SunSpec Model 704 Control Examples & Handover Handbook

This document provides a comprehensive handbook of Model 704 (Active Power & Power Factor Control) capabilities on the FranklinWH aGate system. It outlines the exact register layouts, write sequences, safety protocols, and real-world control patterns.


🔒 Writability Disclaimer & Hardware Support

[!IMPORTANT] FranklinWH Extensions & Write Permissions - Active Power Remote Control (WSet Group) is fully functional and writable on all standard FranklinWH aGate installations. - Active Power Curtailment (WMaxLimPct Group) and proprietary extensions are read-only by default. They will not function unless FranklinWH Support explicitly unlocks them or you are using provisioned SPAN/Lumin smart panels. - When writing registers, writes to read-only or locked registers will return a Modbus Success (ACK) packet but will be silently ignored/discarded internally by the gateway's firmware. The only way to verify successful writes is through readback verification.


⏱️ The SunSpec 6-Phase Sequencing Protocol

To ensure reliable control state transitions and prevent hardware race conditions or Modbus buffer overflows, all control operations must be executed in a structured, phased sequence:

Phase 0: PRE-FLIGHT READS       ← Captured baseline telemetry; no writes yet.
Phase 1: CONFIGURE MODE         ← Write configuration and operating mode registers.
Phase 2: SAFETY / REVERSION     ← Write reversion rates, timeouts, and reversion flags.
Phase 3: WRITE SETPOINT         ← Write the target active power / limit setpoint.
Phase 4: ENABLE (Commit)        ← Write the enable register last — this is the "go" trigger.
Phase 5: VERIFY READBACK        ← Read back the registers to confirm they are accepted.

Hardware Settling and Timing Requirements

  • Command Settling Delay: Allow at least 200ms between configuring parameters and writing the enable register.
  • Modbus Inter-command Delay: Allow at least 100ms between individual writes to prevent Modbus TCP/serial buffer overflows.
  • Ramp Processing Delay: Allow at least 500ms after enabling a mode before reading back telemetry or initiating verification loops.

🔄 Safety Flow Integration (Standby & Clean Release)

To guarantee predictable physical transitions and prevent the battery from becoming locked in remote VPP mode permanently, all active power control sequences should utilize the following safety flow:

  1. Initial Standby Initialization: Before dispatching charge/discharge power, initialize remote VPP mode with 0W power flow. This establishes control safely without sudden power spikes.
    model704.WSetMod = 0    # Absolute watts mode
    model704.WSetPct = 0    # 0% / 0W setpoint
    model704.WSetEna = 1    # Enable remote control last
    
  2. Core Operation Execution: Transition the setpoint to the desired dispatch value.
  3. Explicit Cleanup & Handover: Upon sequence completion or exit, always release control explicitly to return the aGate to its native automatic operating mode (e.g. Self-Consumption, Backup).
    model704.WSetEna = 0    # Disable remote control
    model704.WSetPct = 0    # Reset setpoint to 0
    

📖 Model 704 Control Examples

Group 3: Limit Maximum Export Power

Use these registers to restrict the maximum power exported from the battery/inverter to the grid.

[!WARNING] These curtailment registers are physically read-only unless unlocked via SPAN smart panels or support configuration.

Use Case A: Temporary 5kW Export Limit (50% of a 10kW Inverter)

Utility requires a temporary 5kW export limit, reverting to 100% rated capacity after 1 hour (3600 seconds).

# Sequential Write Sequence:
model704.WMaxLimPct = 50          # 1. Setpoint: 50% of rated capacity
model704.WMaxLimPctRvrt = 100     # 2. Reversion value: Revert to 100% on timeout
model704.WMaxLimPctRvrtTms = 3600 # 3. Timeout: 3600 seconds (1 hour)
model704.WMaxLimPctEnaRvrt = 1    # 4. Enable reversion safety
model704.WMaxLimPctEna = 1        # 5. Enable the limit (write last)

Use Case B: Permanent 3kW Export Limit (30% of a 10kW Inverter)

A permanent export limit with reversion disabled.

