Home Assistant: Monitoring with Modbus YAML¶
A minimal, monitor-only way to see your aGate's core metrics in Home Assistant, using HA's built-in Modbus integration and a block of YAML. No add-on, no Python, no FranklinWH library.
Read before you start
- Monitor only. This guide reads registers and never writes. Don't add
modbus.write_registerautomations against the aGate: there's no clamp, no release and no verification here. For battery control, use a FranklinWH integration built on this library. - One Modbus client per aGate: stop or uninstall the others first. Home Assistant's Modbus integration keeps its own TCP connection open to the aGate. Before adding this YAML, stop or uninstall any FranklinWH bridge add-on or integration, and anything else that talks to port 502: this library's CLI or TUI, or a tool that probes :502. Two clients cause dropped connections and "unavailable" sensors.
- Scale factors are fixed in the YAML. SunSpec keeps scale factors in separate registers; the values below were read on firmware V10R01B04D00 on 2026-05-14. Check yours (step 1), and again after a firmware update.
- Tested against the gateway emulator, not yet against a real aGate. On 2026-10-20 the guide's first 12 sensors and the dashboard card worked in Home Assistant 2026.10.1 (HAOS VM) against the FranklinWH Gateway Emulator 0.1.0. The emulator proves the YAML works; its numbers aren't device values. Compare HA's values with the CLI (step 4) before relying on them.
What you get¶
| Sensor | Register (PDU) | Source |
|---|---|---|
| Battery SoC (%) | 1037 | SunSpec M713 SoC |
| Battery power (W; + discharging, − charging) | 1048 | SunSpec M714 DCW |
| Grid power (W; + import, − export) | 80 | SunSpec M701 W |
| Solar power (W) | 15502 | FranklinWH extension |
| Home load (W) | 16000 | FranklinWH extension (undocumented, ~1 W resolution) |
| Self-consumption reserve (%) | 15508 | FranklinWH extension |
| Operating mode (raw number) | 15507 | FranklinWH extension |
| Grid import / export energy (Wh, lifetime) | 93 / 89 | SunSpec M701 TotWhAbs / TotWhInj |
| Solar energy (Wh, lifetime) | 15510–15511 | FranklinWH extension, uint32, high word first |
| Grid connection state (raw) | 75 | SunSpec M701 ConnSt: 0 = DISCONNECTED, 1 = CONNECTED |
| Inverter state (raw) | 74 | SunSpec M701 InvSt: 0 OFF … 3 RUNNING … 6 FAULT, 7 STANDBY |
| DER mode bits (raw) | 78–79 | SunSpec M701 DERMode: bit 0 GRID_FOLLOWING, bit 1 GRID_FORMING (off-grid), bit 2 PV_CLIPPED |
| Alarm bits (raw) | 76–77 | SunSpec M701 Alrm: bit 4 GRID_DISCONNECT and others |
| Grid status (derived) | — | Template: On grid / Backup (off-grid) / Grid disconnected |
| Grid connected (derived) | — | Template binary sensor |
| Battery charged / discharged energy (Wh, lifetime) | 1053 / 1049 | SunSpec M714 DCWhAbs / DCWhInj |
Addresses are Modbus PDU addresses. Home Assistant also counts from 0, so they go into address: exactly as listed. Don't add 40000 or 40001. Older firmware (V10R01B04D00) answers those with exception 2, and the extension registers have no 40000 mirror that anyone has verified. See Register Addressing.
1. Before you start¶
- Modbus TCP enabled. Your installer has to turn Modbus TCP on for the aGate; the FranklinWH app can't.
- The aGate's IP address, reachable from Home Assistant. Give it a fixed address (DHCP reservation).
- Your scale factors (recommended). With this library installed on any computer, and with no other Modbus client running, run:
Check these against the values the YAML assumes:
| Point | PDU | Value the YAML assumes |
|---|---|---|
M713 Pct_SF |
1041 | −1 (SoC raw 500 = 50.0 %) |
M714 DCW_SF |
1059 | 0 |
M714 DCWH_SF |
1060 | 0 |
M701 W_SF |
186 | 0 |
M701 TotWh_SF |
190 | 0 |
Also check the model IDs sit where the YAML expects: M701 at 70, M713 at 1033, M714 at 1042. If any differ, your firmware lays the map out differently; don't use this YAML unchanged.
