FranklinWH Modbus TCP Implementation Guide

Definitive reference for controlling FranklinWH aGate battery systems via Modbus TCP. Last verified: 2026-03-08 on aGate X (FW V10R01B04D00)


1. Connection

Host:    YOUR_AGATE_IP (default aGate IP)
Port:    502 (Modbus TCP)
Unit ID: 1 or 2 (both work, DA=1)
Base:    Address 1 (NOT standard 40000 for raw TCP)
Timeout: 10s recommended (WiFi can be slow)
from franklinwh_modbus import FranklinWHController
ctrl = FranklinWHController('YOUR_AGATE_IP')
ctrl.connect()  # Scans SunSpec models, probes extension writability

Models discovered: 1, 502, 701, 702, 703, 704, 705, 706, 707, 708, 709, 710, 711, 712, 713, 714, 715


2. What You CAN and CANNOT Do

┌─────────────────────────────────────────────────────┐
│ ✅ CAN DO (SunSpec M704):     ❌ CANNOT DO:         │
│  • Charge battery at Xw        • Change mode        │
│  • Discharge battery at Xw     • Set reserve %      │
│  • Set idle (standby)          • Switch to Backup   │
│  • Toggle power factor (PF)    • Set max power cap  │
│  • Read ALL registers          • Control ramp rate  │
│  • Auto-revert (software)      • Use heartbeat      │
└─────────────────────────────────────────────────────┘

Extension registers (15507-15509) are read-only. Writes to the FranklinWH extension registers are undocumented and unconfirmed. FranklinWH has not documented these registers and has never documented any of them as writable. Whether FranklinWH must authorise a Modbus client to write them, and how, is unknown. On V12R02B60D00 (owner observation, 2026-10-21), writes to 15507–15509 did not take effect: the mode did not switch and the reserves did not change. Treat them as read-only.


3. Complete Writable Register Map

After exhaustive P1-P4 testing, only 5 of 48 M704 registers accept writes:

Register Address Type Works? What It Does
WSetEna 40318 enum16 ✅ Enable/disable battery power control
WSetMod 40319 enum16 ✅ Power mode: 1 = watts (WSet), 0 = percent (WSetPct)
WSetPct 40324 int16 ⚠️ Percent setpoint; V12 refuses values over 10 %
WSetRvrtTms 40327 uint32 ⚠️ Accepts value, countdown never activates
PFWInjEna 40298 enum16 ✅ Power factor enable (on by default)

Everything else — WMaxLimPct, VarSet, WRmp, ControllerHb, LocRemCtl — is either read-only (writes silently discarded) or unimplemented (returns None).


4. How to Control the Battery

What happens on the wire

send_command() makes up to three Modbus requests and then checks the result. The battery only moves once WSetEna = 1.

sequenceDiagram
    autonumber
    participant App as Your code
    participant Lib as FranklinWHController
    participant aGate as aGate (M704)
    participant Bat as Battery (M714)

    App->>Lib: send_command(BatteryCommand(-3000))
    Lib->>aGate: read M704 (is WSetEna already 1?)
    Lib->>aGate: FC16 WSetMod=1, WSet=3000 (one write)
    aGate-->>Lib: ack
    alt WSetEna was 0
        Lib->>aGate: write WSetEna=1
        aGate-->>Lib: ack
    end
    aGate->>Bat: discharge 3000 W
    Lib->>aGate: read back WSetEna, WSetMod, WSet
    aGate-->>Lib: 1, 1, 3000
    Lib-->>App: (True, "Command Sent: -3000W (WSet=3000)")
    Note over App,Bat: The setpoint stays after your program exits

    App->>Lib: verify_dispatch(-3000, timeout_s=15)
    loop every 2 s until within tolerance or timeout
        Lib->>aGate: read M704 setpoint
        Lib->>Bat: read M714 DCW
    end
    Lib-->>App: {'ok': True, 'actual_w': -3000, ...}

Changing power while running is one write, with no enable step (DER v1.2 §3.3). Stopping writes WSetEna = 0:

sequenceDiagram
    autonumber
    participant App as Your code
    participant Lib as FranklinWHController
    participant aGate as aGate (M704)

    App->>Lib: send_command(BatteryCommand(-1500))
    Lib->>aGate: FC16 WSetMod=1, WSet=1500
    Note right of aGate: WSetEna already 1, so it is not rewritten
    Lib->>aGate: read back 1, 1, 1500
    Lib-->>App: (True, ...)

