FranklinWH Extension Registers

Besides the SunSpec models, the aGate's Modbus TCP Server (aGate :502) has FranklinWH-specific holding registers: the operating mode, the SoC reserves, the solar breakdown and the home load. This page is the one place they are listed.

How they work

  • Outside the SunSpec model chain. sunspec2 can't see them. Read them with a plain FC3 request at the PDU address below. FC6 writes are undocumented; see Writing.
  • Use the address as listed. These are Modbus PDU addresses, 0-based, as sent on the wire. Don't offset by 40000 or 40001: untested for these registers, and an exception 2 on V10R01B04D00 for the SunSpec map. See Register Addressing.
  • Vendor-specific and partly undocumented. Behaviour can change with firmware. Each row says what it rests on: Documented (listed on the SPAN tab of FranklinWH's PICS, which is proprietary, not distributed and not a public specification; it does not confirm writability on current firmware), Measured (read on the device, with date and firmware), or Inferred.
  • One Modbus client per aGate. Stop other clients before reading.

Register table

PDU Name Access Type, unit Meaning In the library Evidence
15500 PVUse R uint16 flag Proximal (aGate) PV installed read, not returned Documented
15501 apBoxPVUse R uint16 flag Remote (aPbox/aHub) PV installed read, not returned Documented
15502 PVOutputP R uint16, W Total PV power, all sources read_solar_status()['extension']['pv_total'] Documented; measured
15503 — R uint16, W PV proximal …['pv_proximal'] Documented
15504 — R uint16, W PV remote 1 …['pv_remote1'] Documented
15505 — R uint16, W PV remote 2 …['pv_remote2'] Documented
15506 LoadActiveP R uint16, W (~100 W steps on V10R01B04D00; ~1 W on V12R02B60D00) Home load …['home_load_ext_quantized'] Documented; measured 2026-03-15 (V10), 2026-11-03 (V12)
15507 OnGridMode R (writes undocumented) uint16 enum Operating mode read_native_mode()['mode_raw'], ['mode_name']; written by set_native_mode() Measured 2026-10-21/22, V12R02B60D00 (1, 2, 3); see below
15508 SelfReserve R (writes undocumented) uint16, % Self-consumption SoC reserve read_native_mode()['self_reserve_pct']; set_self_consumption_reserve() Measured 2026-10-18, V10R01B04D00
15509 TouReserve R (writes undocumented) uint16, % TOU SoC reserve. On V12R02B60D00 it holds the TOU reserve (15 vs SC 8, matching the app). On V10R01B04D00 it repeated 15508 read_native_mode()['tou_reserve_pct']; set_tou_reserve() Measured 2026-10-20/21, V12R02B60D00; the defect measured 2026-10-18, V10R01B04D00 (#63)
15510–15511 PVOutputWh R uint32 (high, low), Wh PV energy, total (lifetime) read, not returned Measured: matches M502 OutWh
15512–15513 proxOutputWh R uint32 (high, low), Wh PV energy, proximal (lifetime) read, not returned Measured: matches M502 OutWh
16000 — R uint16, W (~1 W) Home load, high resolution …['home_load_ext'] (falls back to 15506) Undocumented; measured 2026-03-15
16001 — R uint16, % Reserve for the active mode: 100 in Emergency Backup, 15508's value in Self-Consumption (8), 15509's in TOU (15) — Undocumented; measured on V12R02B60D00, one read per mode, 2026-10-21/22 (#63)
16002 — R uint16 20 in both Self-Consumption and TOU on the reference site; matches the local API's BBBackupSoc — Undocumented; meaning unconfirmed (#63)
15000–15043 — R uint16 raw; some pairs look like 32-bit values Undocumented. Several match SunSpec values; see register by register and the mapping — Undocumented; raw values measured; meanings inferred. Writes accepted but discarded (probe 2026-03-08)

… = read_solar_status()['extension']. The raw scans behind the measured rows are in the Extensions Manifest (V10R01B04D00) and the V12R02B60D00 snapshot.

15000–15043, register by register

Raw uint16 values from one site (#132). V10R01B04D00: the undated scan in the Extensions Manifest. V12R02B60D00: the 2026-10-20 re-scan and an owner read on 2026-10-31 (15000–15039 only). Candidates are inferred from equal or near values in the same capture, not measured meanings; none is used by the library. Each register has an entry in firmware_quirks.json (ext_15000 … ext_15043; 15013, 15016 and 15035 keep their earlier ids), all with mapped: false.

