Short version: the FranklinWH API models everything as split-phase (L1 + L2), including single-phase installations where no L2 exists. On an AU/NZ system, L1 and L2 are not two independent legs — treat gridLineVol as the real measurement.

Evidence tiers per AP-14. Vendor citations carry a version and date — see VENDOR_DOCUMENTS.md. A claim sourced to "the datasheet" without a revision ages silently, and FranklinWH revises these: the Ethernet port naming already reversed meaning between two of them.

Sources used on this page

Claim Source Version / date
AU/NZ is 230/240 VAC L/N/PE, 50 Hz System Datasheet aGate X-01-AU & aPower X-02-AU V1.7, 2026-05-30
AU three-phase is 415 V same V1.7, 2026-05-30
Observed L1 119.7 / L2 119.7 / Line 239.4 at 49.93 Hz live AU gateway, user report 2026-09
US split-phase 120/240 V market standard + US datasheets — not observed, see DEF-AC-TOPOLOGY-NO-US-SAMPLE —

What the API reports

Every AC reading arrives with L1/L2 companions, regardless of what is actually installed:

Concern Fields
Grid voltage gridVol1, gridVol2, gridLineVol
Inverter invVolt1, invVolt2, invLineVol
Current gridCurr1, gridCurr2
BMS detail gridVoltAN, gridVoltBN, solarVoltAN, solarVoltBN

The A/B and 1/2 naming is split-phase vocabulary: two 120 V legs in antiphase summing to 240 V, which is the North American residential standard.

On a single-phase system this is a modelling artifact

OBSERVED on a live AU gateway (user report, 2026-09):

GRID VOLTAGES      INVERTER LINES      Frequency
  L1   119.7 V       L1   119.6 V        49.93 Hz
  L2   119.7 V       L2   119.6 V
  Line 239.4 V       Line 239.4 V

CONFIRMED — System Datasheet aGate X-01-AU & aPower X-02-AU, V1.7, issued 2026-05-30 (DS-AGATE-AU-V1.7 in VENDOR_DOCUMENTS.md): the AU/NZ system is 230/240 VAC L/N/PE, 50 Hz — line, neutral and protective earth. There is no second active conductor.

So the two "legs" are the API halving a single L-N measurement, or reporting the same measurement twice. 49.93 Hz confirms this is a 50 Hz installation, not a US one. L1 = 119.7 V does not mean the site has 120 V legs.

Consequences

  • Do not treat L1 and L2 as independent measurements on single-phase. They are not two circuits, and an alarm on "L2 low" has no physical referent.
  • Do not sum them. gridLineVol is already the L-N voltage. (This library performs no L1/L2 arithmetic anywhere — verified — so nothing currently double-counts. Keep it that way.)
  • gridLineVol is tenths of a volt — 2440 = 244.0 V. Handled in mixins/stats.py.

The three_phase flag is ambiguous

isThreePhaseInstall is a boolean, and models.py documents 0 as "split-phase". That is a US-centric reading: on an AU/NZ site, 0 means single-phase, which is a different topology.

So the library can distinguish three-phase from everything-else, but cannot distinguish split-phase from single-phase from that flag alone. Today the gap is bridged by region:

is_single_phase = not snap.flags.three_phase
is_au = snap.site.country_id == 3
if is_au and is_single_phase:   # ... treat as L-N, suppress L2

ASSUMED: that country_id == 3 implies single-phase. It holds for AU/NZ residential and matches the datasheet, but it is an inference from market, not a reading from the device. A US 208 V commercial installation, or any market added later, would not be covered.

Current handling is inconsistent

Surface Single-phase aware?
discover Yes — labels "Voltage"/"Current", suppresses L2 for AU
diag Partial — says "Single Phase (L1)" but renders L1/L2 elsewhere
bms No — always "Grid Feed (L1/L2)", "Inv Bus (L1/L2)"
support No — emits grid_voltage_l1_v / _l2_v unconditionally
schema No — lists both with no topology note

discover got this right and the rest were never updated. Tracked as DEF-AC-TOPOLOGY-INCONSISTENT.

Guidance

Reading: on single-phase, use gridLineVol / invLineVol. Ignore the per-leg values, or present them explicitly as an API artifact.

Building automations: do not alarm on per-leg imbalance on single-phase — the legs are derived, so imbalance is meaningless. Frequency and line voltage are the meaningful grid-quality signals.

Three-phase: isThreePhaseInstall == 1. How L1/L2/L3 map onto these two-leg fields is not established — no three-phase capture exists in the corpus. Do not assume L1/L2 carry two of the three phases.

The pattern: a split-phase-first data model

Added 2026-09-15. INFERRED — this is a reading of accumulated evidence, not a vendor statement. It is recorded because it explains, in one shape, a set of defects filed separately.

The API appears to model a North American split-phase installation as the baseline, with other markets expressed as that model constrained. Evidence, each item filed as its own ticket:

Observation Ticket
Every AC reading is an L1/L2 pair, including where no second conductor exists DEF-AC-TOPOLOGY-INCONSISTENT
isThreePhaseInstall is a boolean, so single-phase and split-phase are indistinguishable DEF-PHASE-FLAG-AMBIGUOUS
nemType: 0 maps to a Californian tariff scheme on an Australian gateway DEF-NEM-TYPE-ZERO-UNRESOLVED
US-utility programme flags (sgipEntrance, bbEntrance, ja12Entrance, sdcpFlag) are present on non-US gateways DEF-SDCP-MEANING-UNSOURCED
The CarSW/V2L channel reports live telemetry on AU hardware while the feature flag stays off DEF-AU-V2L-HARDCODED-FALSE
aHub is 120/240 Vac 60 Hz — North America only — yet is the accessory carrying 4-8 circuits DEF-CATALOG-AHUB-CIRCUIT-COUNT
Vendor port naming differs by hardware revision, with the AU line on the oldest DEF-ETH-PORT-IDENTITY-UNCONFIRMED

Documentation is localised per market — the AU guides speak in 230/240 VAC L/N/PE at 50 Hz and never mention split-phase, while the US ones use 120/240, 60 Hz, L1/L2 and 208 V. The wire protocol is not localised in the same way. An AU gateway is handed the US field set and leaves the inapplicable parts null, zero, or — in the CarSW case — quietly populated.

Why this matters for callers

  1. Prefer what the device reports over what the market implies. The reverse produced DEF-AU-V2L-HARDCODED-FALSE, where a regional assumption discarded the gateway's own answer.
  2. A field being present says nothing about it applying. sdcpFlag exists on gateways thousands of kilometres from San Diego.
  3. A US-shaped default is not a neutral default. nemType: 0 → "NEM 2.0" is confidently wrong outside California, and being non-empty made it harder to notice than a blank would have been.

What would change this reading

A vendor statement about the data model, or a US capture showing the same fields behaving differently there. ASSUMED until then: this is a pattern across observations, and a pattern is not a specification. Every individual ticket above stands on its own evidence and does not depend on this section being right.

Not established

  • Whether single-phase L1/L2 are a halved measurement or the same value reported twice. The observed values are equal to 0.1 V, which is consistent with either.
  • Whether any field distinguishes split-phase from single-phase directly, removing the need for the region inference.
  • How three-phase sites populate these fields.
  • Whether 208 V US commercial installs behave as split-phase here.