    App->>Lib: reset_control_state()
    Lib->>aGate: write WSet=0, WSetPct=0 (battery to 0 W)
    Note right of Lib: wait 1 s
    Lib->>aGate: write WSetEna=0, WSet=0, WSetPct=0
    Lib->>aGate: read back WSetEna=0
    Lib-->>App: True
    Note over aGate: The aGate goes back to its own mode (self-consumption, TOU, ...)

Sign convention: BatteryCommand.power_watts is positive = charge, negative = discharge, 0 = hold. The library converts it for the aGate.

Power range

Power is in watts, from 0 to the battery's rating (ctrl.RATED_MAX_DISCHARGE_W, read from the aGate at connect; 5000 W on one battery). Anything above the rating is clamped to it. For a percentage, convert it to watts (example 3).

Python examples

Setup used by every example:

from franklinwh_modbus import FranklinWHController
from franklinwh_modbus.types import BatteryCommand

ctrl = FranklinWHController('YOUR_AGATE_IP')
ctrl.connect()

1. Discharge at 3000 W and confirm the battery moved

ok, msg = ctrl.send_command(BatteryCommand(power_watts=-3000))
if not ok:
    raise SystemExit(msg)          # refused, or read-back did not match

# A successful write is not proof: check battery power (it ramps for a few seconds)
result = ctrl.verify_dispatch(expected_w=-3000, timeout_s=15)
print(result['ok'], result['actual_w'], result['reason'])

2. Minimum and maximum

ctrl.send_command(BatteryCommand(power_watts=-500))
ctrl.send_command(BatteryCommand(power_watts=-5000))   # maximum (M702 rating)
ctrl.send_command(BatteryCommand(power_watts=-8000))   # clamped to -5000, logs a warning

Use ctrl.RATED_MAX_DISCHARGE_W instead of a fixed 5000; it is read from M702 at connect.

3. Percent of maximum

send_command() takes watts. To work in percent, convert:

pct = 40
watts = pct / 100 * ctrl.RATED_MAX_DISCHARGE_W          # 2000 W
ctrl.send_command(BatteryCommand(power_watts=-watts))

4. Discharge for 30 minutes, then hand back to the aGate

ctrl.send_command(BatteryCommand(power_watts=-2000), duration_s=1800)
ctrl.get_command_timer_status()    # {'active': True, 'interval_s': 1800}

The timer runs in your process. If the process exits, the battery keeps discharging: the aGate's own reversion timer does not work (§5.2). Keep the process running, or stop it yourself.

5. Change power while running

ctrl.send_command(BatteryCommand(power_watts=-1000))
ctrl.send_command(BatteryCommand(power_watts=-4000))   # one write, applies directly

6. Hold the battery at 0 W (standby)

ctrl.send_command(BatteryCommand(power_watts=0))

Standby: the battery neither charges nor discharges; solar and grid supply the house. Control stays with you. Release (example 7) hands control back, and the aGate resumes its own mode, which may charge or discharge.

7. Release control (hand back to the aGate)

ctrl.reset_control_state()          # True when WSetEna reads back 0

8. Check the result

ok, msg = ctrl.send_command(BatteryCommand(power_watts=-2000))
if not ok:
    print(msg)   # the aGate refused it, or the read-back did not match

send_command() returns (ok, msg) and does not raise; always check ok.

Check the aGate's state

Read this before a command (is the aGate already under control? what mode is it in?) and after (did it take?). Mode and reserves come from FranklinWH extension registers; see Extension registers.

bat  = ctrl.read_battery_status()    # M713/M714
mode = ctrl.read_native_mode()       # extension 15507–15509
ctl  = ctrl.read_control_status()    # M704
grid = ctrl.read_grid_status()       # M701

print("SoC            ", bat['soc'], "%")
print("Battery        ", bat['battery_power_w'], "W", bat['battery_state'])  # + = discharge; state from DCW, ±50 W
print("Operating mode ", mode['mode_name'])        # 15507: Emergency Backup / Self-Consumption / TOU
print("SC reserve     ", mode['self_reserve_pct'], "%")   # 15508
print("TOU reserve    ", mode['tou_reserve_pct'], "%")    # 15509
print("Grid           ", grid['connection_state'])
print("Under Modbus control:", ctl['wset_enabled'] == 1)

Notes:

  • battery_state is derived from battery power. M713 Sta always reads 0 (§5.3).
  • No extension register is documented as a run status. Don't treat any of 15000–15043 as one.
  • Extension registers are read-only in practice (§5.6). Don't write them to change mode or reserves.