PDU V10 V12 10-20 V12 10-31 Meaning
15000 0 1 1 Meaning unknown: 1 on V12, 0 on V10.
15001 0 0 0 Meaning unknown; read 0 on every capture.
15002 0 0 0 Meaning unknown; read 0 on every capture.
15003 0 800 200 Confirmed 2026-11-03: PV power, equal to M502 OutPw.
15004 0 0 0 Meaning unknown; read 0 on every capture.
15005 0 0 0 Meaning unknown; read 0 on every capture.
15006 0 65535 65535 Meaning unknown: high word of a signed pair with 15007 (65535 on V12).
15007 257 65375 65303 Meaning unknown: low word of a signed pair with 15006 (-161 on 2026-10-20, -233 on 2026-10-31).
15008 0 0 0 Meaning unknown; read 0 on every capture.
15009 0 0 0 Meaning unknown; read 0 on every capture.
15010 0 0 0 Meaning unknown; read 0 on every capture.
15011 583 195 198 Confirmed 2026-11-03: home load, equal to 16000.
15012 65535 65535 65535 Read 65535 throughout the 2026-11-03 run (charging). Whether it is the high word of a 32-bit value with 15013 is still open.
15013 60538 64907 65507 Confirmed: battery power, int16, positive = discharging, negative = charging; tracks M714 DCW at ~1 W.
15014 0 65535 65535 Meaning unknown: high word of a signed pair with 15015 (65535 on V12).
15015 61 65511 65512 Meaning unknown: low word of a signed pair with 15014 (-25 on 2026-10-20, -24 on 2026-10-31).
15016 2 2 2 Inferred: status. 2 normal, 6 dispatch, 3 likely off-grid, 1 likely start-up (week of bridge history).
15017 20 20 20 Candidate: same value as 16002 (20) on every read.
15018 65535 5000 5000 Candidate: M702 WChaRteMaxRtg (5000 on V12); 65535 on V10.
15019 65535 5000 5000 Candidate: M702 WDisChaRteMaxRtg (5000 on V12); 65535 on V10.
15020 13600 13600 13600 Candidate: M713 WHRtg (13600 on every read).
15021 1 1 1 Meaning unknown: 1 on every read.
15022 5581 65533 65475 Meaning unknown: varies (5581 on V10; 65533, 65475 on V12).
15023 0 0 0 Meaning unknown; read 0 on every capture.
15024 49969 50010 50030 Candidate: grid frequency x 1000 (49969, 50010, 50030).
15025 2380 2422 2416 Confirmed 2026-11-03: grid voltage × 10, M701 LNV.
15026 1 1 1 Meaning unknown: 1 on every read.
15027 0 0 0 Meaning unknown; read 0 on every capture.
15028 0 0 0 Meaning unknown; read 0 on every capture.
15029 70 91 94 Confirmed 2026-11-03: high word of M701 TotWhInj (uint32 with 15030).
15030 30761 993 18367 Confirmed 2026-11-03: low word of M701 TotWhInj.
15031 0 0 0 Meaning unknown; read 0 on every capture.
15032 0 0 0 Meaning unknown; read 0 on every capture.
15033 22 29 29 Confirmed 2026-11-03: high word of M701 TotWhAbs (uint32 with 15034).
15034 22637 18330 19910 Confirmed 2026-11-03: low word of M701 TotWhAbs.
15035 268 325 994 Confirmed 2026-11-03: SoC × 10, 0.1 % steps.
15036 956 948 948 Candidate: M713 SoH raw (948 = 948 on 2026-10-20).
15037 0 0 0 Meaning unknown; read 0 on every capture.
15038 0 0 0 Meaning unknown; read 0 on every capture.
15039 0 0 0 Meaning unknown; read 0 on every capture.
15040 65527 826 — Inferred: PV power (int16) as Direct Connect reports it; −9 W after dark.
15041 0 0 — Meaning unknown; read 0 on every capture.
15042 0 0 — Meaning unknown; read 0 on every capture.
15043 1 1 — Meaning unknown: 1 on every read.

A read-only correlation run on 2026-11-03 (charging, 54 samples) confirmed 15003, 15011, 15013, 15025, 15029–15030, 15033–15034 and 15035; see the mapping. The rest stay candidate or unknown (#132).

