Firmware map — what changed between two aGate releases

Status: WORKING DRAFT. This is the evidence as it stands, written down so the permanent version can be formulated from something real rather than from memory. Structure and wording are provisional; the measurements are not.

Scope: one aGate, one site. Everything here is the reference AU gateway (SyHdVersion 102 = AGT-R1V1-AU, "aGate X-01-AU"), single aPower. One site on one upgrade path is not a release map for the product — it is two points on one device. Nothing here should be read as "FranklinWH changed X in release Y".

Earlier IBG_VER V12R02B30D06_260304 — from a packet capture of the official app
Later IBG_VER V12R02B60D00_260924 — from a read on 2026-10-31
Apart roughly six months
Hardware identical. Nothing swapped between the two.

1. The headline: the wire protocol version changed

protocolVer   V1.11.03  ->  V1.12.02

This is the finding that explains the others. Both commands known to have changed their key set did so across this boundary. If a key set varies, protocolVer is the field most likely to predict it — more so than IBG_VER, which moves for reasons that do not affect the wire.

Unverified: that protocolVer causes or reliably signals key-set changes. Two commands across one upgrade is a correlation, not a rule. But it is the right field to record and to test against.

Note this library's login sends minProtocolVer: "V1.00.00", and both firmwares accepted it. There is no evidence the gateway refuses an old minimum.

2. Component versions — measured, complete for 1102

All from the 1102 login manifest, both sides. Serials excluded.

Field Earlier Later
protocolVer V1.11.03 V1.12.02 changed
IBG_VER V12R02B30D06_260304 V12R02B60D00_260924 changed
APP_VER V12R00B07D04_260205 V12R00B16D00_260825 changed
AWS_VER V12R00B06D04_260304 V12R00B15D00_260918 changed
SL_VER V12R02B07D81 V12R02B12D00 changed
BMS_VER ['V11R50B03D00'] ['V11R50B07D00'] changed
DCDC_VER ['V12R02B07D01'] ['V12R02B10D00'] changed
INV_VER ['V12R02B09D03'] ['V12R02B15D00'] changed
FPGA_VER ['V12R01B00D00'] ['V12R01B00D00'] unchanged
TH_VER ['V11R02B01D00'] ['V11R02B01D00'] unchanged
BL_VER ['V11R06B00D00'] ['V11R06B00D00'] unchanged
METER_VER V12R00B11D00 V12R00B11D00 unchanged
SyHdVersion 102 102 unchanged
deviceType 0 0 unchanged
FHP_NUM 1 1 unchanged
threePhasePvPower 0 0 unchanged

Seven of eleven component versions moved; four did not. An OTA is not monolithic — the FPGA, thermal, bootloader and meter firmware stayed put while the controller, app, cloud agent, BMS, DC-DC and inverter all advanced.

SyHdVersion and deviceType did not move, which is consistent with them identifying hardware rather than firmware. Two readings on one device; not proof.

Version string shape (inferred)

V{major}R{revision}B{build}D{patch} with an optional _{YYMMDD} build date:

  • V12R02B30D06_260304 → 2026-03-04; V12R02B60D00_260924 → 2026-09-24.
  • The date suffix appears only on IBG_VER, APP_VER and AWS_VER — the component versions carry none.
  • Each component dates independently: at the earlier reading APP_VER was _260205 while IBG_VER and AWS_VER were _260304.

Inferred from eight strings on one device. The D field is read as a patch number because D81 → D00 alongside a build increase (B07 → B12) resembles a reset, but nothing confirms the letters' meaning.

3. Key-set changes — two commands, both confirmed

1102 login manifest: 23 keys → 27 keys

Added (all per-unit lists, all reading a single element on this one-aPower site):

PE_HW_VER [2]   BMS_MAIN_HW_VER [0]   BMS_BL_HW_VER [0]   BMS_TH_HW_VER [0]

Removed: none. The change is purely additive.

PE_HW_VER reading [2] is interesting but not established: apower_models[2] in franklinwh-cloud's catalogue is APR-05K13V1-AU, "aPower X-01-AU", which fits an AU site. That PE_HW_VER indexes that table is inferred — aGate codes run 100–104 and aPower codes 0–7, two separate spaces, and a hardware-revision field that happened to read 2 would look identical.

1701/1702 install profile: gridImportLimit absent → present

Earlier, 21 keys, no gridImportLimit, across four replies:

airSwitchCur  electricSupply  electricSys  fhpRatePower  genRatePower
gridExportEnable  gridHardLimit  gridPhaseConSet  gridPhaseSeqSet  gridSoftLimit
isPcsDischgEn  isThreePhaseInstall  kwRatePower  ratedGridHz  ratedGridVolt
solarInstallState  solarInvManu  solarInvRatePower  opt  result  reason

Later: gridImportLimit present, reading -1. Partial evidence — that is a single field reported by the Direct Connect Bridge session from a raw read on 2026-10-24, not a full 1702 of my own. The rest of the later key set is unknown.


4. What this document cannot tell you

The comparison is complete for 1102 only. Both sides exist for exactly one command.

Earlier firmware Later firmware
1102 full full
1702 full (21 keys) one key, third-party
the other 30 cmdTypes full nothing

The capture holds 32 cmdTypes: 1101/1102, 1109/1110, 1111/1112, 1113/1114, 1117/1118, 1119/1120, 1301/1302, 1409/1410, 1411/1412, 1701/1702, 1723/1724, 1725/1726, 1727/1728, 1829/1830, 1901/1902, 1903/1904. For every one of those except 1102 there is no later-firmware reading at all, so this document cannot say whether they changed. Absence of a reported change is not evidence of no change.

Also absent from both sides: 1105/1106 device_check, 1709/1710 relay_status, 1831/1832 battery_modules, 1303/1304 energy_history, 1407/1408 tou_schedule, 1707/1708 ibg_run_status. Never exercised by the recorded app session.

5. What would complete it

One read-only session on the current firmware, capturing the same 32 cmdTypes the earlier capture holds, would turn a one-command comparison into a real map. It needs the owner's go-ahead and the aGate roll call, and it is a read throughout — no opt:1 anywhere.

Until then the honest summary is: the protocol version moved, four keys were added to the login manifest, one key was added to the install profile, and seven of eleven component firmwares advanced. Everything else is unobserved.


Evidence: a packet capture of the official app against the reference aGate (V12R02B30D06_260304), and an owner-approved read-only login on 2026-10-31 (V12R02B60D00_260924). No serials, no site identifiers. The capture became readable only after the pcap decoder was fixed — before that it decoded 12 frames of 335 and reported success, so any earlier conclusion drawn from it is suspect.