Virtual Mode Specifications & Validation Targets

Purpose: Define what each mode does, power sources, load priorities, and validation targets for hardware testing.
Last Updated: 2026-03-12
References: Understanding Operating Modes, Emergency Backup, Time of Use, System Operation Mode


⚠️ Primary Constraint: FranklinWH Modbus TCP Implementation

Everything in this document is shaped by what the aGate actually exposes via Modbus TCP:

Capability Status Detail
Read battery state SoC, power, voltage, temp, energy (M713, M714)
Read grid/solar/inverter Power, voltage, frequency, status (M701, M502)
Read aGate native mode Ext.15507 (Emergency/Self-Consumption/TOU/Manual) — read-only
Write battery power M704 WSetPct, WSet, WSetEna — the ONLY writable control
Change operating mode Ext.15507 is read-only without SPAN Modbus unlock
Control reserve SoC Ext.15508-15509 are read-only without SPAN unlock
Control solar PV No writable registers for PV curtailment or production
Control smart circuits Not exposed via Modbus TCP at all
See generator/V2L Not exposed via Modbus TCP
Hardware reversion timer WSetRvrtTms accepted but never executes (quirk)
Hardware heartbeat ControllerHb silently ignored (quirk)

[!CAUTION] Our ONLY control lever is M704 battery power commands. Everything else — mode, reserves, solar, smart circuits, load shedding — is either read-only or invisible. All virtual modes are constrained to: "tell the battery how many watts to charge or discharge." The aGate's native mode runs in parallel and resumes the instant we release control.


FranklinWH aGate X — System Architecture

Power Sources

Source On-Grid Off-Grid Modbus Visible Controllable via M704
Solar PV (Proximal) M502.OutPw, Ext.15502-15503 ❌ (read-only)
Solar PV (Remote via aPbox/aHub) Ext.15504-15505 ❌ (read-only)
Grid M701.W Indirect (via battery charge/discharge)
Generator ❌ (not visible via Modbus TCP)
V2L (Vehicle-to-Load) ❌ (not visible via Modbus TCP)
Battery (aPower) M714.DCW, M713.SoC ✅ M704 WSetPct/WSet

AC Input/Output Capacity

Interface Rating Notes
AC Input 1 (Solar/Grid) 63A / circuit Proximal PV or grid
AC Input 2 (Solar/Grid) 63A / circuit Proximal PV or grid
Max Inverter Power 5000W continuous M703.WRtg
Max Charge Rate 5000W M703.MaxChaRte
Max Discharge Rate 5000W M703.MaxDisChaRte
Smart Circuits 2–3 per aGate ⚠️ NOT visible via Modbus TCP

Curtailment

Scenario Condition What Happens
On-Grid: Battery Full SoC = 100%, excess solar Excess exported to grid (if export allowed)
On-Grid: Export Restricted Grid export disabled by utility Solar production curtailed by aGate
Off-Grid: Battery Full SoC = 100%, excess solar aGate curtails solar (shuts down PV production)
Off-Grid: Overload Home load > inverter + battery capacity aGate load-sheds (Smart Circuits first)
PV Capacity Limit Solar > 2× AC input (10kW+) Hardware limit, not software-controllable

Smart Circuits are controlled by the aGate firmware and are NOT visible or controllable via Modbus TCP. They appear in the FranklinWH app only.


Two Control Layers

The FranklinWH system has two independent control layers running in parallel:

Layer Source Registers Can We Change?
aGate Native FranklinWH Cloud/App Ext.15507 (OnGridMode) ❌ Read-only without SPAN Modbus unlock
Virtual (Ours) modes.py via M704 WSetEna, WSetPct, WSet ✅ Always writable

Our virtual modes override the aGate's native battery behavior by sending M704 power commands every 5 seconds. The native mode keeps running in the background — when we release control (--stop), the aGate resumes its native mode immediately.

[!IMPORTANT] We can only control battery charge/discharge power via M704. We CANNOT: - Change the aGate's operating mode (Ext.15507) without SPAN unlock - Control Smart Circuit load shedding - Directly control solar PV production or curtailment - Control grid import/export limits (only indirect via battery)


aGate Native Modes (Ext.15507 — Read Only)

These are what the FranklinWH app sets. We can READ them but not WRITE them (without SPAN Modbus unlock).