15507 operating mode values

Value Mode Evidence
1 Emergency Backup Measured on V12R02B60D00 with the app in that mode (2026-10-21; again 2026-10-28)
2 Self-Consumption Measured on V12R02B60D00 (2026-10-21)
3 TOU Measured on V12R02B60D00 (2026-10-21)

No other value has been read from 15507. This matches the library, the 2026-05-14 device scan and the first QUIRKS table. Earlier docs and code also listed 0 = Emergency and 4 = Manual, and one QUIRKS revision had 1 = TOU and 3 = Manual. Those were added without a source and have been removed (#75). Writing 15507 did not take effect on V12R02B60D00 (owner observation, 2026-10-21), so the mapping holds for reading only.

Extension → SunSpec mapping

One row per register. For each register: the SunSpec point that carries the same quantity, or none (non-SunSpec), and whether a client should prefer the extension value. Non-SunSpec registers are vendor quirks: no SunSpec model holds them.

Status: - Confirmed: named in FranklinWH's register list and/or read with a known device state, and equal to the SunSpec point where there is one. - Inferred: equal or near the SunSpec value in a capture, but not read in the same pass as the SunSpec chain under controlled conditions. Equal values are leads, not proof (#132). - Unknown: no candidate, or a lead from a value match only.

Captures: V10 = V10R01B04D00, undated scan (Extensions Manifest). V12 = V12R02B60D00: the 2026-10-20 snapshot (export and re-scan), and owner reads on 2026-10-31 and 2026-11-03 (unit 1, extensions only, no SunSpec read). All from one site. Type is the uint16/int16 reading of the raw register; pairs are (high, low).

