tested.


Releasing a force

There are four ways, and they are not quite the same.

Where Label What it does
Top bar Release (red, pulsing) Asks "Release force dispatch", then sends Release (releaseBattery() in app.js → POST /api/battery/command). Shown only while this bridge holds a force, and only if the Release item is switched on in the top-bar preferences.
Control → Battery Control Command → Release (or Not Active) Sends Release at once, without asking, because releasing is the safe direction (battery_control.js).
Scheduler → a schedule card Stop Shown while the schedule is active. Asks "Stop this schedule?", then POST /api/schedules/{id}/stop. Acts only if this schedule started a dispatch that is still running; then it releases, and marks the run stopped. The schedule stays enabled and does not fire again in the same window.
API only — POST /api/schedules/{id}/pause releases and keeps the run, so POST /api/schedules/{id}/resume can re-enter it while the window is open. There is no Pause button in the UI.

There is no release item in any menu. The "use the Release button" wording in the bridge's own messages (vpp_monitor.py) means the top-bar button.

What a release does: battery_control.execute("Release") tells the Modbus TCP Server (aGate :502) to stop following the setpoint (reset_control_state() in the franklinwh-modbus library), clears the bridge's record of the force, and closes the saved dispatch record.

Things to know:

  • A release is global. It clears whatever force the aGate is following, including one a schedule card's Stop did not start. Stop checks that its own schedule started a dispatch, but the release it sends is the same one.
  • A release needs the Modbus client (this bridge) on. If you switch the client off while a force is running, the release is refused with the "Modbus client is off" reason, even though the code's comment says a release is always allowed. Switch the client back on, then release. (Read from battery_control.execute(); not tested.)
  • "Released" is reported without checking. The library reads the setpoint back, but the bridge ignores the result and always reports released. Check the FORCE chip on the next poll.

Planned: an always-visible Release

A Release button that is always visible, as in the Modbus Bridge, is planned in

165. It is not available yet.


How a force ends on its own

Event What happens Source
Its duration runs out The bridge's watchdog releases it. It checks every 5 seconds. A duration of 0 means no time limit. _watch() in battery_control.py
It reaches the target SoC Charging stops at SoC ≥ target, discharging at SoC ≤ target, from the gateway's last poll. _watch()
A schedule's window closes, or its exit conditions become true On the first tick after, the schedule releases the force as a safety net, even if the watchdog already did. tick() in scheduler.py
A newer force The new command replaces the old one. battery_control
The bridge shuts down cleanly It releases a force it holds. lifespan in app.py
The bridge restarts mid-force dispatch_interrupt_policy decides. The default, notify, sends you a notification and does not touch the battery. reconcile_interrupted() in battery_control.py; see Control

The aGate's own revert timer is not relied on. The code calls it "cosmetic" on this firmware, so the bridge's watchdog is what ends a force. If the bridge stops unexpectedly, a force can keep running until something releases it.

A schedule's Restore on exit option does nothing for a force. It applies only to mode changes (RESTORABLE in scheduler.py); a force auto-releases.


Known issues

Checked with gh issue view on 2026-10-17. All are open.

  • #160: a force in a Recurring-windows schedule stops after the hidden duration (default 90 minutes), not at the window's end. Use Daily or Weekly (above).
  • #162: the Scheduler has no Release action, no release policies, and no "hold instead of release". A force ends by its window, exit conditions, target SoC or duration.
  • #129: a schedule's reserve_soc action is always skipped, even with cloud credentials. Do not rely on a schedule to set the reserve.
  • #122: Home Assistant controls for the battery command (a select, staged parameters and status) are planned. Today Home Assistant can change the operating mode and smart circuits over MQTT, but cannot start or release a force.
  • #124: detecting VPP through the cloud and through the Modbus client (this bridge) is to be retired in favour of the aGate's local run status. Until then, the VPP chip's wording may change.