Alarms, Errors and Exceptions

What the aGate reports when something is wrong, per firmware (M1 Vr). There are three kinds:

  • Alarm and status points: registers that should change when the device has a fault.
  • Modbus exceptions: the aGate refuses a request with an exception code.
  • Silent discards: the aGate acknowledges a write without an exception, but the value doesn't stick or has no effect. No alarm or exception reports these.

Every row cites its source. Firmware columns: V10 = V10R01B04D00, V12 = V12R02B60D00. "—" = not on record. Re-check every row when the firmware changes, and add a column for the new firmware rather than overwriting.

Alarm and status points

No alarm or status point has ever been seen in a fault state, so whether the aGate raises any alarm over Modbus is unknown. All captures on record are from normal operation at one site.

Point (PDU) Meaning (SunSpec) V10 V12 Library
M701 Alrm (76) DER alarm bitfield 0 (2026-03-13 probe under out-of-range writes; 2026-05-14 scan) 0 (2026-10-20) read_alarms()['system_alrm'], named in decoded
M701 St (73) Operating state 1 (2026-05-14) 1 (2026-10-20) —
M701 InvSt (74) Inverter state 3 = RUNNING (2026-05-14) 3 (2026-10-20) —
M701 ConnSt (75) Grid connection state 1 (2026-05-14) 1 (2026-10-20) —
M701 DERMode (78) DER mode bitfield 1 (2026-05-14) 1 (2026-10-20) —
M701 ThrotPct (180) Throttle % not implemented (2026-05-14 scan). An undated QUIRKS row says "readable, always 0 %"; it conflicts with the scan and has no raw read behind it not implemented (2026-10-20) —
M701 ThrotSrc (181) Throttle source bitfield not implemented (0xFFFFFFFF) not implemented (2026-10-20) —
M701 MnAlrmInfo (193) Manufacturer alarm text "Manufacturer custom error info", a fixed placeholder (2026-03-13; 2026-05-14) same placeholder (2026-10-20) read_alarms()['vendor_info']: empty when the value is the placeholder; vendor_info_raw has the string as read (#136)
M713 Sta (1039) Storage status: 0 OK, 1 WARNING, 2 ERROR 0, including while charging at 400 W (2026-03-10) 0 (2026-10-20) read_alarms()['battery_sta']; also read_battery_status()['status_raw']
M714 PrtAlrms (1044) Which DC ports have an alarm 0 (2026-03-13 probe; 2026-05-14) 0 (2026-10-20) read_alarms()['dc_port_alrm']
M714 Prt.1.DCAlrm (1085) Port alarm bitfield — (port block not read) 0, with the whole port block 0 (#129) named in read_alarms()['decoded']
M714 Prt.1.DCSta (1084) Port state — 0 = OFF while the battery moves 600 W (#129) WARNING/ERROR named in decoded
M502 Stat, StatVend, Evt, EvtVend Solar module status and events 0 (2026-05-14) 0 (2026-10-20) read_alarms()['solar_evt'] (Evt)
M715 DERHb (1090) DER heartbeat 0 (2026-05-14) 0, does not advance (2026-10-23, #107) —
M715 AlarmReset (1094) Alarm reset write accepted, reads back 0, no latched alarms (2026-03-13) 0 (2026-10-20) —
M715 OpCtl (1095) Operation control 0 (2026-03-13); write not tested 0 (2026-10-20) —
Extension 15016 Status code (undocumented) 2 on-grid; 6 during a WSet dispatch; 3 off-grid (bridge reports, 2026-10-09/15) 2 on-grid; 1 for ~2 min after the aGate was unreachable (bridge report, 2026-10-21) not read; see ext_15016_status

Sources: V10, docs/AGATE_FULL_SCAN_2026-05-14.txt and the 2026-03-13 alarm probe in PICS Conformance Cross-Reference. V12, the 2026-10-20 re-scan behind the V12 snapshot, with values listed in #136. Extension 15016: firmware_quirks.json.

Modbus exceptions

Request V10 V12 Library
Read at PDU 40000+ (the SunSpec map's conventional base) exception 2 (2026-03-15) served: the map is mirrored at 40000 (2026-10-20, #84) binds to whichever base answers (#84)
Read at PDU 50000 — exception 2 (2026-10-20) —
M704 WSetPct above +100 raw (10.0 %) accepted, e.g. raw 1500 (2026-05-14) exception 3 (2026-10-24, #92, #104) logged "Refused by the aGate", raised as ModbusClientException("Rejected by the aGate (…)"), not retried (#96, #114 A4)
M704 WSetPct negative (charge) accepted (2026-03-13 probe, raw −1500) exception 3 for every negative value (2026-10-24, #104) as above
M704 WSet negative (charge) — exception 3 (2026-10-22, #104) as above
Extension 15000–15043, 15500–15513, 16000–16002 reads none none; 15044–15099, 15514–15599, 16003–16099 also read without an exception (all 0) —

A refused write leaves the earlier setpoint in place. Every refusal is logged with the register, the raw values and the firmware.

Silent discards (acknowledged, not applied)

These writes get a normal response, with no exception and no alarm. Only a read-back shows that nothing happened.

Write V10 V12 Library
M702 WMax reads back 0 (2026-03-13) WMax stays 0 (2026-10-22, #104) not written in normal use
M715 ControllerHb reads back 0 reads back 0, and DERHb stays 0 (2026-10-23, #107) —
M704 WMaxLimPctEna reads back 0 (2026-03-13) — —
M704 VarSetEna reads back 0 (2026-03-13) — —
M702 WChaRteMax, WDisChaRteMax, VAChaRteMax, VADisChaRteMax 0xFFFF (not implemented); writes discarded (2026-03-13) — —
Extension 15507 mode, 15508/15509 reserves — normal FC06 echo; values unchanged after 30–90 s (2026-10-23, #107) set_native_mode() etc. return the read-back result; a failed write is reported
M704 WSetRvrtTms reversion countdown runs, power not reverted at expiry (2026-03-13) inverted: the reversion value applies during the countdown and the setpoint after it (2026-10-22, #104) software timer + reset_control_state()

Sources: SunSpec Quirks deviation table (2026-03-13 tests), PICS Conformance Cross-Reference, firmware_quirks.json (m702_wmax_write, m715_controller_heartbeat, ext_15507_15509_writes, m704_wsetrvrttms_reversion).

Not reported (reads 0 instead of "not implemented")

Model 714 DCA and the whole port 1 block read plain 0 on V12. The PICS declares them supported. From the next release the library reports these as None (#129, #130). See SunSpec Quirks, Model 714.

Open

  • No alarm has been observed in a fault state. Reading the alarm points during a real event (grid outage, over-temperature, battery fault) would show whether any of them is wired up. Record the date, firmware and every point above.
  • The V10 rows from 2026-03-13 have no raw capture on record except where a scan is cited.