15000–15043

PDU Type, scale, units, sign SunSpec equivalent Status and evidence Prefer the extension?
15000 uint16 none (non-SunSpec) Unknown. 1 on V12 (10-20, 10-31, 11-03), 0 on V10 —
15001, 15002, 15004, 15005, 15008–15010, 15023, 15027, 15028, 15031, 15032, 15037–15039, 15041, 15042 uint16 none known Unknown. 0 on every capture —
15003 uint16, W M502 OutPw Confirmed. Equal to OutPw in 54/54 samples, 1700–5600 W, while charging (run 2026-11-03). Earlier: equal to 15502 (10-20, 10-31) No: same value
15006–15007 int32 pair, sign unknown none known Unknown. −161 (10-20), −233 (10-31), −594 (11-03); −268..−7 while charging (run 2026-11-03); +268..+270 after dark (run 2026-11-06). Flips sign between day and night; no SunSpec point matches. V10 15007 = 257 —
15011 uint16, W none (SunSpec has no home load point) Confirmed: home load. Equal to 16000 in 54/54 samples, 67–945 W (run 2026-11-03) Use 16000 (same value)
15012–15013 int16 (15013), W, positive = discharging, negative = charging M714 DCW Confirmed both ways. Charging: tracks DCW in 54/54 samples, −1446 to −4740 W, median 10 W apart (run 2026-11-03). Discharging: positive in 28,320/28,320 samples, within 100 W of DCW in 99.9 % (bridge history 2026-10-30–11-06); +240..+256 at DCW +200..+300 (run 2026-11-06). DCW moves in 100 W steps. 15012 read 65535 throughout, so int16 vs int32 is still open Yes, for resolution: about 1 W vs DCW's 100 W steps
15014–15015 int32 pair, sign unknown none known Unknown. −25 (10-20), −24 (10-31), −22 (11-03); −135..302 while charging, no match (run 2026-11-03); −529..−420 after dark, moving with M701 Var (r = −0.98 over a small range) (run 2026-11-06). Lead only. V10 15015 = 61 —
15016 uint16 enum none (non-SunSpec) Inferred: operating status. Over a week of 10 s samples (bridge history 2026-10-30–11-06): 2 in 53,708 (normal); 6 in 2,482, with the battery discharging ~4.9 kW to the grid (a dispatch); 3 in 631, with grid power 0 and the battery supplying the home (likely off-grid); 1 in 12, all values 0 (likely start-up or unreachable). Earlier bridge reports agree: 6 during a WSet dispatch, 3 off-grid (V10) Yes, as a vendor status. SunSpec has no equivalent
15017 uint16 none known Unknown. 20 on every read, equal to 16002. An ambient-temperature lead comes from a value match only —
15018 uint16, W M702 WChaRteMaxRtg Inferred. 5000 = 5000 (V12 snapshot). V10: 65535 No: same value
15019 uint16, W M702 WDisChaRteMaxRtg Inferred. 5000 = 5000 (V12 snapshot). V10: 65535 No: same value
15020 uint16, Wh M713 WHRtg Inferred. 13600 = 13600 on every capture (V10 and V12) No: same value
15021 uint16 none known Unknown. 1 on every read —
15022 int16 none known Unknown. V10 5581; V12 −3, −61, −295 (10-20, 10-31, 11-03); −342..520 while charging, −13..11 after dark; no match in either run (run 2026-11-03, run 2026-11-06) —
15024 uint16, × 0.001, Hz M701 Hz (Hz_SF −3, same scale) Inferred. Close to Hz but not equal: within the bracketing reads in only 3/54 samples, up to 0.020 Hz apart (run 2026-11-03). Possibly a different measurement or averaging No
15025 uint16, × 0.1, V M701 LNV (V_SF −1) Confirmed. Equal to LNV raw in 48/54 samples, the rest within 0.2 V (run 2026-11-03) No: same scale
15026 uint16 none known Unknown. 1 on every read —
15029–15030 uint32 pair, Wh M701 TotWhInj Confirmed. Equal in 54/54 samples (run 2026-11-03); also 5964768 = 5964768 (V12 snapshot). 15030 alone is the low word, not a voltage No: same value
15033–15034 uint32 pair, Wh M701 TotWhAbs Confirmed. Equal in 54/54 samples (run 2026-11-03); also 1918874 = 1918874 (V12 snapshot) No: same value
15035 uint16, × 0.1, % M713 SoC Confirmed. Tracks SoC × 10 within ±5 in 54/54 samples (run 2026-11-03); within 1 % of the bridge's SoC in 56,835/56,835 samples over 0–100 % (bridge history 2026-10-30–11-06). SoC reads whole percents Yes, for resolution: 0.1 % steps
15036 uint16, × 0.1, % M713 SoH Inferred. 948 = 948 (V12 snapshot); 956 on V10 (SoH 95.6 % on 2026-05-14). 948 on 11-03 No: same value
15040 int16, W none (non-SunSpec) Inferred: PV power as Direct Connect reports it. Equal to the Direct Connect bridge's solar figure (median 1 W apart, 13/17 within 50 W) while M502 OutPw read about 59 W lower (run 2026-11-03); −9..−8 W after dark while OutPw and 15003 read 0 (run 2026-11-06). V10 65527 (−9) Yes, if a client wants the figure the app shows; otherwise 15003 / OutPw
15043 uint16 none known Unknown. 1 on every read —

15500–15513 and 16000–16002

PDU Type, scale, units, sign SunSpec equivalent Status and evidence Prefer the extension?
15500, 15501 uint16 flags none (non-SunSpec) Confirmed: PV installed (proximal, remote). Listed by FranklinWH; 15500 = 1, 15501 = 0 (V12 10-20) Yes: no SunSpec equivalent
15502 uint16, W M502 OutPw Confirmed. Listed by FranklinWH as total PV, all sources; 300 = 300 (V12 snapshot) No on a site with proximal PV only. With remote PV the two may differ: untested
15503 uint16, W none (non-SunSpec) Confirmed: PV proximal. Listed by FranklinWH; 300 (V12 snapshot) Yes: SunSpec has no per-source split
15504, 15505 uint16, W none (non-SunSpec) Listed by FranklinWH as PV remote 1/2. 0 on a site with no remote PV, so the values are untested Yes: SunSpec has no per-source split
15506 uint16, W none (SunSpec has no home load point) Confirmed: home load. Listed by FranklinWH; 185 = 16000 (V12 snapshot); within 100 W of 16000 in 54/54 samples (run 2026-11-03). Resolution: ~100 W steps on V10 (2026-03-15), ~1 W on V12 (2026-11-03) Use 16000
15507 uint16 enum none (non-SunSpec) Confirmed: 1 Emergency Backup, 2 Self-Consumption, 3 TOU, read with the app in each mode (V12, 2026-10-21/28) Yes: no SunSpec equivalent
15508 uint16, % none (non-SunSpec) Confirmed: Self-Consumption reserve (V10 2026-10-18; V12 2026-10-21) Yes
15509 uint16, % none (non-SunSpec) Confirmed on V12: TOU reserve (2026-10-21). On V10 it repeated 15508 (#63) Yes, on V12
15510–15511 uint32 pair, Wh M502 OutWh Confirmed. Listed by FranklinWH; 15882870 = 15882870 (V12 snapshot); equal on V10 No: same value
15512–15513 uint32 pair, Wh none (proximal only) Confirmed: PV energy, proximal. Listed by FranklinWH; equal to M502 OutWh on a site with proximal PV only Yes, for the per-source split
16000 uint16, W, ~1 W none (SunSpec has no home load point) Confirmed: home load, ~1 W steps (V10 2026-03-15); 185 = 15506 (V12 snapshot) Yes, over 15506: finer resolution. The library already does this
16001 uint16, % none (non-SunSpec) Confirmed on V12: reserve of the active mode. 8 in Self-Consumption, 15 in TOU, 100 in Emergency Backup (2026-10-21/28) Yes: no SunSpec equivalent
16002 uint16, % none (non-SunSpec) Unknown. 20 in all three modes (V12 2026-10-21). Equal to the local API's BBBackupSoc (V10 2026-10-17): a value match, unconfirmed —

