Modbus TCP vs Cloud API — Metrics Comparison

The same aGate can be read two ways:

  • Modbus TCP Server (aGate :502): read locally by a Modbus client such as this library, franklinwh-modbus.
  • Cloud API: franklinwh-cloud get_stats() over the FranklinWH cloud (getDeviceCompositeInfo, cmdType 203, result.runtimeData).

This page maps each metric across the two. franklinwh-cloud keeps its own copy of this table, linked to its own examples: Cloud API vs Modbus TCP. The two are maintained separately on purpose. Code examples for every Modbus field are in the API Cookbook.

Evidence. Modbus names are from this library's develop (controller.py). Cloud names, units and signs are from franklinwh-cloud's code (models.py, mixins/stats.py, const/modes.py), as reported by its maintainer session on 2026-10-19. A mapping marked INFERRED or ASSUMED has not been confirmed by a side-by-side capture. One site's data is a candidate, not a rule.

Units and signs

Modbus client Cloud API
Power W kW
Energy Wh, lifetime counters kWh, daily (resets at local midnight; ASSUMED site-local)
Grid sign + import (per these docs; unconfirmed on device) + import, − export
Battery sign − charging − charging, + discharging

The cloud grid sign was observed live on 2026-10-17: grid_use = −2.7 kW while exporting (solar 2.9 kW, home 0.2 kW).

Power and state

Metric Modbus (franklinwh-modbus) Modbus source Cloud (stats.current.…) Cloud raw key Notes
Solar power read_solar_status()['total_solar_w'], else ['ac_power_w'] (W) Extension total, else M502 OutPw solar_production (kW) p_sun
Generator power — — generator_production (kW) p_gen Not over Modbus
Battery power read_battery_status()['battery_power_w'] (W) M714 DCW, summed over ports battery_use (kW) p_fhp Modbus is the DC side; whether p_fhp is AC or DC is unknown, so the equivalence is INFERRED
Grid power read_grid_status()['grid_power_w'] (W) M701 W grid_use (kW) p_uti Same sign convention (see above)
Home load read_solar_status()['extension']['home_load_ext'] (W) Extension 16000 (~1 W), else 15506 (~100 W steps) home_load (kW) p_load 16000 is undocumented
Battery SoC read_battery_status()['soc'] (%) M713 SoC battery_soc (%) soc
Smart circuit / V2L power — — switch_1_load, switch_2_load, v2l_use (kW) cmdType 311 (not composite) Cloud only
Operating mode read_native_mode()['mode_name'] Extension 15507 work_mode / work_mode_desc result.currentWorkMode (1 TOU, 2 Self-Consumption, 3 Emergency Backup) Compare by name: the 15507 values in this library are under review (#75). The mode doesn't change during a remote dispatch (see the VPP row)
Active programme — — tou_mode / tou_mode_desc runtimeData.mode / .name A programme ID, not a run status
Run status No direct register; nearest is read_battery_status()['battery_state'] M714 DCW sign with a ±50 W deadband run_status / run_status_desc runtimeData.run_status INFERRED mapping
External control (VPP) read_control_status()['wset_enabled'] M704 WSetEna tou_mode == 9, effective_mode == "VPP mode" runtimeData.mode = 9 The cloud showed mode 9 within a minute of a Modbus force discharge (one site, 2026-10-14). See VPP Mode Reference
Grid connection read_grid_status()['connection_state'] (3 states) M701 ConnSt grid_connection_state (4 states) Derived; see below Closest raw cloud field: main_sw[0]

Grid connection: 3 Modbus states vs 4 cloud states

The cloud value is derived, not read from one field (cloud page):

Modbus ConnSt Cloud state How the cloud library decides
Connected CONNECTED main_sw[0] == 1 (grid relay closed)
Disconnected (INFERRED) OUTAGE offGridFlag set, or relay open and offgridState == 0
Disconnected (INFERRED) SIMULATED_OFF_GRID Relay open (or offgridreason set) and selectOffgrid → offgridState == 1
— NOT_GRID_TIED Site configured with no grid
Fault — No cloud counterpart identified

Modbus can't tell a user-simulated island from a real outage; the cloud needs an extra selectOffgrid call for that.

Energy

Metric Modbus (lifetime Wh) Modbus source Cloud (stats.totals.…, daily kWh) Cloud raw key Notes
Solar — — solar kwh_sun Not over Modbus
Generator — — generator kwh_gen Not over Modbus
Grid import read_grid_status()['grid_import_wh'] M701 TotWhAbs grid_import kwh_uti_in Modbus daily = difference of two readings
Grid export read_grid_status()['grid_export_wh'] M701 TotWhInj grid_export kwh_uti_out As above
Battery charge The TUI reads it; a library wrapper is queued (example) M714 DCWhAbs battery_charge kwh_fhp_chg
Battery discharge The TUI reads it; a library wrapper is queued (example) M714 DCWhInj battery_discharge kwh_fhp_di
Home — — home_use kwh_load Not over Modbus

For a cloud lifetime figure to compare with the Modbus counters, franklinwh-cloud uses get_power_details(type=5, …). Nobody has checked yet whether the cloud lifetime total and the Modbus counter agree.

Modbus-only data

See the API Cookbook for every key.

  • Battery: SoH, capacity (wh_rating, wh_available), DC current and temperature, and a per-battery breakdown.
  • Grid: voltage, frequency, VA, VAR, power factor and temperatures. The cloud has some of these via get_stats(include_electrical=True): cmdType 211, an extra call.
  • Reserves: extension 15508 (SC) and 15509 (TOU). 15509 holds the TOU reserve on V12R02B60D00, but only repeated 15508 on V10R01B04D00 (#63).
  • Read quality and control state: remote-control state, and the partial and error read-quality flags.

Choosing a source

Modbus TCP Server (aGate :502) Cloud API
Network Local LAN only Internet + FranklinWH cloud
Clients One Modbus client at a time Rate limits shared per account
Daily totals, solar/home energy, programme name No Yes
Electrical detail, per-battery data Yes Partial
Tells simulated off-grid from outage No Yes