# Sequential Write Sequence:
model704.WMaxLimPct = 30          # 1. Setpoint: 30% of capacity (3kW)
model704.WMaxLimPctEnaRvrt = 0    # 2. Disable reversion (make limit permanent)
model704.WMaxLimPctEna = 1        # 3. Enable the limit (write last)

Disable Export Limiting

Exiting and turning off all export limits:

model704.WMaxLimPctEna = 0        # Turn off export limit control

Group 4: Set Exact Power Output

Use these registers to force the battery to charge or discharge at an exact rate under remote VPP control.

  • Positive (+) values: Discharging (exporting power to home/grid).
  • Negative (-) values: Charging (importing power from solar/grid).

Use Case A: Force Battery Discharge at 1000W (Absolute Mode)

Force battery discharge at exactly 1000W, reverting to 0W idle after 30 minutes (1800 seconds).

# Sequential Write Sequence:
model704.WSetMod = 0              # 1. Configure mode: 0 = absolute watts mode
model704.WSet = 1000              # 2. Setpoint: 1000W discharge (positive)
model704.WSetRvrt = 0             # 3. Reversion value: Revert to 0W on timeout
model704.WSetRvrtTms = 1800       # 4. Timeout: 1800 seconds (30 minutes)
model704.WSetEnaRvrt = 1          # 5. Enable reversion safety
model704.WSetEna = 1              # 6. Enable remote control (write last)

Use Case B: Force Battery Charge at 2000W (Absolute Mode)

Force battery charge at exactly 2000W from the grid, reverting to 0W idle after 2 hours (7200 seconds).

# Sequential Write Sequence:
model704.WSetMod = 0              # 1. Configure mode: absolute watts mode
model704.WSet = -2000             # 2. Setpoint: -2000W charge (negative)
model704.WSetRvrt = 0             # 3. Reversion value: Revert to 0W
model704.WSetRvrtTms = 7200       # 4. Timeout: 7200 seconds (2 hours)
model704.WSetEnaRvrt = 1          # 5. Enable reversion safety
model704.WSetEna = 1              # 6. Enable remote control (write last)

Use Case C: Discharge at 50% Rate (Percentage Mode)

Discharge at 50% of rated max capacity using percentage mode, reverting to 0% after 1 hour (3600 seconds).

# Sequential Write Sequence:
model704.WSetMod = 1              # 1. Configure mode: 1 = percentage mode
model704.WSetPct = 50             # 2. Setpoint: 50% of rated capacity
model704.WSetPctRvrt = 0          # 3. Reversion value: Revert to 0%
model704.WSetRvrtTms = 3600       # 4. Timeout: 3600 seconds (1 hour)
model704.WSetEnaRvrt = 1          # 5. Enable reversion safety
model704.WSetEna = 1              # 6. Enable remote control (write last)

Disable Active Power Dispatch (Release Control)

Explicitly stop VPP operations and restore native automatic operation:

model704.WSetEna = 0              # Disable remote control

Group 1 & 2: Power Factor Control

Use these registers to enable reactive power / power factor offset operations required by local utilities.

  • Scale Factor: Power Factor (PF) values use a standard scale factor of -3, meaning a PF of 0.95 is represented as raw value 950, and a PF of 0.90 is represented as raw value 900.

Use Case A: 0.95 Power Factor During Export

Utility requires 0.95 power factor when exporting power to the grid (injection).

model704.PFWInjEna = 1            # Enable PF control for injection (export)

Use Case B: 0.90 Power Factor During Import

Maintain 0.90 power factor when absorbing/charging from the grid.

model704.PFWAbsEna = 1            # Enable PF control for absorbing (import)

🛠️ Real-World Scenario Sequences

Scenario A: Time-of-Use (TOU) Arbitrage

Charge the battery from the grid during off-peak hours (midnight to 6am at 3kW), and discharge to home loads during peak hours (4pm to 9pm at 5kW).

