Model 704 Conformance Results — Firmware V12R02B60D00

Tests of SunSpec Model 704 (DER AC Controls) active-power control on an aGate running V12R02B60D00, recorded on 2026-10-22.

  • Test files: examples/sequencer/v12_conformance/ (c0–c6, plus v12c_restore.json).
  • Runs: each test ran 3 times — rounds 1 and 3 at base address 0, round 2 at base 40000. All three rounds agreed.
  • Evidence: every result below is decoded from the raw Modbus frames (pysunspec2 trace_func), not from the library's own read-back.
  • Reference: SunSpec DER Information Model Specification v1.2, §3.3.

Summary

# What was tested Result (3 of 3 runs)
c1 Spec order: set WSetPct, then WSetEna=1; change value while enabled ✅ Matches §3.3. 10 % → 714.DCW 500 W; change while enabled applies without rewriting the enable; 0 % holds 0 W
c2 702.WMax as the percentage reference ⚠️ Writes acknowledged but ignored (WMax stays 0). 10 % stays 500 W, so the reference is 5000 W
c3 Watts path: WSetMod=1, WSet 500 → 1000 W ✅ Works. 1000 W is above the 10 % WSetPct cap
c8 Full-rate watts path: WSetMod=1, WSet=5000, WSetEna=1 (2026-10-23) ✅ 714.DCW 4900–5000 W, 701.W about −4710 W, within 5–10 s; after cleanup back to about 200 W (house load)
c4, c4b Reversion (WSetRvrtTms, WSetPctRvrt) ❌ Behaves opposite to the spec (see below)
c5 Charge by percentage: WSetPct = −5 % ❌ Rejected, Modbus exception 3
c6 Charge by watts: WSetMod=1, WSet = −500 W ❌ Rejected, Modbus exception 3

Charging: what "both routes" means

Model 704 offers two ways to set active power, and a negative value means charge in both:

  1. Percentage route — WSetMod=0, WSetPct (int16, scale −1). Tested with −5 %.
  2. Watts route — WSetMod=1, WSet (int32, scale 0). Tested with −500 W.

The positive (discharge) value worked on both routes. The negative (charge) value was refused on both:

Test Frame sent Encoding check Response
c5 FC06 WSetPct = 0xFFCE −50 raw = −5.0 % at scale −1; int16 is 1 register ✔ exception 3 (×3)
c6 FC16 WSet = 0xFFFF FE0C −500 as int32, 2 registers ✔ exception 3 (×3)

Exception 3 is Illegal Data Value: the aGate refused the value at write time. It is not a battery limit, because state of charge was 88–90 % during these tests, leaving room to charge.

Limits of this result

These results show that the aGate refused these two writes. They do not prove that V12 cannot charge through Model 704. The following were not tested:

  • Only one magnitude per route (−5 %, −500 W).
  • Both negative writes were made while WSetEna=0. A negative write while enabled was not tried.
  • Other charge paths outside Model 704 were not tested here.

Reversion (c4, c4b)

What the spec says: when the reversion timer (WSetRvrtTms) expires, the controller reverts to the reversion values (WSetPctRvrt and the others).

What V12 does, 3 of 3 runs:

  • The countdown starts when WSetRvrtTms is written, not when the enable is set.
  • During the countdown the reversion value applies (0 W with WSetPctRvrt=0, about 250 W with WSetPctRvrt=5).
  • After expiry the setpoint applies (10 % → 500 W). WSetEna stays 1.

That is the reverse of the spec. Don't rely on reversion as a fail-safe on V12.

Full-rate discharge (c8)

Run 2026-10-23, 3 rounds, raw frames: FC16 @320 n=2 = 0x0000 1388 (5000 W). Every write was acknowledged. 714.DCW reached 4900–5000 W within 5–10 s of WSetEna=1 and held for the 30 s window. After cleanup (WSetEna=0, WSet=0, WSetMod=0) it returned to about 200 W within 6 s.

The same request through the percentage route (WSetPct raw 1000 = 100 %) is refused with exception 3. A bridge log from 2026-10-23 recorded 116 such refusals in one hour. So on V12, watts requests must use WSet.

Measurement notes

  • 714.DCW reports in 100 W steps, and the house load was about 200–300 W. So the 5 % step (about 250 W) couldn't be told apart from load and is recorded as inconclusive.
  • Base address 0 and 40000 produced identical reads. The controller currently ignores the configured base (#103), so this does not yet show that both bases work.

Effect on the library

FranklinWHController.send_command departs from §3.3:

  • It cycles WSetEna 0 → 1 around each change, which the spec says is not required.
  • It scales WSetPct from the battery rate, not from WMax/WMaxRtg.

Changing it needs the owner's sign-off (it affects hardware) and is tracked separately.