SunSpec Infopoint Sequencer Guide

The SunSpec InfoPoint Sequencer is a high-level orchestration engine integrated into franklinwh-cli. it enables complex, multi-step Modbus operations defined via JSON configuration files.

Purpose & Intent

FranklinWH aGate systems often require specific sequences of register writes (e.g., enabling Remote Control before setting a power level) or periodic verification of hardware state transitions. This tool automates those sequences, ensuring that: 1. Values are Scaled Correctly: Human-readable values (like 30%) are automatically converted to raw Modbus values (like 300) based on the point's Scale Factor (_SF). 2. State is Verified: Every write is followed by a readback loop to confirm the hardware actually accepted and persisted the change. 3. Fail-Fast Execution: Sequences can be configured to abort immediately if a critical step fails.

For a detailed list of supported registers and their compliance status, see the SunSpec Model Reference.


Native Addressing

While the SunSpec standard often defaults to 40000, the FranklinWH native base address is 1. The sequencer automatically handles this based on the -b or --base-address flag.


Usage

Sequences are executed via the franklinwh_cli.py tool:

# Execute a sequence from a JSON file
python3 tools/franklinwh_cli.py -i <IP> --sequence-file examples/reversion_limit_example.json

# Run with custom base address and Modbus unit
python3 tools/franklinwh_cli.py -i <IP> -b 1000 -u 1 --sequence-file <PATH>

2. JSON Schema Master Reference

Key Type Purpose / Function Typical Use Case
name / step string Descriptive label for the step in logs. "Step": "Enable VPP Mode"
writes object Dictionary of Model.Point: Value to write. {"704.WSetEna": 1}
reads list List of Model.Point tags to read and log. ["704.WSetPct", "714.DCW"]
verify bool Wait for readback to match written value. true (Default)
verify_timeout_ms int Max time to poll for write verification. 2000 (Default)
abort_on_failure bool Stop sequence if this step fails. true (Default)
sleep_ms int Wait after step completion (settling time). 500 for hardware propagation.
wait_for object Poll a register until a condition is met. See "Wait For Configuration" below.

Wait For Configuration (wait_for)

Sub-Key Type Purpose Example
point string The Model.Point tag to poll. "704.WSetRvrtRem"
operator string Comparison: ==, !=, >, <, >=, <=. "<="
value any The target value to compare against. 0
timeout_ms int Max polling time (default 30s). 60000 (1 minute)
poll_ms int Time between poll attempts (default 1s). 500 (twice a second)

3. Timing & Settling (sleep_ms)

FranklinWH hardware often requires time to process register changes before they reflect in telemetry or physical state. You can add explicit delays using sleep_ms.

{
  "step": "Enable Remote Control",
  "writes": { "704.WSetEna": 1 },
  "sleep_ms": 500
}
  • sleep_ms: Executed after the writes/verification of the current step.
  • post_sleep_ms: An alias for sleep_ms.

4. Waiting for Conditions (wait_for)

Polls a register until it matches a specific value (useful for verifying slow state transitions or dead-man timers).

{
  "name": "Wait for Reversion",
  "type": "wait_for",
  "point": "704.WSetPct",
  "value": 0,
  "timeout": 20,
  "interval": 2
}

Conformance Diagnostic Suite

Due to inconsistencies in aGate firmware versions (where some SunSpec registers are declared but not implemented), a Diagnostic Suite is provided in examples/diagnostics/.

These examples serve as a "Conformance Test" to track when features become functional in your firmware:

Test File Purpose Intent
curtailment_conformance.json Tests WMaxLimPct Determines if Global Curtailment is functional.
reactive_power_conformance.json Tests VarSet Determines if Reactive Power control is enabled.
heartbeat_conformance.json Tests ControllerHb Checks if the hardware safety heartbeat is active.
reversion_conformance.json Tests WSetRvrtTms Validates if the dead-man switch actually reverts power.

6. Cleanup & Releasing Control

While the CLI provides a dedicated --stop flag, you can also include a "Stop" step at the end of your JSON sequences to ensure the gateway returns to its native operating mode automatically.

A "Clean Release" sequence step:

{
  "m": 704,
  "p": ["WSetEna", "WSetPct", "WSet"],
  "v": [0, 0, 0],
  "note": "Release Modbus control"
}

Why use the Sequencer to stop? - Atomic Automation: Charge for N seconds, then release, all in one command without needing a separate --stop call. - Verification: The sequencer will verify that WSetEna actually returned to 0, catching any persistent "Zombie States." - Custom Fallbacks: In advanced scenarios, you may want to set a specific power level before disabling the master switch.


📖 Model 704 Battery Control Examples

For a detailed suite of real-world active power, export limiting, power factor control, and arbitrage sequences, refer to the Model 704 Control Examples Handbook.

All 12 sequence examples are fully mapped to production JSON files under examples/sequencer/ and utilize safety standby and automatic release steps.


Hardware-Specific Learnings (aGate X)

Last Updated: 2026-05-15

Through development and testing on aGate firmware V10R01B04D00, the following patterns were established:

The "Silent Discard" Pattern

Many registers (like WMaxLimPctEna and ControllerHb) will return a Modbus Success (ACK) when written to, but the internal hardware will silently discard the value. The sequencer's verification loop detects this by comparing the readback against the expected value.

Verified Control Path: WSet (Remote Control)

For curtailing or forcing power, the Remote Control group in Model 704 is the only verified working path: 1. 704.WSetEna = 1: Master switch to enable remote setpoints. 2. 704.WSetPct = X: Set active power as a percentage of rated capacity.

Cleanup

To release the gateway from a sequence and return it to its normal operating mode, use the --stop flag:

python3 tools/franklinwh_cli.py -i <IP> --stop