Cloud API vs Modbus TCP — Metrics Comparison

The same aGate can be read two ways:

  • Cloud API — this library, get_stats() over the FranklinWH cloud (getDeviceCompositeInfo, cmdType 203, result.runtimeData).
  • Modbus TCP Server (aGate :502) — read locally by a Modbus client such as franklinwh-modbus.

This page maps each metric across the two. franklinwh-modbus keeps its own copy of this table, linked to its own examples; the two are maintained separately on purpose: franklinwh-modbus — Modbus vs Cloud comparison (its API Cookbook and extension registers have the Modbus-side examples). Code examples for every cloud field are in the API Cookbook.

[!NOTE] Evidence (AP-14). Cloud names, units and signs are from this library's code (models.py, mixins/stats.py, const/modes.py). Modbus names are from franklinwh-modbus develop (controller.py). A mapping marked INFERRED or ASSUMED has not been confirmed by a side-by-side capture. One site's data is a candidate, not a rule.

Units and signs

Cloud API Modbus client
Power kW W
Energy kWh, daily (resets at local midnight — ASSUMED site-local) Wh, lifetime counters
Grid sign + import, − export + import (per franklinwh-modbus docs; unconfirmed on device)
Battery sign − charging, + discharging − charging

Grid sign on the cloud side was observed live on 2026-10-17: grid_use = −2.7 kW while exporting (solar 2.9 kW, home 0.2 kW).

Power and state

Metric Cloud (stats.current.…) Cloud raw key Modbus (franklinwh-modbus) Modbus source Notes
Solar power solar_production (kW) p_sun read_solar_status()['total_solar_w'], else ['ac_power_w'] (W) Extension total, else M502 OutPw
Generator power generator_production (kW) p_gen — — Not over Modbus
Battery power battery_use (kW) p_fhp read_battery_status()['battery_power_w'] (W) M714 DCW, summed over ports Modbus is DC side; whether p_fhp is AC or DC is unknown — INFERRED equivalent
Grid power grid_use (kW) p_uti read_grid_status()['grid_power_w'] (W) M701 W Same sign convention (see above)
Home load home_load (kW) p_load read_solar_status()['extension']['home_load_ext'] (W) Extension 16000 (~1 W), else 15506 (~100 W steps) 16000 is undocumented
Battery SoC battery_soc (%) soc read_battery_status()['soc'] (%) M713 SoC
Smart circuit / V2L power switch_1_load, switch_2_load, v2l_use (kW) cmdType 311 (not composite) — — Cloud only; extra MQTT call
Operating mode work_mode / work_mode_desc result.currentWorkMode (1 TOU, 2 Self-Consumption, 3 Emergency Backup) read_native_mode()['mode_name'] Extension 15507 Does not change during a remote dispatch — see VPP row
Active programme tou_mode / tou_mode_desc runtimeData.mode / .name — — A programme ID, not a run status
Run status run_status / run_status_desc runtimeData.run_status No direct register Nearest: DCW sign + deadband → charge / discharge / standby INFERRED mapping. Codes in RUN_STATUS
External control (VPP) tou_mode == 9, effective_mode == "VPP mode" runtimeData.mode = 9 Remote-control state See franklinwh-modbus VPP_MODE_REFERENCE.md Cloud showed mode 9 within a minute of a Modbus force discharge (one site, 2026-10-14) — VPP Mode
Grid connection grid_connection_state (4 states) Derived — see below read_grid_status()['connection_state'] (3 states) M701 ConnSt Closest raw cloud field: main_sw[0]

Grid connection — 4 cloud states vs 3 Modbus states

The cloud value is derived, not read from one field (Grid Connection State):

Cloud state How the library decides Modbus ConnSt
CONNECTED main_sw[0] == 1 (grid relay closed) Connected
OUTAGE offGridFlag set, or relay open and offgridState == 0 Disconnected — INFERRED
SIMULATED_OFF_GRID relay open (or offgridreason set) and selectOffgrid → offgridState == 1 Disconnected — INFERRED
NOT_GRID_TIED Site configured with no grid (startup flag) —

Modbus cannot tell a user-simulated island from a real outage; the cloud needs the extra selectOffgrid call to do it. Modbus Fault has no cloud counterpart identified.

Energy

Metric Cloud (stats.totals.…, daily kWh) Cloud raw key Modbus (lifetime Wh) Modbus source Notes
Solar solar kwh_sun — — Not over Modbus
Generator generator kwh_gen — — Not over Modbus
Grid import grid_import kwh_uti_in read_grid_status()['grid_import_wh'] M701 TotWhAbs Modbus daily = difference of two readings
Grid export grid_export kwh_uti_out read_grid_status()['grid_export_wh'] M701 TotWhInj As above
Battery charge battery_charge kwh_fhp_chg Not read by franklinwh-modbus yet M714 DCWhAbs Device has it
Battery discharge battery_discharge kwh_fhp_di Not read by franklinwh-modbus yet M714 DCWhInj Device has it
Home home_use kwh_load — — Not over Modbus

For a lifetime figure to compare with Modbus counters, use get_power_details(type=5, …) — see Historical Energy Data. Whether the cloud lifetime total and the Modbus counter agree has not been checked.

Modbus-only data

  • Battery: SoH, capacity (wh_rating, wh_available), DC current and temperature, per-battery breakdown.
  • Grid: voltage, frequency, VA, VAR, power factor, temperatures. (The cloud has some of these via get_stats(include_electrical=True) — cmdType 211, an extra MQTT call.)
  • Reserves: extension 15508 and 15509 (15509 repeats 15508 on current firmware).
  • Remote-control state and a partial read-quality flag.

Choosing a source

Cloud API Modbus TCP Server (aGate :502)
Network Internet + FranklinWH cloud Local LAN only
Concurrent clients Many (sharing the account's rate limit) One Modbus client at a time
Rate limits Yes — shared per account (Rate Limiting) None known
Daily totals, solar/home energy, programme name Yes No
Electrical detail, per-battery data Partial Yes
Tells simulated off-grid from outage Yes No