Not mapped: 15044–15099, 15514–15599 and 16003–16099 read without exceptions but nothing is populated (V12 2026-10-20).

Correlation run 2026-11-03 (V12R02B60D00, one site): read-only, sole client, 3 runs × 18 samples while charging. Each sample read the extension blocks, the SunSpec chain, then the extension blocks again. Positive controls 15510–15511 = M502 OutWh and 15502 = M502 OutPw passed. 16000 ≈ 15506 passed once the check compared both bracketing reads; it was changed after the run because 15506 updated mid-pass in 1 sample. Evening run 2026-11-06: read-only, 3 runs × 18 samples after dark (M714 DCW +200..+300 W, PV 0). The other Modbus clients were left running at the owner's call; every read succeeded and all three positive controls passed. Bridge point history 2026-10-30–11-06: the Modbus bridge's 10 s history of 15013, 15035 and 15016 alongside its SunSpec points (charging values of 15013 were missing because of a bridge defect, since fixed). Direct Connect bridge metrics: 30 s samples overlapping the 2026-11-03 run. Still open: the unknown signed pairs (15006–15007, 15014–15015, 15022), whether 15012–15013 is int16 or int32, and whether 15024 is the same frequency measurement (#132).

Reading

Use the library methods:

solar = ctrl.read_solar_status()
ext   = solar.get("extension") or {}          # 15500–15509, 16000
mode  = ctrl.read_native_mode()               # 15507–15509
print(ext.get("pv_total"), ext.get("home_load_ext"), mode.get("mode_name"))

For registers the library doesn't return, use a raw FC3 read; see API Cookbook §8.3.

Writing ⚠️

  • Writes to the FranklinWH extension registers are undocumented and unconfirmed. FranklinWH has not documented these registers and has never documented any of them as writable. Whether FranklinWH must authorise a Modbus client to write them, and how, is unknown. On V12R02B60D00 (owner observation, 2026-10-21), writes to 15507–15509 did not take effect: the mode did not switch and the reserves did not change. Re-tested 2026-10-23 with two independent tools (plain pymodbus, and the sequencer after the raw-write fix in #100): 15508 8→9, 15509 15→16 and 15507 2→3 were each acknowledged with a normal FC06 echo, and none changed within 30 s (90 s for the mode); 16001 stayed 8. All restored. Treat them as read-only.
  • The library writes only 15507–15509, through set_native_mode(), set_self_consumption_reserve() and set_tou_reserve(). Each attempts the write, reads back, and returns (ok, message) with the read-back result; a failed write is reported, not assumed. Use dry_run=True to preview.
  • connect() never writes. test_extension_writability() does: it writes test values to the mode and reserves, then restores them.
  • 15509 can only be read back as the TOU reserve on V12R02B60D00. On V10R01B04D00 it reads the same value as 15508. On V12R02B60D00, writes to it did not take effect (owner observation, 2026-10-21).

Not available over Modbus

Smart circuits, the generator, V2L and per-MPPT telemetry aren't in any register found so far. Use the FranklinWH app or the cloud API.