2. The YAML¶
Add this to configuration.yaml, or to a file you include from it. Replace 192.0.2.10 with your aGate's IP.

modbus:
- name: franklinwh_agate
type: tcp
host: 192.0.2.10 # your aGate
port: 502
timeout: 5
sensors:
# --- SunSpec models ---------------------------------------------
- name: aGate Battery SoC
unique_id: agate_battery_soc
device_address: 2
address: 1037 # M713 SoC
data_type: uint16
scale: 0.1 # Pct_SF = -1
precision: 1
nan_value: "0xFFFF"
unit_of_measurement: "%"
device_class: battery
state_class: measurement
scan_interval: 30
- name: aGate Battery Power
unique_id: agate_battery_power
device_address: 2
address: 1048 # M714 DCW: + discharging, - charging
data_type: int16
nan_value: "0x8000"
unit_of_measurement: W
device_class: power
state_class: measurement
scan_interval: 10
- name: aGate Grid Power
unique_id: agate_grid_power
device_address: 2
address: 80 # M701 W: + import, - export
data_type: int16
nan_value: "0x8000"
unit_of_measurement: W
device_class: power
state_class: measurement
scan_interval: 10
- name: aGate Grid Import Energy
unique_id: agate_grid_import_energy
device_address: 2
address: 93 # M701 TotWhAbs
data_type: uint64
nan_value: "0xFFFFFFFFFFFFFFFF"
unit_of_measurement: Wh
device_class: energy
state_class: total_increasing
scan_interval: 60
- name: aGate Grid Export Energy
unique_id: agate_grid_export_energy
device_address: 2
address: 89 # M701 TotWhInj
data_type: uint64
nan_value: "0xFFFFFFFFFFFFFFFF"
unit_of_measurement: Wh
device_class: energy
state_class: total_increasing
scan_interval: 60
- name: aGate Battery Charged Energy
unique_id: agate_battery_charged_energy
device_address: 2
address: 1053 # M714 DCWhAbs (DC side)
data_type: uint64
nan_value: "0xFFFFFFFFFFFFFFFF"
unit_of_measurement: Wh
device_class: energy
state_class: total_increasing
scan_interval: 60
- name: aGate Battery Discharged Energy
unique_id: agate_battery_discharged_energy
device_address: 2
address: 1049 # M714 DCWhInj (DC side)
data_type: uint64
nan_value: "0xFFFFFFFFFFFFFFFF"
unit_of_measurement: Wh
device_class: energy
state_class: total_increasing
scan_interval: 60
# --- FranklinWH extension registers ------------------------------
- name: aGate Solar Energy
unique_id: agate_solar_energy
device_address: 2
address: 15510 # PVOutputWh: uint32, high word first
data_type: uint32
unit_of_measurement: Wh
device_class: energy
state_class: total_increasing
scan_interval: 60
- name: aGate Solar Power
unique_id: agate_solar_power
device_address: 2
address: 15502 # total PV, incl. aPbox/aHub remote PV
data_type: uint16
unit_of_measurement: W
device_class: power
state_class: measurement
scan_interval: 10
- name: aGate Home Load
unique_id: agate_home_load
device_address: 2
address: 16000 # undocumented, ~1 W; 15506 = ~100 W steps
data_type: uint16
unit_of_measurement: W
device_class: power
state_class: measurement
scan_interval: 10
- name: aGate Self-Consumption Reserve
unique_id: agate_self_consumption_reserve
device_address: 2
address: 15508
data_type: uint16
unit_of_measurement: "%"
scan_interval: 300
- name: aGate Operating Mode Raw
unique_id: agate_operating_mode_raw
device_address: 2
address: 15507 # value mapping under review, see note
data_type: uint16
scan_interval: 300
# --- Grid connection status (SunSpec M701) ------------------------
- name: aGate Grid Connection Raw
unique_id: agate_grid_connection_raw
device_address: 2
address: 75 # M701 ConnSt: 0 DISCONNECTED, 1 CONNECTED
data_type: uint16
nan_value: "0xFFFF"
scan_interval: 10
- name: aGate Inverter State Raw
unique_id: agate_inverter_state_raw
device_address: 2
address: 74 # M701 InvSt
data_type: uint16
nan_value: "0xFFFF"
scan_interval: 30
- name: aGate DER Mode Raw
unique_id: agate_der_mode_raw