CLI

# Discharge at 3000 W (persists after the CLI exits)
python3 tools/franklinwh_cli.py -i YOUR_AGATE_IP --discharge 3000

# Discharge at 2000 W for 30 minutes (the CLI counts down, then stops; Ctrl+C stops early)
python3 tools/franklinwh_cli.py -i YOUR_AGATE_IP --discharge 2000 --revert 1800

# Maximum discharge (M702 rating)
python3 tools/franklinwh_cli.py -i YOUR_AGATE_IP --max-discharge

# Standby: hold at 0 W, control stays with you
python3 tools/franklinwh_cli.py -i YOUR_AGATE_IP --standby

# Check status (does not change the setpoint)
python3 tools/franklinwh_cli.py -i YOUR_AGATE_IP --status

# Release: hand control back to the aGate
python3 tools/franklinwh_cli.py -i YOUR_AGATE_IP --stop

5. Key Hardware Quirks

5.1 The LocRemCtl Paradox

M715 LocRemCtl (addr 1089) is read-only, always "Local" (1). Per SunSpec 2, this should mean the DER rejects ALL writes. FranklinWH violates this — it selectively accepts power writes while ignoring lifecycle features:

Feature SunSpec 2 Expects FranklinWH Does
Power writes (WSetPct) ❌ Reject ✅ Accepts
Reversion countdown N/A ⚠️ Not verified with proper sequencing†
Controller heartbeat ❌ Reject ⚠️ Not verified with proper sequencing†
LocRemCtl write Allow ❌ Read-only

Impact: All lifecycle features (heartbeat, reversion timer) currently implemented in software. †Re-verification with proper SunSpec 6-phase sequencing pending — see SUNSPEC_DER_SEQUENCING_REFERENCE.md.

5.2 Command Persistence

Commands persist indefinitely after disconnect. The aGate holds the last WSetPct value until: - Another send_command() overwrites it - reset_control_state() sets WSetEna=0 - The aGate is power-cycled

There is no automatic timeout — hardware reversion (WSetRvrtTms) accepts values but never executes. Use the library's software timer (duration_s parameter).

5.3 Battery State Is Not in M713

M713 Sta is a status flag (SunSpec 2: 0 OK, 1 WARNING, 2 ERROR), not a charge/discharge state; it read 0 (OK) while charging. Derive battery state from M714 DCW (positive = discharging on V12, c8):

if dc_power < -50:   state = 'CHARGING'
elif dc_power > 50:  state = 'DISCHARGING'
else:                state = 'IDLE'

5.4 Sign Convention

Register Software Hardware
WSet Positive = Charge Negative = Charge (V12, c3/c8)
WSetPct Positive = Charge Negative = Charge

The library inverts: m704.WSet.value = -watts

5.5 WSet vs WSetPct

An earlier note said writing WSet alongside WSetPct caused "mode flickering". It came from one user report (2026-02) with no firmware, frames or WSetMod=1 test, and is unverified. With WSetMod=1, WSet works on V12 (c3, c8). The library now sends watts through WSet.

5.6 Extension Registers: Writes Undocumented

Address Name Access Notes
15507 OnGridMode R (writes undocumented) 1=Backup, 2=Self-Consumption, 3=TOU
15508 SelfReserve R (writes undocumented) Reserve SOC %
15509 TouReserve R (writes undocumented) ⚠️ Always mirrors 15508 (firmware defect)

Writes to the FranklinWH extension registers are undocumented and unconfirmed. FranklinWH has not documented these registers and has never documented any of them as writable. Whether FranklinWH must authorise a Modbus client to write them, and how, is unknown. On V12R02B60D00 (owner observation, 2026-10-21), writes to 15507–15509 did not take effect: the mode did not switch and the reserves did not change. Treat them as read-only.

The library's setters (set_native_mode(), set_self_consumption_reserve(), set_tou_reserve()) attempt the write, read the register back, and return (ok, message) with the read-back result. They do not promise any effect.

Earlier versions of this guide said that writes need a "SPAN Modbus" unlock that FranklinWH enables for SPAN Smart Panel owners, and that a SPAN panel on the network or a cloud spanFlag setting predicts writability. That was speculation (undocumented, unverified) and has been removed. SPAN is a third-party smart-panel company; nothing here implies any relationship between SPAN and FranklinWH or this library.

Checking your unit

--test-extension-write (or ctrl.test_extension_writability()) writes test values to 15507–15509, reads them back and restores them. ⚠️ It writes to the device. The read-back is the only reliable answer.