Mode 0: Emergency Backup

Aspect Behavior
Intent Keep battery at 100% for outage resilience
Load Priority 1. Solar → Home, 2. Grid → Home, 3. Solar → Battery, 4. Grid → Battery
Battery Charges to 100% from solar + grid. Does NOT discharge for self-consumption.
Grid (on-grid) Primary power source for home loads. Battery held in reserve.
Off-Grid Battery powers home. Solar recharges battery (curtails if full).
Ext.15507 0

Mode 1: Self-Consumption

Aspect Behavior
Intent Maximize solar self-use, minimize grid import
Load Priority 1. Solar → Home, 2. Solar → Battery, 3. Battery → Home, 4. Grid → Home (last resort)
Battery Charges from excess solar. Discharges to cover home load when solar insufficient.
Grid (on-grid) Import only when battery depleted AND solar insufficient. Export excess when battery full.
Off-Grid Battery + solar power home. Solar curtailed if battery full.
Reserve User-configurable reserve % (Ext.15508). Battery won't discharge below reserve.
Ext.15507 2

Mode 2: Time-of-Use (TOU)

Aspect Behavior
Intent Arbitrage — charge off-peak, discharge on-peak
Load Priority (On-Peak) 1. Solar → Home, 2. Battery → Home, 3. Grid → Home (avoid)
Load Priority (Off-Peak) 1. Solar → Home, 2. Solar → Battery, 3. Grid → Battery, 4. Grid → Home
Battery (On-Peak) Discharges to power home, avoiding expensive grid import
Battery (Off-Peak) Charges from solar + cheap grid power
Grid Minimize import during peak. Allow import during off-peak.
Schedule User defines: Super Off-Peak, Off-Peak, Mid-Peak, On-Peak periods
Reserve User-configurable reserve % (Ext.15509). Battery won't discharge below.
Ext.15507 1

Mode 3: Manual

Aspect Behavior
Intent User/API-directed battery behavior
Ext.15507 3

Virtual Modes: Battery Orchestration Plans

The Reality: Native FranklinWH Operating Modes (set via the mobile app) are comprehensive ecosystem orchestration plans. They control battery behavior, grid import/export permissions, smart circuit load shedding, and generator triggers simultaneously.

Because the Modbus TCP interface ONLY provides access to M704 Battery Power, our Virtual Modes are merely battery orchestration plans. They emulate the core battery behavior of the native modes, but cannot touch the wider ecosystem.

These modes run in our software (modes.py) and send continuous M704 power setpoints every 5 seconds. They override the aGate's native battery behavior but nothing else.

Load Priority Reference

How each virtual mode prioritizes power sources for covering home load:

Priority Self-Consumption Emergency Backup Grid Zero Peak Shave TOU (On-Peak) TOU (Off-Peak) Manual
1st Solar Solar+Grid→Battery Solar Solar Solar Solar→Battery User-set
2nd Battery discharge Hold at target Battery discharge Idle (<threshold) Battery discharge Grid→Battery
3rd Grid import Idle (no discharge) — (target=0W grid) Battery (>threshold) Grid import Grid→Home
4th Grid import

1. self_consumption — Default Mode

Emulation Target: FranklinWH Native Self-Consumption (Ext.15507=2)
Emulation Fidelity: Partial. We calculate net load and direct the battery to cover it, successfully minimizing grid import. However, if the home load exceeds inverter capacity off-grid, the native mode drops Smart Circuits; our virtual mode cannot, leading to an abrupt microgrid collapse.

Power Flow (Our Implementation):

IF SoC >= target_soc + self_reserve:
    excess_solar = solar - home
    IF excess_solar > 0: charge from excess solar (up to max)
    IF excess_solar < 0: discharge to cover shortfall
    IF excess_solar = 0: idle
ELSE:
    FULL POWER CHARGE from grid+solar (to reach target ASAP)

Validation Targets: - [ ] Night, SoC < target: charge at max from grid - [ ] Night, SoC ≥ target: discharge to cover home load - [ ] Day, excess solar: charge from excess only - [ ] SoC at reserve: stop discharging


2. emergency_backup — Keep Battery Full

Emulation Target: FranklinWH Native Emergency Backup (Ext.15507=0)
Emulation Fidelity: Partial. We successfully hold the battery at 100% and aggressively prevent discharging to the home. However, the native mode also triggers the Generator (if installed) during an outage to keep the battery topped up. We cannot trigger the generator via Modbus.