device_address: 2
address: 78 # M701 DERMode bitfield32: bit 1 = GRID_FORMING
data_type: uint32
nan_value: "0xFFFFFFFF"
scan_interval: 10
- name: aGate Alarm Bits Raw
unique_id: agate_alarm_bits_raw
device_address: 2
address: 76 # M701 Alrm bitfield32: bit 4 = GRID_DISCONNECT
data_type: uint32
nan_value: "0xFFFFFFFF"
scan_interval: 30
# Readable grid status, derived from the raw sensors above
template:
- sensor:
- name: aGate Grid Status
unique_id: agate_grid_status
state: >
{% set conn = states('sensor.agate_grid_connection_raw') | int(-1) %}
{% set mode = states('sensor.agate_der_mode_raw') | int(0) %}
{% if mode | bitwise_and(2) %}Backup (off-grid)
{% elif conn == 1 %}On grid
{% elif conn == 0 %}Grid disconnected
{% else %}Unknown{% endif %}
- binary_sensor:
- name: aGate Grid Connected
unique_id: agate_grid_connected
device_class: connectivity
state: >
{{ states('sensor.agate_grid_connection_raw') | int(-1) == 1
and not (states('sensor.agate_der_mode_raw') | int(0) | bitwise_and(2)) }}
Notes:
- Unit ID. device_address: 2 is the FranklinWH default. The aGate answers on any unit ID (QUIRKS).
- Scan intervals. About 10 s for power and longer for energy and settings keeps traffic modest: 16 Modbus sensors means 16 requests per cycle. HA's default is 15 s. Polling faster than about 5 s hasn't been tested against an aGate.
- Reconnects. HA's Modbus client reconnects by itself. How it behaves when the aGate drops the session hasn't been measured.
- TOU reserve. On firmware V12R02B60D00 and later, 15509 holds the TOU reserve. Add it like the self-consumption reserve (address 15509, uint16, %). On V10R01B04D00 it just repeats 15508, so don't add it there (#63). Check your firmware with the aGate Firmware sensor from §2b.
- Operating mode is shown as a raw number. Which number means which mode is still being confirmed (#75). The library and a 2026-05 device scan say 1 = Emergency Backup, 2 = Self-Consumption, 3 = TOU, but treat that as provisional.
- Grid status: what it can and can't tell you. "Backup (off-grid)" comes from M701 DERMode bit 1 (GRID_FORMING: the aPower is making its own AC). "Grid disconnected" comes from ConnSt = 0. Neither has been observed during a real outage on an aGate yet; all readings so far were on-grid. Modbus also can't tell a real utility outage from a deliberate off-grid switch, which the FranklinWH cloud API can (Modbus vs Cloud). The "Emergency Backup" operating mode (15507) is a setting that keeps the battery in reserve; it doesn't mean the grid is down.
- Battery power is the DC side (M714). With more than one aPower, PDU 1048 is the model's top-level total. That hasn't been verified on a multi-battery site.
2b. Optional: everything the TUI shows¶
The core YAML above covers the main numbers. This section adds the rest of what the TUI monitor displays, plus description templates that turn codes into words: inverter state, battery state (charging, discharging), grid mode (grid forming, grid following), operating mode and active alarms.
Paste the sensors entries under the same sensors: list as the core YAML, and the template entries under the existing template: list. Home Assistant allows only one modbus: hub entry per aGate and one top-level template: key.
Where these addresses come from
Most come from the device scan (2026-05-14, V10R01B04D00). Two of them, battery voltage (1073) and battery temperature (1083), are in model 714's per-port block, which the scan doesn't print. They're computed from the SunSpec model 714 definition (model at 1042; port 1 starts at 1062). The emulator test confirmed the addresses against the emulator's own SunSpec map. With more than one aPower, each port's block follows the previous one, 25 registers on.