1. Off-Peak Charge Step (Midnight)

model704.WSetMod = 0
model704.WSet = -3000             # -3000W charge from grid
model704.WSetRvrtTms = 21600      # 21600 seconds (6 hours)
model704.WSetEnaRvrt = 1          # Revert to 0W after off-peak ends
model704.WSetEna = 1              # Enable

2. Peak Discharge Step (4:00 PM)

model704.WSetMod = 0
model704.WSet = 5000              # 5000W discharge to home/grid
model704.WSetRvrtTms = 18000      # 18000 seconds (5 hours)
model704.WSetEnaRvrt = 1          # Revert to 0W after peak ends
model704.WSetEna = 1              # Enable

Scenario B: Zero Export

Completely prevent any power from exporting to the grid (essential in zero-export compliance zones).

model704.WMaxLimPct = 0           # 0% export power allowed
model704.WMaxLimPctEnaRvrt = 0    # Disable reversion (make limit permanent)
model704.WMaxLimPctEna = 1        # Enable the limit

Scenario C: Emergency Backup Hold

Stop all battery discharge to preserve capacity for a forecasted grid outage or severe weather emergency.

model704.WSetMod = 0
model704.WSet = 0                 # Force 0W discharge flow
model704.WSetRvrtTms = 86400      # Hold for 24 hours (86400 seconds)
model704.WSetEnaRvrt = 1          # Revert to standard mode after 24h
model704.WSetEna = 1              # Enable Remote Hold

🗃️ Model 704 Register Address Reference

Register Point Modbus PDU Addr SunSpec Type Scale Factor Range / Values Description
WMaxLimPctEna 310 enum16 0 = Disabled, 1 = Enabled Enable active power curtailment limit.
WMaxLimPct 311 uint16 -2 / -1 0 to 100 (%) Target active power curtailment limit rate.
WMaxLimPctEnaRvrt 313 enum16 0 = Disabled, 1 = Enabled Enable reversion for curtailment.
WMaxLimPctRvrt 312 uint16 -2 / -1 0 to 100 (%) Reversion value for curtailment.
WMaxLimPctRvrtTms 314 (32-bit) uint32 0 to 86400 (s) Reversion timeout duration in seconds.
WSetEna 318 enum16 0 = Disabled, 1 = Enabled Enable remote active power dispatch (VPP).
WSetMod 319 enum16 0 = Watts, 1 = Percent Active power mode.
WSet 320 (32-bit) int32 0 -10000 to 10000 (W) Target active power setpoint (Watts mode).
WSetPct 324 int16 -2 / -1 -100 to 100 (%) Target active power setpoint (Percent mode).
WSetEnaRvrt 328 enum16 0 = Disabled, 1 = Enabled Enable reversion for dispatch.
WSetRvrt 325 (32-bit) int32 0 -10000 to 10000 (W) Reversion value (Watts mode).
WSetPctRvrt 326 int16 -2 / -1 -100 to 100 (%) Reversion value (Percent mode).
WSetRvrtTms 327 uint32 0 to 86400 (s) Reversion timeout duration in seconds.
WSetRvrtRem 329 uint32 0 to 86400 (s) Remaining time before reversion.
PFWInjEna 330 enum16 0 = Disabled, 1 = Enabled Enable PF control during export (injection).
PFWAbsEna 331 enum16 0 = Disabled, 1 = Enabled Enable PF control during import (absorption).

🖥️ Executing Sequences via the CLI

All sequences detailed in this guide are pre-configured as JSON sequence files located under the examples/sequencer/ directory.

To run any sequence, invoke the franklinwh_cli.py utility with the --sequence-file option:

# Execute a temporary export limit sequence
python3 tools/franklinwh_cli.py -i <YOUR_AGATE_IP> --sequence-file examples/sequencer/limit_export_temporary.json

# Execute an active discharge dispatch sequence
python3 tools/franklinwh_cli.py -i <YOUR_AGATE_IP> --sequence-file examples/sequencer/discharge_watts_temporary.json

To run dry-run validation on a sequence file (which reads initial states and simulates execution without executing writes):

python3 tools/franklinwh_cli.py -i <YOUR_AGATE_IP> --sequence-file examples/sequencer/scenario_tou_charge.json --dry-run