Mode Control Tiers (Web App)

The admin console defines three control tiers. Tier 1 assumes extension writes work, which is speculation (undocumented, unverified):

Tier Method Capability
⚡ Tier 1: Extension writes Direct Modbus register writes (undocumented; not applied on V12R02B60D00) Full mode/reserve control (Phase 4)
☁️ Tier 2: Cloud Bypass Mode changes via Cloud API Mode control, data stays Modbus
📖 Tier 3: Read-Only View only No control

TODO: Mode Control Tier selection should move from MQTT Admin to a Setup Wizard — it's a one-time configuration decision, not an MQTT setting.

5.7 PFWInjEna (Power Factor)

PFWInjEna (40298) is enabled by default (=1) and writable: - Enabled (=1): PF ≈ unity (-1 raw, SF -3) - Disabled (=0): PF = 0.003 (essentially no correction) - Do not leave disabled — it controls the aGate's default PF correction

5.8 SunSpec2 Library Quirks

The sunspec2 Python client remaps addresses internally. Extension registers (15000+, 15500+) must be read via raw Modbus TCP socket, not sunspec2.client.read():

import struct
sock = ctrl.dev.client.socket
req = struct.pack('>HHHBBHH', 0, 0, 6, unit_id, 3, addr, count)
sock.sendall(req)
resp = sock.recv(256)

5.9 M715 Address Space

M715 registers are read and written at their PDU addresses (1087–1095, as in the FranklinWH PICS). Offsetting by 40000 (PDU 41087+) returned exception 2 (ILLEGAL_DATA_ADDRESS) on V10R01B04D00; V12R02B60D00 mirrors the map at 40000. Use the PDU address. The aGate's SunSpec map starts at PDU 0; see QUIRKS, Register Addressing.


6. Software vs Hardware Features

Feature Hardware Software (Library)
Charge/Discharge ✅ M704 WSetPct ✅ send_command()
Auto-Revert Timer ❌ WSetRvrtTms broken ✅ duration_s param
Heartbeat ❌ ControllerHb ignored ❌ Not implemented
SoC Ramp ❌ WRmp unimplemented ✅ --soc-ramp-window
Battery State ❌ Not in M713 (Sta is OK/WARNING/ERROR) ✅ Derived from M714 DCW
Conflict Detection N/A ✅ check_state()
Mode Control ❌ Extensions read-only ⚠️ Virtual modes (power-only)

7. Reading System State

# Battery
bat = ctrl.read_battery_status()
# → soc, dc_power, dc_voltage, temperature, battery_state

# Solar + Grid + Load
solar = ctrl.read_solar_production()
grid  = ctrl.read_grid_status()

# Control status
ctl = ctrl.read_control_status()
# → wset_enabled, wset_pct, wset_watts

# Native mode (aGate's cloud setting)
mode = ctrl.read_native_mode()
# → mode_name, self_reserve_pct, tou_reserve_pct

# Health check (zombie state detection)
h = ctrl.healthcheck()
# → healthy, message, recommendations

Document What It Covers
DER_CONTROL_REFERENCE.md Full register map — all 48 M704 + 6 M715 fields
FRANKLINWH_SUNSPEC_QUIRKS.md Detailed quirk analysis (LocRemCtl, M713, extensions)
ORCHESTRATION_AND_CONTROL.md Command sequences, SoC ramping, entry points
VERIFICATION_BASELINE.md Full register dump + cross-verification

Test Evidence

Test Result Evidence
P1: Heartbeat ❌ Confirmed non-functional (6-phase re-test) tests/results/2026-03-08_p1_control_tests.md
P1: WSetRvrtTms ✅ WORKS (60s accepted, countdown active) Re-tested 2026-03-13 with proper sequencing
P2: WMaxLimPct ❌ Confirmed non-functional (enable silently discarded) tests/results/2026-03-08_p2p4_control_tests.md
P3: VarSet ❌ Confirmed non-functional (VarSetEna silently discarded) Re-tested 2026-03-13 with 6-phase protocol
PCS WChaRteMax/WDisChaRteMax ❌ Confirmed 0xFFFF (not writable) tests/results/2026-03-13_pcs_charge_rate_write_probe.md
P4: WRmp ❌ Unimplemented Same file
PFWInjEna ✅ Writable Same file
Extension write-probe ❌ Read-only tests/results/2026-03-08_extension_write_probe.md

Device: FranklinWH aGate X (SN: XXXXXXXXXXXXXXXXXXXX, FW: V10R01B04D00) Last Updated: 2026-03-09