Battery voltage and temperature may read 0
On firmware V12R02B60D00 they read 0. A read-only scan of the reference aGate on 2026-10-20 found model 714's whole port block (1062–1086) at 0. The gateway emulator's V10R01B04D00 profile has it zeroed too. Battery Current then shows as unavailable. Leave the three out unless your firmware reports real values (check with step 4).
Extra Modbus sensors¶
# --- Battery (TUI: DC Power panel) --------------------------------
- name: aGate Battery SoH
unique_id: agate_battery_soh
device_address: 2
address: 1038 # M713 SoH, Pct_SF = -1
data_type: uint16
scale: 0.1
precision: 1
nan_value: "0xFFFF"
unit_of_measurement: "%"
state_class: measurement
scan_interval: 3600
- name: aGate Battery Energy Available
unique_id: agate_battery_energy_available
device_address: 2
address: 1036 # M713 WHAvail, WH_SF = 0
data_type: uint16
nan_value: "0xFFFF"
unit_of_measurement: Wh
device_class: energy_storage
state_class: measurement
scan_interval: 60
- name: aGate Battery Energy Rating
unique_id: agate_battery_energy_rating
device_address: 2
address: 1035 # M713 WHRtg, WH_SF = 0
data_type: uint16
nan_value: "0xFFFF"
unit_of_measurement: Wh
device_class: energy_storage
scan_interval: 3600
- name: aGate Battery Voltage
unique_id: agate_battery_voltage
device_address: 2
address: 1073 # M714 port 1 DCV, DCV_SF = 0 (computed address)
data_type: uint16
nan_value: "0xFFFF"
unit_of_measurement: V
device_class: voltage
state_class: measurement
scan_interval: 30
- name: aGate Battery Temperature
unique_id: agate_battery_temperature
device_address: 2
address: 1083 # M714 port 1 Tmp, Tmp_SF = 0 (computed address)
data_type: int16
nan_value: "0x8000"
unit_of_measurement: "°C"
device_class: temperature
state_class: measurement
scan_interval: 60
# --- AC side (TUI: AC Power panel) --------------------------------
- name: aGate AC Voltage
unique_id: agate_ac_voltage
device_address: 2
address: 86 # M701 LNV, V_SF = -1
data_type: uint16
scale: 0.1
precision: 1
nan_value: "0xFFFF"
unit_of_measurement: V
device_class: voltage
state_class: measurement
scan_interval: 30
- name: aGate AC Current
unique_id: agate_ac_current
device_address: 2
address: 84 # M701 A, A_SF = -1
data_type: int16
scale: 0.1
precision: 1
nan_value: "0x8000"
unit_of_measurement: A
device_class: current
state_class: measurement
scan_interval: 30
- name: aGate AC Frequency
unique_id: agate_ac_frequency
device_address: 2
address: 87 # M701 Hz (uint32), Hz_SF = -3
data_type: uint32
scale: 0.001
precision: 2
nan_value: "0xFFFFFFFF"
unit_of_measurement: Hz
device_class: frequency
state_class: measurement
scan_interval: 30
- name: aGate Power Factor
unique_id: agate_power_factor
device_address: 2
address: 83 # M701 PF, PF_SF = -3
data_type: int16
scale: 0.001
precision: 3
nan_value: "0x8000"
state_class: measurement
scan_interval: 30
- name: aGate Apparent Power
unique_id: agate_apparent_power
device_address: 2
address: 81 # M701 VA, VA_SF = 0
data_type: int16
nan_value: "0x8000"
unit_of_measurement: VA
device_class: apparent_power
state_class: measurement
scan_interval: 30
- name: aGate Reactive Power
unique_id: agate_reactive_power
device_address: 2
address: 82 # M701 Var, Var_SF = 0
data_type: int16
nan_value: "0x8000"
unit_of_measurement: var
device_class: reactive_power
state_class: measurement
scan_interval: 30
- name: aGate Ambient Temperature
unique_id: agate_ambient_temperature
device_address: 2
address: 105 # M701 TmpAmb, Tmp_SF = -1
data_type: int16
scale: 0.1
precision: 1
nan_value: "0x8000"
unit_of_measurement: "°C"
device_class: temperature
state_class: measurement
scan_interval: 60
- name: aGate Cabinet Temperature