Power Flow:

IF SoC >= target: idle (0W) — do NOT discharge
ELSE: charge proportionally (higher power when further from target)

Validation Targets: - [ ] SoC < target: charge at high power - [ ] SoC ≥ target: idle (0W, no discharge even with home load) - [ ] Key: battery never discharges to cover home load on-grid


3. grid_zero — Minimize Grid Interaction

Emulation Target: None (Custom Mode)
Emulation Fidelity: N/A. This is a purely custom orchestration plan that tries to zero-out the grid meter by directly reacting to M701.W (Grid Power) rather than relying on solar projections. It has no native equivalent.

Power Flow:

net_load = home - solar
IF net_load > 0: discharge to cover (grid import → 0W)
IF net_load < 0 AND SoC < target: charge from excess (grid export → 0W)
IF net_load < 0 AND SoC >= target: idle (excess exports)

Validation Targets: - [ ] Home > solar: M701.W near 0W (battery discharging) - [ ] Solar > home: M701.W near 0W (battery absorbing excess)


4. peak_shave — Reduce Peak Grid Demand

Emulation Target: None (Custom Mode)
Emulation Fidelity: N/A. This is a purely custom orchestration plan designed to shave utility demand-charge spikes. It has no native equivalent.

Power Flow:

IF home > threshold AND SoC > min + 5%:
    discharge = home - threshold (cap at max_discharge)
ELSE: idle (0W)

Validation Targets: - [ ] Home < threshold: battery idle - [ ] Home > threshold: battery discharges (threshold - home), grid caps at threshold


5. time_of_use — Schedule-Based Arbitrage

Emulation Target: FranklinWH Native TOU (Ext.15507=1)
Emulation Fidelity: Partial / Experimental. We parse the TOU JSON schedule and force the battery to charge/discharge at the correct times. However, the native mode perfectly orchestrates solar curtailment and grid export limits during Peak periods. Our virtual mode must rely purely on aggressive battery discharging, which can sometimes "fight" the native grid topology.

Power Flow:

strategy = schedule.get_strategy()  // "charge", "discharge", "grid_zero", "solar_priority"

"charge":    charge at max (solar + grid)
"discharge": discharge to cover home load
"grid_zero": → grid_zero algorithm
"solar_priority": charge from solar only, else self_consumption

Validation Targets: - [ ] During "charge" period: battery charges - [ ] During "discharge" period: battery discharges - [ ] Period transition: switches behavior at boundary


6. manual — Direct Power Control

Emulation Target: Cloud API Standby/Forced Charge/Discharge
Emulation Fidelity: Full. This directly commands the battery at a specific wattage. It is the purest and most reliable Modbus mode, completely mirroring the Cloud API's manual overrides.

Power Flow: return manual_power_w

Validation Targets: - [x] Positive → CHARGING (validated 2026-03-12) - [x] Negative → DISCHARGING (validated 2026-03-12) - [ ] Zero → IDLE


Safety Systems (All Modes)

Safety Trigger Action
SoC Hard Limit SoC ≥ 99.5% or ≤ 0.5% Block command
SoC Ramp Within 10% of limit Linearly reduce power
Inverter Limit Power > 5000W Cap at rated max
Load Safety Home > 90% of capacity Reduce discharge
Alarm Block Blocking alarms active Stop operation

Hardware Validation Plan

Tier 2 Tests (Pre-Approved, ≤500W, ≤30s)

# Test CLI Command Expect Verify
1 Manual charge --charge 500 CHARGING M714.DCW positive ✅
2 Manual discharge --discharge 500 DISCHARGING M714.DCW negative ✅
3 Manual idle --mode manual --power 0 IDLE M714.DCW ~0W
4 Self-consumption (below target) --mode self_consumption --target-soc 99 CHARGING max Grid importing
5 Self-consumption (above target) --mode self_consumption --target-soc 50 DISCHARGING Grid reduced
6 Emergency backup (below target) --mode emergency_backup --target-soc 99 CHARGING Grid importing
7 Emergency backup (above target) --mode emergency_backup --target-soc 50 IDLE (0W) No discharge
8 Grid zero --mode grid_zero Varies M701.W near 0W
9 Peak shave (below threshold) --mode peak_shave IDLE No battery

Post-Each-Test (Mandatory)

python3 tools/franklinwh_cli.py -i YOUR_AGATE_IP --stop
python3 tools/franklinwh_cli.py -i YOUR_AGATE_IP --healthcheck | grep zombie_state