unique_id: agate_cabinet_temperature
device_address: 2
address: 106 # M701 TmpCab, Tmp_SF = -1
data_type: int16
scale: 0.1
precision: 1
nan_value: "0x8000"
unit_of_measurement: "°C"
device_class: temperature
state_class: measurement
scan_interval: 60
# --- Solar inputs (TUI: Solar AC Inputs panel) --------------------
- name: aGate Solar Proximal
unique_id: agate_solar_proximal
device_address: 2
address: 15503 # PV on the aGate's own inputs
data_type: uint16
unit_of_measurement: W
device_class: power
state_class: measurement
scan_interval: 10
- name: aGate Solar Remote 1
unique_id: agate_solar_remote_1
device_address: 2
address: 15504 # aPbox / aHub remote PV 1
data_type: uint16
unit_of_measurement: W
device_class: power
state_class: measurement
scan_interval: 10
- name: aGate Solar Remote 2
unique_id: agate_solar_remote_2
device_address: 2
address: 15505 # aPbox / aHub remote PV 2
data_type: uint16
unit_of_measurement: W
device_class: power
state_class: measurement
scan_interval: 10
# --- Device info (TUI: Device Info panel) -------------------------
- name: aGate Model
unique_id: agate_model
device_address: 2
address: 20 # M1 Md, 16 registers
data_type: string
count: 16
scan_interval: 86400
- name: aGate Firmware
unique_id: agate_firmware
device_address: 2
address: 44 # M1 Vr, 8 registers
data_type: string
count: 8
scan_interval: 86400
The serial number (M1 SN, PDU 52, 16 registers) can be added the same way. Keep it out of screenshots and shared configs.
Description templates¶
- sensor:
- name: aGate Inverter State
unique_id: agate_inverter_state
state: >
{% set names = {0: 'Off', 1: 'Sleeping', 2: 'Starting', 3: 'Running',
4: 'Throttled', 5: 'Shutting down', 6: 'Fault', 7: 'Standby'} %}
{% set v = states('sensor.agate_inverter_state_raw') | int(-1) %}
{{ names.get(v, 'Unknown (' ~ v ~ ')') }}
- name: aGate Battery State
unique_id: agate_battery_state
state: >
{% set w = states('sensor.agate_battery_power') | float(0) %}
{% if w < -50 %}Charging{% elif w > 50 %}Discharging{% else %}Idle{% endif %}
- name: aGate Grid Mode
unique_id: agate_grid_mode
state: >
{% set m = states('sensor.agate_der_mode_raw') | int(0) %}
{% if m | bitwise_and(2) %}Grid Forming{% elif m | bitwise_and(1) %}Grid Following{% else %}Unknown{% endif %}
- name: aGate Operating Mode
unique_id: agate_operating_mode
state: >
{% set names = {1: 'Emergency Backup', 2: 'Self-Consumption', 3: 'TOU'} %}
{% set v = states('sensor.agate_operating_mode_raw') | int(-1) %}
{{ names.get(v, 'Unknown (' ~ v ~ ')') }}
- name: aGate Battery Current
unique_id: agate_battery_current
unit_of_measurement: A
device_class: current
state_class: measurement
availability: "{{ states('sensor.agate_battery_voltage') | float(0) > 0 }}"
state: >
{% set w = states('sensor.agate_battery_power') | float(0) %}
{% set v = states('sensor.agate_battery_voltage') | float(0) %}
{{ (w / v) | round(1) if v > 0 else 0 }}
- name: aGate Active Alarms
unique_id: agate_active_alarms
state: >
{% set names = ['GROUND_FAULT', 'DC_OVER_VOLT', 'AC_DISCONNECT', 'DC_DISCONNECT',
'GRID_DISCONNECT', 'CABINET_OPEN', 'MANUAL_SHUTDOWN', 'OVER_TEMP',
'OVER_FREQUENCY', 'UNDER_FREQUENCY', 'AC_OVER_VOLT', 'AC_UNDER_VOLT',
'BLOWN_STRING_FUSE', 'UNDER_TEMP', 'MEMORY_LOSS', 'HW_TEST_FAILURE',
'MANUFACTURER_ALRM'] %}
{% set a = states('sensor.agate_alarm_bits_raw') | int(0) %}
{% set ns = namespace(on=[]) %}
{% for i in range(names | length) %}
{% if a | bitwise_and(2 ** i) %}{% set ns.on = ns.on + [names[i]] %}{% endif %}
{% endfor %}
{{ ns.on | join(', ') if ns.on else 'No alarms' }}
- binary_sensor:
- name: aGate PV Clipped
unique_id: agate_pv_clipped
state: "{{ states('sensor.agate_der_mode_raw') | int(0) | bitwise_and(4) > 0 }}"
| Template | Built from | Meaning |
|---|---|---|
| Inverter State | M701 InvSt |
SunSpec names: Off, Sleeping, Starting, Running, Throttled, Shutting down, Fault, Standby |
| Battery State | Battery power | Charging below −50 W, Discharging above +50 W, else Idle: the same 50 W deadband as the library. M713 Sta isn't populated on the aGate, so it can't be used |
| Grid Mode | M701 DERMode |
Grid Forming (bit 1: the aPower makes its own AC, i.e. off-grid) or Grid Following (bit 0: on grid) |
| Grid Status / Grid Connected | ConnSt + DERMode |
On grid, Backup (off-grid), Grid disconnected (core YAML) |
| PV Clipped | M701 DERMode bit 2 |
Solar is being curtailed, typically off-grid; not yet observed |
| Operating Mode | Extension 15507 | 1 Emergency Backup, 2 Self-Consumption, 3 TOU, each read with the app in that mode (#75) |
| Battery Current | Power ÷ voltage | M714 DCA isn't populated on the aGate, so current is worked out as the library does. Unavailable while the voltage reads 0 |
| Active Alarms | M701 Alrm |
Names of the set bits, from SunSpec model 701, or "No alarms". A template result of None would show as unknown in Home Assistant |
Tested 2026-10-20 against the gateway emulator: all 34 Modbus sensors and 9 templates loaded with no errors. Switching the emulator off-grid turned Grid Status to "Backup (off-grid)", Grid Connected to "Disconnected" and Grid Mode to "Grid Forming".
| On grid | Off grid (emulator) |
|---|---|
![]() |
![]() |
TUI panel → Home Assistant entities¶
| TUI panel | Entities |
|---|---|
| Power Flow | Solar Power, Battery Power, Grid Power, Home Load, Battery State |
| Battery SoC | Battery SoC, Self-Consumption Reserve |
| DC Power (Battery) | Battery Power, Battery Current, Battery Voltage, Battery Temperature, Battery SoH, Battery Energy Available / Rating |
| AC Power | AC Voltage, AC Current, AC Frequency, Power Factor, Apparent Power, Reactive Power, Grid Mode |
| Solar AC Inputs | Solar Power, Solar Proximal, Solar Remote 1 and 2 |
| Lifetime Energy | Grid Import / Export, Battery Charged / Discharged, Solar Energy |
| Device Info | Model, Firmware, Operating Mode, Inverter State |
| Alarms & Status | Active Alarms, Grid Status, Grid Connected, PV Clipped |
More sensors mean more Modbus requests per cycle. The long scan_interval values on slow-changing points (SoH, ratings, device info) keep the load down.
3. Restart and check¶
Check the configuration first (Developer tools → YAML → Check configuration), then restart Home Assistant (Settings → System → Restart).

Then open Settings → Devices & services → Entities and search for aGate. All 16 Modbus sensors and the 2 template sensors should have values within a minute.

| Symptom | Likely cause |
|---|---|
| All sensors unavailable | Another Modbus client is connected, Modbus TCP isn't enabled, or the IP is wrong |
| One sensor unavailable, log shows exception 2 | Wrong address (e.g. offset by 40000 on older firmware), or the register doesn't exist on your firmware |
| SoC shows 500 instead of 50 | scale: 0.1 missing |
| Values look plausible but differ from the app | Scale factor or address differs on your firmware: redo step 1 |
A clean run shows no Modbus errors in Settings → System → Logs (search "modbus"):

Sensor history (History, add the aGate sensors):

4. Verify against the CLI¶
Stop Home Assistant's Modbus hub first (one client at a time): comment out the YAML and restart, or stop HA. Then run:
Compare SoC, battery power, grid power, solar and home load with what HA showed a moment before. They should agree within normal fluctuation. Then put the YAML back.
5. Energy dashboard¶
Settings → Dashboards → Energy. In Home Assistant 2026.10, grid import and export are one grid connection ("Add grid connection"):
| Energy dashboard field | Sensor |
|---|---|
| Grid connection: energy imported | aGate Grid Import Energy |
| Grid connection: energy exported | aGate Grid Export Energy |
| Solar production | aGate Solar Energy |
| Battery: energy going in | aGate Battery Charged Energy |
| Battery: energy coming out | aGate Battery Discharged Energy |

The Energy dashboard needs at least one completed hour of statistics, and up to 2 hours after setup, before it shows totals.
Solar energy comes from extension register 15510–15511, total PV including remote inputs. It's a 32-bit value with the high word first: a reader capture on 2026-10-19 showed 00F1 D254 = 15,848,020 Wh, as reported by the franklinwh-modbus-bridge session. All energy sensors here are in Wh; the Energy dashboard accepts Wh.
6. A simple dashboard card¶
Built-in cards only:
type: vertical-stack
cards:
- type: gauge
entity: sensor.agate_battery_soc
name: Battery
min: 0
max: 100
- type: entities
title: aGate now
entities:
- entity: sensor.agate_solar_power
name: Solar
- entity: sensor.agate_home_load
name: Home
- entity: sensor.agate_battery_power
name: Battery (+ out, − in)
- entity: sensor.agate_grid_power
name: Grid (+ import, − export)
- entity: sensor.agate_self_consumption_reserve
name: Reserve
- entity: sensor.agate_grid_status
name: Grid status
- entity: binary_sensor.agate_grid_connected
name: Grid connected
- type: history-graph
title: Power (last 6 h)
hours_to_show: 6
entities:
- sensor.agate_solar_power
- sensor.agate_home_load
- sensor.agate_battery_power
- sensor.agate_grid_power
Entity IDs follow the name: values; check yours in the entity list if they differ.

Optional, if you added section 2b: a TUI-style card with the descriptions.
type: grid
columns: 2
square: false
cards:
- type: entities
title: Status
entities:
- entity: sensor.agate_operating_mode
name: Operating mode (provisional)
- entity: sensor.agate_battery_state
name: Battery
- entity: sensor.agate_inverter_state
name: Inverter
- entity: sensor.agate_grid_mode
name: Grid mode
- entity: sensor.agate_grid_status
name: Grid status
- entity: sensor.agate_active_alarms
name: Alarms
- type: entities
title: Battery
entities:
- sensor.agate_battery_soc
- sensor.agate_battery_soh
- sensor.agate_battery_voltage
- sensor.agate_battery_current
- sensor.agate_battery_temperature
- sensor.agate_battery_energy_available
- type: entities
title: AC
entities:
- sensor.agate_ac_voltage
- sensor.agate_ac_current
- sensor.agate_ac_frequency
- sensor.agate_power_factor
- sensor.agate_cabinet_temperature
- type: entities
title: Solar
entities:
- sensor.agate_solar_power
- sensor.agate_solar_proximal
- sensor.agate_solar_remote_1
- sensor.agate_solar_remote_2
Pros and cons¶
| HA Modbus YAML (this guide) | A FranklinWH integration built on this library | |
|---|---|---|
| Setup | Copy YAML, restart | Install and configure an add-on or integration |
| Dependencies | None beyond Home Assistant | The integration and this library |
| Transparency | Every sensor maps visibly to one register | Hidden behind the integration |
| Battery control | No (monitor only) | Yes, with clamp, release and verification |
| Scale factors | Fixed in YAML; can go stale after a firmware update | Read from the device |
| FranklinWH quirks | Not handled (e.g. M713 Sta, 15509, sentinel values beyond nan_value) |
Handled |
| Daily totals | From HA's Energy dashboard (lifetime counters) | Same, plus whatever the integration adds |
| Shares the aGate | No: it is the one Modbus client | No: it is the one Modbus client |
Choose this guide if you only want to watch your system and like seeing exactly what is read. Choose an integration if you want control, or don't want to maintain YAML across firmware updates.